RS Securit 7 User manual

Introduction
The Securit 7 is a microprocessor controlled intruder alarm
panel. It features seven zones of which five are programmable
and two dedicated to entry/exit and personal attack. A non-
volatile memory holds the programming options and the 18
event log. These will be retained even in the event of total
power loss. The panel utilises a blind control box, remote
programming and control keypad. The system is designed to
be simple to program and allow flexibility in use.
Note: Before proceeding with installation read this document
thoroughly.
System planning
To enable the installation to proceed smoothly it is best to plan
the work before you begin. Start by drawing a plan of the
building to be protected (see figures 1 and 2). You will need to
divide the building into zones. Zone 1 is always used as the
final exit zone with the securit 7 panel.
The system layouts shown are a guide to typical positions of
the system components. This will obviously vary depending on
the premises and the level of protection to be afforded.
However, the general rules given cover all installation layouts.
General rules
1. Final exit doors should have magnetic contact switches
fitted to ensure that the premises cannot be vacated with
the doors left open and also to protect against forced entry.
2. PIR detectors are best fitted where an intruder has to pass
through an area to gain access (i.e. halls and landings) or
to protect specific valuable items (i.e. office, lounge). Care
should be taken in siting to avoid direct sunlight, strong
lighting and heat sources (hence the vibration detectors in
the kitchen) as these may cause nuisance tripping. They
are best sited so the intruder cuts across the field of view,
see figure 1 (some products are specifically designed for
long corridors in this instance this rule does not apply),
hence a corner position is usually adopted.
3. PIR, ultrasonic, vibration detectors, etc. all have complex
electronics. These are best given their own zone as in the
event of a fault occurring isolating the fault will be quicker
and nuisance tripping quickly eliminated. Magnetic door
contacts tend to be very reliable if installed well within their
magnetic actuation limit. Hence these can be put in series
together on a loop if appropriate. They are also easier to
test if faulty.
4. Wiring is best concealed where possible to prevent
damage and tampering. Try to avoid running along side
mains cables as interference may occur.
5. The sound/strobe unit should be fitted well above head
height to avoid tampering. The wiring should pass directly
through the wall behind the bell to make it inaccessible.
6. The control panel requires a 240V power source. An
unswitched fused spur preferably direct from the consumer
unit on its own fuse wired in accordance with the current
IEE regulations should be provided.
Using the above general rules you should plan your installation
on your sketched drawing considering the panel siting, how the
cable runs can be minimised, where different types of detector
will be fitted and which zone they will be on. When you have
finalised your plan you can begin installation.
Mounting the control panel and keypad
Control panel
1. Remove the lid screws.
2. Disconnect the a.c. lead from the PCB (see figure 5).
3. Gently pull the PCB from its nylon mounts.
4. Offer the panel up to the wall and mark the holes.
5. Using suitable fixings for the wall material, fix the panel to
the wall.
Securit 7 Alarm Panel
Stock No. 436-881
Garage
Kitchen
Dining
Room
Lounge
Hall
A A
BC
D
E
CC
F
GG
G
H
I
J
K
L
Figure 1. Ground floor view of a domestic premises
Office
Factory
Lobby
Accounts
A
B
C
D
E
F
GG
H
I
J
K
L
A
Figure 2. Ground floor view of a commercial premises
A. Magnetic door contact zone 1
B. Zone 2
C. Zone 3
D. Magnetic door contact zone 4
E. Zone 5
F. Zone 6 may be a PIR on the
first floor landing
G. PIR
H. Siren
I. Personal attack switch
J. Vibration detector
K. Keypad
L. Control panel
Note: Alarm control panel should
be located within the
protected area
A. Magnetic contact zone 1
B. Zone 2
C. Dual tech zone 3
D. Seismic detector zone 4
E. Zone 5
F. Zone 6
G. PIR
H. Siren
I. Personal attack switch
J. Keypad
K. Control panel
L. Additional keypad

