Samsung AE040RXEDEG User manual

ECO HEATING SYSTEM CONTENTS
ECO HEATING SYSTEM
OUTDOOR UNIT
TANK INTEGRATED
HYDRO UNIT
1. Precautions
2. General Overview
3. Disassembly and Reassembly
4. Troubleshooting
5. PCB Diagram
6. Wiring Diagram
7. Reference Sheet
Model : (Split)
AE040RXEDEG
AE060RXEDEG
AE090RXEDEG
AE090RXEDGG
(Mono)
AE050RXYDEG
AE080RXYDEG
AE120RXYDEG
AE160RXYDEG
AE080RXYDGG
AE120RXYDGG
AE160RXYDGG
(Split)
AE200RNWSEG
AE260RNWSEG
AE260RNWSGG
(Mono)
AE200RNWMEG
AE260RNWMEG
AE260RNWMGG

Contents
1. Precautions.................................................................................................................3
1-1 Precautions for the Service..................................................................................................................................................3
1-2 Precautions related to static electricity and PL ..........................................................................................................3
1-3 Precautions for the Safety....................................................................................................................................................4
1-4 Precautions for handling a system containing refrigerants.................................................................................5
1-5 Precautions for the brazing.................................................................................................................................................5
1-6 Precautions for charging refrigerants.............................................................................................................................5
2. General Overview......................................................................................................6
2-1 Features of the System..........................................................................................................................................................6
2-2 Product Specications...........................................................................................................................................................8
2-3 Specications of optional items.....................................................................................................................................16
3. Disassembly and Reassembly............................................................................... 18
3-1 Tank Integrated Hydro Unit..............................................................................................................................................19
3-2 Outdoor Unit...........................................................................................................................................................................24
4. Troubleshooting ..................................................................................................... 74
4-1 Wired remote controller ....................................................................................................................................................74
4-2 Troubleshooting by symptoms......................................................................................................................................77
4-3 Hydro Unit...............................................................................................................................................................................78
4-4 Items to check before diagnostics...............................................................................................................................84
4-5 Troubleshooting by symptoms.....................................................................................................................................85
5. PCB Diagram ......................................................................................................... 100
5-1 Tank Integrated Hydro Unit........................................................................................................................................... 100
5-2 Outdoor Unit........................................................................................................................................................................ 102

2Samsung Electronics
Contents
6. Wiring Diagram..................................................................................................... 113
6-1 Hydro unit............................................................................................................................................................................. 113
6-2 Outdoor Unit........................................................................................................................................................................ 115
7. Reference Sheet.................................................................................................... 118
7-1 Index for Model Name..................................................................................................................................................... 118
7-2 Tank intergrated hydro unit(SPLIT)............................................................................................................................ 119
7-3 Tank intergrated hydro unit(MONO)......................................................................................................................... 120
7-4 FSV Data check and update using S-NET Pro2..................................................................................................... 121
7-5 EHS FSV Values Import and Export............................................................................................................................ 122

Samsung Electronics 3
1. Precautions
1-1 Precautions for the Service
Use the standard parts when replacing the electric parts.
– Confirm the model name, rated voltage, rated current of the electric parts.
When repairing the equipment, connection of the harness parts must be firm and solid.
– A loose connection may cause noise or other malfunction.
When assembling and disassembling the equipment while it is laid down, lay it on soft cloth.
– Otherwise it may scratch the back of the exterior of the product.
Remove dust or dirt completely from the housing block, wiring block and service parts during repair.
– This helps prevent the danger of fire caused by tracking or short circuit.
Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches.
Check the status of the components’ assembly after repair service.
– The status must be the same as before the repair service.
1-2 Precautions related to static electricity and PL
The PCB power supply block is susceptible to static electricity. Therefore, care must be taken during repair or measuring
while the power is on.
– Wear insulation gloves for PCB repair or measuring.
Check whether the installation location is at least two meters away from other electronic products such as TV, video, or
audio.
– Otherwise, the video quality might be degraded or noise might be generated.
Do not let end users repair the products themselves.
– Unauthorized disassembly might cause electric shock or fire.

