
Safety Instructions
1. The unit may be used only in the operating conditions and positions specified by the manufacturer.
The R&S FSH is protected against dripping water and dust (IP degree 51). Unless otherwise
agreed, the following applies : pollution severity 2, overvoltage category 2, altitude max. 2000 m
powered from AC power supply, altitude max. 3000 m powered from battery.
The unit may be operated only from supply networks fused with max. 16 A.
Unless specified otherwise in the data sheet, a tolerance of ±10% shall apply to the nominal
voltage and of ±5% to the nominal frequency.
2. For measurements in circuits with voltages Vrms > 30 V, suitable measures should be taken to
avoid any hazards (using, for example, appropriate measuring equipment, fusing, current limiting,
electrical separation, insulation).
3. For permanently installed units without built-in fuses, circuit breakers or similar protective devices,
the supply circuit must be fused such as to provide suitable protection for the users and
equipment.
4. Prior to switching on the unit, it must be ensured that the nominal voltage set on the unit matches
the nominal voltage of the AC supply network.
If a different voltage is to be set, the power fuse of the unit may have to be changed accordingly.
5. If the unit has no power switch for disconnection from the AC supply, the plug of the connecting
cable is regarded as the disconnecting device. In such cases it must be ensured that the power
plug is easily reachable and accessible at all times (length of connecting cable approx. 2 m).
Functional or electronic switches are not suitable for providing disconnection from the AC supply.
If units without power switches are integrated in racks or systems, a disconnecting device must be
provided at system level.
6. Applicable local or national safety regulations and rules for the prevention of accidents must be
observed in all work performed.
Prior to performing any work on the unit or opening the unit, the latter must be disconnected from
the supply network.
Any adjustments, replacements of parts, maintenance or repair may be carried out only by
authorized R&S technical personnel.
Only original parts may be used for replacing parts relevant to safety (eg power switches, power
transformers, fuses). A safety test must be performed after each replacement of parts relevant to
safety.
(visual inspection, PE conductor test, insulation-resistance, leakage-current measurement,
functional test).
7. Ensure that the connections with information technology equipment comply with IEC950 /
EN60950.
8. NiMH batteries must not be exposed to high temperatures or fire.
Keep batteries away from children.
If the battery is replaced improperly, there is danger of explosion. Only replace the battery by R&S
type (see spare part list).
NiMH batteries are suitable for environmentally-friendly disposal or specialized recycling. Dispose
them into appropriate containers, only.
Do not short-circuit the battery.
9. Equipment returned or sent in for repair must be packed in the original packing or in packing with
electrostatic and mechanical protection.
10. Electrostatics via the connectors may damage the equipment. For the safe handling and operation
of the equipment, appropriate measures against electrostatics should be implemented.
11. The outside of the instrument is suitably cleaned using a soft, lint-free dustcloth. Never use
solvents such as thinners, acetone and similar things, as they may damage the front panel
labeling or plastic parts.
12. Any additional safety instructions given in this manual are also to be observed.