Keypad
1. Pushing a terminal screwdriver into the slot on the right-
hand side of the keypad to release the back plate.
2. Mark the wall using the holes at the left and right-hand side
of the back plate. Also mark the large cable entry hole.
3. Fix the back plate to the wall using suitable fixings for the
wall material.
Note: The cable entry hole should also be made if
applicable.
Wiring
Keypad
Install a 6-core cable (RS stock no. 365-587) between the
panel and the keypad. Connect units as shown in figure 3.
Note: If the tamper circuit is used throughout the installation it
is recommended that an additional connector block
(such as RS stock no. 423-655) be used to loop the
tamper circuit between zones (see figure 4 for wiring
details).
Mains
A mains supply should be connected via an unswitched 3A
fused spur wired in accordance with the current IEE
regulations. The mains unit cable should be brought in a
separate entry to the panel to the low voltage cables. If in
doubt consult a qualified electrician.
At this stage it is worth checking the panel for correct operation,
this can be done as follows:
1. Check that the terminals marked Ô24 hour tamper, 1, 2, 3,
4, 5, 6 and PAÕ have loop connections as shown below:
Screw the lid on the control panel.
2. Switch on the mains.
3. Enter Ô1234Õ the buzzer will emit a steady sound and the
exit time start. Press the Ô*Õ key followed by the Ô9Õ key.
The exit buzzer will stop and all LEDs will light. After the
10 seconds LED test the internal sounder, which will
operate for 5 seconds, the control will then emit an accept
tone and revert to the ÔDAYÕ mode. You may end the test
at any time by pressing the Ô*Õ key.
4. The test is now complete.
5. Should the above not occur re-check your wiring and
repeat steps 1. to 4.
D
BELL
ST
SPK AUX L ID D C
R S 12 3 4 56PA
24 HR
TAMPER
A
C
TAMPER 12V
B C
D
LINK 1
Figure 3. Keypad connections
12 3 4 56PA
24 HR
TAMPER
Figure 4.
*
TamperPA
* * *
Power
supply
Tamper
detect
N/C N/C
BELL
ST
SPK AUX L ID D C
R S 123456PA
24 HR
TAMPER
A
B
C
D
E
F
G
H
I I
J
K
M
L
O
T
Figure 5. Control panel detector connections
A. Securit 7 control panel
B. Tamper switch
C. Bleeper
D. Remote keypad
A. Securit 7 control panel
B. AC lead connection
C. Link 2 memory default
D. Battery fuse 1A
E. Auxiliary 12V supply for PIRs etc.
F. Link 1 (remove this link for panel tamper)
G. Part set volume
H. 6-core cable
I. Additional tamper connectors
J. Passive infrared detector zone 1
K 4-core cable
L. Zone 3
M. Magnetic contacts N/C
N. Personal attack switch
*Additional zone loops show detector normally closed contacts only for clarity
N