Precautions
4Samsung Electronics
1-3 Precautions for the Safety
Do not pull any electric wires and do not touch an auxiliary power switch with a wet hand.
– There is a danger of electric shock or fire.
In case any wire or power plug has been damaged, replace it to eliminate any possible danger.
Do not bend the power cord by force and do not put any heavy object on the power cord.
– There is a danger of electric shock or fire.
Do not use multi socket.
– There is a danger of electric shock or fire.
Ground the product if necessary.
– Be sure to ground the product if there is any danger of electric leakage due to water or moisture.
Be sure to turn off the auxiliary power switch or pull out the power plug during replacement or repair of electric parts.
– There is a danger of electric shock.
The installation must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard.
– Installation by an unqualified person may cause a water leakage, electric shock or fire and so on.
The electric work must be done by service agent or similarly qualified persons according to national wiring regulations and use
only rated cable.
– If the capacity of the power cable is insufficient or electric work is not properly completed, electric shock or fire may occur.
Use only rated parts and tools.
– If you don't use the rated parts and tools, it can cause trouble with the air conditioner and bring about injury.
If any gas or impurities except R-32 refrigerant come into the refrigerant pipe, serious problem may occur and it may cause
injury.
Leak test must be done using only Nitrogen(NO
2
)gas.
R-32 refrigerant is used for EHS.
– When using R-32, moisture or foreign substances may affect to the capacity and reliability of the product. Safety precautions
must be taken when installing the refrigerant pipe.
– The design pressure of the unit is 4.6MPa. Select appropriate material and thickness according to the regulations.

Precautions
Samsung Electronics 5
1-4 Precautions for handling a system containing refrigerants
All system containing refrigerants shall be removed under regional regulations prior to the disposal to
prevent the potential health and environmental consequences.
Harmful for human body
– When emitted liquid refrigerant contacts human body, contacted area may get frostbite, blister or become numb.
If refrigerant leaks in airtight area, lack of oxygen may cause suffocation. When refrigerant is heated, it may generate harmful gas.
Precautions for handling container
– Do not apply shock or heat to the refrigerant container.
1-5 Precautions for the brazing
Clear any dangerous or inflammable materials in surrounding environment.
Make sure to empty the remaining refrigerant in the product or pipe before brazing.
– Brazing with the refrigerant still remaining in the product or pipe may cause poor result and generate harmful gas. Furthermore,
pressure of the refrigerant may increase and cause damage to the leaking part. This may lead harmful refrigerant and oil to spurt
out which can be dangerous for service personnel.
Use nitrogen gas to get rid of the oxide forming during brazing.
– Using other type of gas may cause damage to the product or the exterior.
1-6 Precautions for charging refrigerants
Add quantity of the refrigerant using a scale and perform a test operation with S-net.
– Product performance may decrease if you add excessive amount of refrigerant.
Do not charge refrigerants while heating the container up.
– The container may get damaged by the heat and result in explosions.
Do not operate the product without pressure switch(for product protection) and sensor.
– If there are any internal blockage, high refrigerant pressure increase may damage the product or exterior.

6Samsung Electronics
2. General Overview
2-1 Features of the System
POWER SAVING
EHS(Eco Heating System) considers the trend in air conditioner use. It optimizes the
energy efficiency of loads ranging from partial to full. It achieves an excellent energy
effect for the users of the air conditioner.
Samsung patented compressor
Samsung has been researching and developing compressors since the 70's.
It has developed power saving compressors for more than thirty years.
The EHS(Eco Heating System) compressor adopts a double-rotor BLDC compressor with permanent magnets made by Samsung.
Electricity for the compressor rotor is obtained from a neodium-iron-boron permanent magnetic material (boron magnet can attract iron
material weighing 1000 times its own weight.) It strengthens the rotary moment of the compressor to maximize the entire efficiency of the
compressor.
BLDC electricity
Permanent magnet, strong magnetic rotor
Double rotor compression cylinder
Nd-Fe-B Neodium-Iron-Boron magnet
SAMSUNG's double-rotor compressor has the upper and lower rotors designed symmetrically.
The double rotor in symmetry can remove vibrations caused by the eccentric design of the cylinder.
2 rotors balancing the rotary moment
Centered symmetry
Upper rotor
Permanent magnet rotor
Lower cylinder
Upper cylinder
Lower rotor
High efficiency heat exchanger
EHS(Eco Heating System) uses new multiple-teeth screw pipes with a diameter of 8 mm to improve the heat exchangeability of the pipe by
30.8%.
The water-friendly aluminum foil in the heat exchanger uses the G-fin patent design to improve the efficiency of heat exchange by 13%.
DC fan electricity
The EHS(Eco Heating System) outdoor machine uses DC fan electricity. The rotational speed of electricity is 100 RPM to 1050 RPM with
step-free control. The electrical efficiency is improved by about 33% compared to AC electricity.
Efficiency
Multiple-teeth screw pipes
General screw pipes