Detectors
The detection circuits consist of 2 series loops, (see figure 6).
The actual detection zone and the 24 hour tamper loop. The
detectors have normally closed contacts that break the series
loop in the event of an alarm or a device being tampered with.
Hence when wiring to a passive infrared (PIR) or vibration
detector or any other electronic detection device 6-core cable
(RS stock no. 365-587) is required to provide zone, 24 hour
and 12V power for magnetic door contacts.
A 4-core cable (RS stock no. 365-571) would be required.
Where a mixture of detectors are used 6-core can be used
throughout and 2-cores ignored for magnetic contacts. Figure
5 illustrates typical connections.
For detectors in the RS product range run the required cable to
each detector and connect up as illustrated.
Testing
Replace the lid on the control panel. Switch the mains on. If
the internal sounder sounds and the ÔTamperÕ LED is lit on the
keypad then there is a break in the tamper series circuit.
Check the covers on all detectors, keypads and control panel to
ensure that the tamper switches are operating. If this does not
cure the fault re-check the tamper wiring connections.
The test procedure is as follows:
1. Type Ô1234Õ into the keypad, the exit time buzzer will begin.
2. Before the exit times out press Ô*Õ followed by Ô9Õ and Ô4Õ.
The buzzer will emit a low level steady tone.
3. Walk around to each detector and check for operation. The
keypad will give a loud pulsing tone to indicate correct
operation and the zone number LED will light whilst the
detector is operated.
4. When the test is over press the Ô*Õ key to finish.
Should any detector not operate at the end of the test re-check
your wiring and re-test.
Sounder/strobe connections
The sounder strobe wiring should now be installed.
Connections for the RS range of units are given in figure 7.
The installation and testing of these units should be as the
included instructions with each sounder/strobe unit.
Internal sounder (speakers)
The control panel is not fitted with a speaker in the box. If
internal speakers are required they should be connected to the
terminals marked SPEAKER (see figure 6). A maximum of two
16½ speakers may be fitted in parallel.
Programming
Programming of the panel can be divided into ÕuserÕ and
ÔengineerÕ programming facilities. The user facilities are those
that may need to be changed in day to day use of the panel
and the engineer facilities are those that will be set up when the
alarm is initially installed. The panel is also set up initially with
factory default settings, these are listed below.
Factory defaults
User/customer code 1 1234
User/customer code 2 Disabled (0000)
Engineer code 7890
Circuit 1 Entry circuit (fixed)
Circuit 2 Alarm circuit isolated in part set
Circuit 3 Alarm circuit
Circuit 4 Alarm circuit
Circuit 5 Alarm circuit
Circuit 6 Alarm circuit
Circuit 7 PA circuit (fixed)
Full set exit time 30 seconds
Part set exit time 15 seconds
Entry time 30 seconds
Bell ring time 15 minutes
Chimes Disabled
User programming
These are functions alterable whilst the panel is unset or by
using the user code.
Changing the user code
There are two separate user codes available. At default the
second user code will be disabled.
1 Master user
2 Second user
Enter the four digit user code, the buzzer will emit a steady
sound and the exit time start. Press the Ô*Õ key followed by the
Ô9Õ key, followed by the key for the user to be altered. The
LEDs 1, 2, 3 and 4 will now come on to indicate a new 4 digit
code is required. Enter your new code. As you press each key
one LED will go out. If your new code is allowed an accept
tone will be given. If the new code is barred an error tone will
be given and your old code will still be valid. Start again and
enter a different four digit code.
B
3
2
1
24 HR
TAMPER
A
U
X
etc.
N/C
N/C
N/C
N/C
N/C
N/C
N/C
N/C
12V
A
B
Figure 6. Schematic diagram of detector connections
BELL
ST
SPK AUX L ID D C
R S
A
RS
stock no.
740-427 Ret sig 0V
740-433 Ret sig 0V
437-660 Return -Ve
Siren
trig.
Strobe
trig.
Siren
trig.
Strobe
trig.
SW
-Ve N/A
+Ve
+Ve
+Ve
B
C
D
E
Figure 7. Sounder/strobe unit connections
A. Magnetic contact
B. PIR
A. Securit 7 control panel
B. AC indicator
C. Battery
D. 2 x 16½ speakers max.
E. RS sounder/strobe
connections

To remove or disable a second user code enter the four digit
user code, the buzzer will emit a steady sound and the exit time
start. Press the Ô*Õ key followed by the Ô9Õ key followed by the Ô2Õ
key. The LEDs 1, 2, 3 and 4 will come on to indicate a new 4
digit code is required. Enter Ô0-0-0-0Õ (four zero keys). As you
press each key one LED will go out. After the last key an accept
tone will be given and the second user code will be disabled.
Chime zones
During the day there may be an area in the building that you
would want to know the presence of a person (e.g. garage)
without setting the alarm. This can be done using the chime
setting. When the detector in the chime zone is activated the
keypad will chime. This can be set as follows:
Whilst the panel is unset press the Ô*Õ key the display will show
the zones currently in chime mode. Press the key number of
the zone you wish to change. If the zone does not have a
chime (e.g. fire or PA zone) an error tone will be given. Press
the Ô*Õ key to finish.
Engineer programming
To enter the engineer programming mode the following
procedure must be followed.
1. The lid should be off the control panel.
2. Switch the mains supply on. The internal sounder will start.
3. Enter Ô1234Õ followed by the Ô#Õ button, this will silence the
sounder, the tamper LED will flash on the remote keypad.
4. Enter Ô7890Õ, the tamper LED will go out and the mains LED
will flash, the panel is now in Ôengineer programming
modeÕ.
The following options are now available for programming to
individual requirements.
Exit time 3-0 range 10-90 seconds
Enter 3-0 LED 3 will light up. This has been preset for factory
default - at 30 seconds. A new time may be programmed by
entering one key from the following table. Once program is set
press Ô*Õ to confirm. The accept tone will sound.
Enter 1 10 seconds
Enter 2 15 seconds
Enter 3 30 seconds
Enter 4 45 seconds
Enter 5 60 seconds
Enter 6 90 seconds
Entry time 3-1 range 10-90 seconds
Enter 3-1 LED 3 will light up. Again this has been preset for
factory default at 30 seconds. To reprogram the entry time
follow exactly the same directions as the EXIT. Again press Ô*Õ
to confirm option. The accept tone will sound.
Enter 1 10 seconds. LED 1 on.
Enter 2 15 seconds. LED 2 on.
Enter 3 30 seconds. LED 3 on.
Enter 4 45 seconds. LED 4 on.
Enter 5 60 seconds. LED 5 on.
Enter 6 90 seconds. LED 6 on.
Bell duration (Bell ring time) 3-2 range 3-20 minutes
Enter 3-2 LED 5 will light up. This has been preset for factory
default at 15 minutes. A new time may be programmed by
entering one key from the following table. Once program is set
press Ô*Õ to confirm. The accept tone will sound.
Enter 1 3 minutes. LED 1 on.
Enter 2 4 minutes. LED 2 on.
Enter 3 5 minutes. LED 3 on.
Enter 4 10 minutes. LED 4 on.
Enter 5 15 minutes. LED 5 on.
Enter 6 20 minutes. LED 6 on.
Part set exit time 3-3 range 0-90 seconds.
Enter 3-3 LED 2 will light up. This has been preset for factory
default at 15 seconds. A new time may be programmed by
entering one key from the following table. Once program is set
press Ô*Õ to confirm. The accept tone will sound.
Enter 0 0 seconds. All LEDs off (instant set in part set).
Enter 1 10 seconds. LED 1 on.
Enter 2 15 seconds. LED 2 on.
Enter 3 30 seconds. LED 3 on.
Enter 4 45 seconds. LED 4 on.
Enter 5 60 seconds. LED 5 on.
Enter 6 90 seconds. LED 6 on.
Note: The exit sounder volume can be altered in part set only
by the control marked PART SET VOLUME. The level
can be reduced to almost zero. When the control sets
an accept tone will sound.
Circuit programming
Circuits 2-6 can be reprogrammed to suit your requirements.
Circuit 1 is fixed as a final exit circuit. Circuit 7 is fixed as a PA
circuit. Circuit 8 is the global tamper circuit. The method of
programming is as follows:
Enter 4-2 for zone 2 Enter 4-3 for zone 3
Enter 4-4 for zone 4 Enter 4-5 for zone 5
Enter 4-6 for zone 6
Select the circuit you wish to alter. That circuit may then be
programmed by entering one key from the following table.
Once program is set press Ô*Õ to confirm, the accept tone will
sound.
Enter 1 Alarm.
Enter 2 Alarm with walkthrough.
Enter 3 Alarm with isolate in part set.
Enter 4 Alarm with walkthrough isolated in part set.
Enter 5 Full set alarm with walkthrough and part set entry.
Enter 6 Fire.
Extended programming options
Once all zones have been programmed you now have further
options available. Again bring up the LED to enable the option
and extinguish the LED to remove the option. ENTER Ô7Õ to
access the extended options then enter a key from the table
below.
Enter 1 - LED 1 Disable external bell and strobe in part set.
Enter 2 - LED 2 Chime enable.
Enter 3 - LED 3 Full set door sense setting.
Enter 4 - LED 4 Convert ID output to signal mains fail.
Enter 5 - LED 5 Allow the isolation of zone 1 (Entry/Exit) in
part set.
Enter 6 - LED 6 Allow PA from remote keypad by pressing Ô*Õ
and Ô#Õ together.
Press * to confirm. The accept tone will sound.
Engineering access code
The engineer access code is programmed to Ô7890Õ as a
factory default. To change this code:
Enter 1-1 LEDs 1, 2, 3 and 4 will light up. Enter the new 4 digit
code. After each keypress one LED will go out. The speaker
will emit an accept tone if the new code is accepted. If the
speaker emits an error tone and all LEDs are extinguished the
old access code is still valid. Repeat the procedure using a
different code.

Engineer event log review
The engineer log is organised into SET and UNSET events.
The log will show the first to alarm and subsequent alarms as
well as isolated circuits. First to alarm is shown by the LED
being ÔonÕ continuously. Subsequent alarms are shown by the
LED(s) flashing and isolated circuits are shown by LED(s)
pulsing slowly. The buzzer will sound whilst reviewing the
ÔSETÕ logs and silent whilst reviewing the ÔUNSETÕ logs.
To view the engineer logs proceed as follows:
From the program mode press the Ô5Õ key. The log routine will
start with DAY 1 SET. The remaining logs are viewed by
pressing the relevant key Ô2Õ for 2nd, Ô3Õ for 3rd etc. on to log 9.
Pressing the Ô0Õ key gives the last alarm condition. The Ô#Õ key
will alternate between ÔSETÕ and ÔUNSETÕ logs and can be used
at any time. To exit logs press the Ô*Õ key.
Factory programming defaults 9-9
Factory defaults have been split into two sections,
programming and codes.
To return to factory programming defaults enter 9-9 the
sounder will give a rapid pipping sound (the entry hurry up
warning). Then enter the engineer code. If entered correctly
an accept tone will sound and the factory programming defaults
will be restored. If any error is made an error tone will sound
and the programming will not be altered. The user and
engineer codes are not changed.
If at any stage you want to return the panel to factory default
user/customer codes, place the small link supplied with the
spare fuses, on the memory link (positioned below the
microprocessor in the centre of the PCB (see figure 4) then
remove the mains and battery supply. When the supply is
restored, the speaker will omit the accept tone and the factory
user code defaults will be restored.
Remove the link.
Once programming is complete exit engineer program mode by
pressing Ô*Õ followed by Ô#Õ, the panel will now be day mode.
Disconnect the mains from the panel. Now connect in the
backup battery (usually 12V 2.8 AH RS stock no. 597-829), the
sounder will indicate a tamper, screw the control panel lid on
and press Ô1234Õ (or your user code if re-programmed) to
silence the alarm. The system is now ready for use.
Note: It is strongly advised that both the user and engineer
code are changed from the factory default.
In the event of the panel not working as described above
please re-check your wiring against the wiring diagrams figures
3, 4 and 5. Remember you can isolate zones by installing wire
links shorting the zone out at the panel.
User instructions
1.0 Setting
1.1 Full set
To start the exit procedure ensure all alarmed doors and
windows are closed and enter the four digit user code, the
buzzer will emit a steady sound and the exit time start.
Leave the building by the approved exit route and close the
final exit door. Wait outside the door until the buzzer has
stopped to indicate that the panel has armed.
If any zones are in fault the buzzer will pulse and the LED
for that zone will be lit. Return to the panel and press the
Ô#Õ key or enter the user code to abort the exit procedure.
Investigate the fault and correct if possible, then start the
exit procedure again. If you do not complete the exit
procedure before the exit time runs out the internal sounder
will start. Enter your user code to stop the sounder. See
section 3.3 to reset the control.
1.2 Part guard
Start the exit procedure as for full set as above. Then press
the Ô*Õ key followed by the Ô0Õ key. The buzzer will change
tone and the LEDs for any zones programmed to be
isolated in part guard will flash. The programmed part
guard exit time will be selected and the exit procedure will
continue. If your system does not allow part guard an error
tone will sound and the exit procedure will be aborted.
1.3 Manual isolation
Start the exit procedure as for full set as above. Then press
the Ô*Õ key followed by the number for each of the zones you
require to isolate. If the zone is isolated the LED for the
required zone will flash and the exit procedure continue.
2.0 Unsetting
Enter by the usual route, the buzzer will sound, do not stop
go directly to the control. Enter the four digit code, the
buzzer will stop and the control return to the ÔDAYÕ mode. If
the exit time has less than 10 seconds remaining the
buzzer will emit a quick pulsing sound to indicate ÔHURRY
UPÕ.
3.0 Tamper faults during day
A tamper fault during the day is indicated by the internal
sounder and the tamper LED. Enter the four digit user code
to stop the sounder, the sounder will now change to a low
level two tone alternating sound to indicate that there is a
ÔRESET REQUIREDÕ. Press the Ô#Õ key to reset the control.
3.1 Alarms during the set period
Enter the four digit user code to unset the system. The
LED display will indicate which zone caused the alarm.
See section 3.3 to reset the control.
3.2 Personal attack alarms
Enter the four digit user code to stop the sounder. Reset
the personal attack button with the key provided. See
section 3.3 to reset the control.
3.3 Resetting the system
To reset the control enter the user code, the sounder will
emit a low level two tone alternating sound to indicate that
there is a ÔRESET REQUIREDÕ. Press the Ô#Õ key to reset
the control. An accept tone will be given, the LEDs for the
zones in alarm will go out and the control will return to the
ÔDAYÕ mode.
4.0 User options
4.1 Auto test
Enter the four digit user code, the buzzer will emit a steady
sound and the exit time start. Press the Ô*Õ key followed by
the Ô9Õ key. The exit buzzer will stop and all LEDs will light.
After the 10 seconds LED test the internal sounder, bell and
strobe will each operate for 5 seconds, the control will then
emit an accept tone and revert to the ÔDAYÕ mode. You
may end the test at any time by pressing the Ô*Õ key.
4.2 Reviewing the alarm logs
The logs are organised as ÔSETÕ and ÔUNSETÕ events. All
events are recorded. The first alarm is shown by the
relevant LED being lit continuously. Subsequent alarms are
shown by a fast pulse of the zone LED. Any zones isolated
are shown by a slow pulse of the zone LED. The buzzer
will sound whilst viewing the ÔSETÕ logs but will be silent
whilst viewing the ÔUNSETÕ logs.
Pressing the Ô#Õ key will change between viewing the ÔSETÕ
and ÔUNSETÕ logs. This may be done at any time. The log
review will automatically end after 15 seconds if no keys are
pressed.

Enter the four digit user code, the buzzer will emit a steady
sound and the exit time start. Press the Ô*Õ key followed by
the Ô9Õ key, then press the Ô3Õ key. The log routine will start
viewing ÔDAYÕ 1 ÔSETÕ.
Key View
1 Log 1
2 Log 2
3 Log 3
4 Log 4
5 Log 5
6 Log 6
7 Log 7
8 Log 8
9 Log 9
0 The last alarm
Press the Ô*Õ key to finish.
4.3 Walk test
You should test your system at regular intervals, to aid this
a walk test mode is provided. You are allowed to test all
ALARM devices. DO NOT TEST ANY PERSONAL
ATTACK BUTTONS.
Enter the four digit user code, the buzzer will emit a steady
sound and the exit time start. Press the Ô*Õ key followed by
the Ô9Õ key, then press the Ô4Õ key. The buzzer will emit a
low level steady tone.
As you test each device the internal sounder will give a loud
pulsing tone to indicate the correct operation of that device.
The zone number LED will light. When the device test is
over the sounder will stop and the zone LED will go out.
The buzzer will emit a low level steady tone as before.
Report any faults to your alarm company.
Press the Ô*Õ key to finish.
Technical specification
Power supply
Mains supply voltage 240V~ Nom
PSU input voltage 13.7V~ Nom
PSU output voltage 12V Nom
Maximum output current 1A (total)
Aux. current 500mA max
Battery fuse 1A (20mm)
Panel quiescent 40mA
Keypads
Supply voltage 12V
Quiescent current 20mA
Active 45mA
Maximum cable run 100 metres
General
Operating temperature 10 to 50¡ centigrade
Humidity Up to 80% non condensing
Dimensions 263mm (W)
223mm (H)
82mm (D)
Control panel weight 2.7kg excluding batt.
Standby battery 2.6AH 12V rechargeable
6AH max.
RS Components Issued November 1994 9954
This manual suits for next models
1
Table of contents
Other RS Security System manuals
Popular Security System manuals by other brands

Swann
Swann GuardianEye instruction manual

Cooper Wheelock
Cooper Wheelock Series 43T AC Bells specification

Mosaic
Mosaic MH803 user manual

Wireless Devices
Wireless Devices AF-21 Operation manual

2gig Technologies
2gig Technologies GO!control 2GIG-CNTRL2 user guide

Copper Connections
Copper Connections CCL BAS-GS manual