General Overview
Samsung Electronics 7
2-1-1 Key features of the EHS(SPLIT)
Integrated Heating & Cooling system
Plate Heat exchanger is a integral part in heating & cooling system. For user’s convenience, PHE is integrated into the system.
This concept will help space saving and lower costs for pipe line reduction.
Running Costs-Reduction of Up to 33.5%
Samsung EHS, known for its world class efficiency (12kW floor heating system with 4.63), can reduce 33.5% of your running costs
as compared to a gas boiler.
High Performance at Low Temperature
Samsung EHS is made up of an inverter compressor optimally operated according to the outdoor temperature, offering heating
performance of 90% at -10°C and reliable frost protection at -25°C.
Heat pump operating range of DHW : -25 ~ 35 °C
At the temperature -25 °C ~ -20 °C, operation is available but capacity cannot be guaranteed.

General Overview
Samsung Electronics 9
8Samsung Electronics
2-2 Product Specifications
2-2-1 Outdoor Unit (Split)
Model Name
Indoor Unit
AE200RNWSEG AE200RNWSEG AE200RNWSEG AE260RNWSGG AE260RNWSEG AE260RNWSEG AE260RNWSEG
Outdoor Unit
AE040RXEDEG AE060RXEDEG AE090RXEDEG AE090RXEDGG AE040RXEDEG AE060RXEDEG AE090RXEDEG
Outdoor Unit & Tank Hydro Unit Figure
System
Mode Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W)
A2W
Condition #1.
(A7/W35) *1
Nominal
Capacity
Heating W4,400 6,000 9,000 9,000 4,400 6,000 9,000
Btu/h 15,000 20,500 30,700 30,700 15,000 20,500 30,700
Cooling W5,000 6,500 8,700 8,700 5,000 6,500 8,700
Btu/h 17,10 0 22,200 29,700 29,700 17,100 22,200 29,700
Power Input
(Nominal)
Heating W846 1,220 1,870 1,870 846 1,220 1,870
Cooling 1,090 1,470 2,110 2,110 1,090 1,470 2,110
Current Input
(Nominal)
Heating A3.9 5.6 8.6 3.0 3.9 5.6 8.6
Cooling 4.9 6.7 9.7 3.4 4.9 6.7 9.7
COP (Nominal Heating) W/W 5.20 4.92 4.81 4.81 5.20 4.92 4.81
EER (Nominal Cooling) W/W 4.59 4.42 4.12 4.12 4.59 4.42 4.12
PdesignH (LWT 35℃) W 5,000 6,000 8,500 8,500 5,000 6,000 8,500
SCOP (35℃)W/W 4.58 4.58 4.45 4.45 4.58 4.58 4.45
SEER *2 W/W 4.40 4.73 5.09 5.09 4.40 4.73 5.09
A7/ W45 Capacity Heating W4,200 5,600 8,600 8,600 4,200 5,600 8,600
COP W/W 3.85 3.71 3.69 3.69 3.85 3.71 3.69
A7/ W55 Capacity Heating W3,900 5,200 8,000 8,000 3,900 5,200 8,000
COP W/W 2.95 2.87 2.93 2.93 2.95 2.87 2.93
A2/W35 Capacity Heating W4200 5200 7700 7,70 0 4200 5200 7700
COP W/W 3.82 3.51 3.41 3.41 3.82 3.51 3.41
A-7/W35 Capacity Heating W4600 5500 7900 7,9 00 4600 5500 7900
COP W/W 2.97 2.75 2.72 2.72 2.97 2.75 2.72
Field
Wiring
Hydro Unit
MCA A22.7 22.7 22.7 3Φ 8.7 / 1Φ 14.0 22.7 22.7 22.7
Max Current A22.7 22.7 22.7 3Φ 8.7 / 1Φ 14.0 22.7 22.7 22.7
MFA A28.4 28.4 28.4 3Φ 10.9 / 1Φ 17.5 28.4 28.4 28.4
Outdoor Unit
MCA A16.0 16.0 22.0 10.0 16.0 16.0 22.0
Max Current A16.0 16.0 22.0 16.1 16.0 16.0 22.0
MFA A20.0 20.0 27. 5 16.1 20.0 20.0 27. 5
Water
Connections
Water Flow Rate (Std)[H/C] LPM 12.7/14.4 17. 3/18 .8 26/25.1 26/25.1 12.7/14.4 17. 3/18 .8 26/25.1
Water Pressure (Max) bar 3333333
Water Pipe Inlet Φ, mm ø28 ø28 ø28 ø28 ø28 ø28 ø28
Outlet Φ, mm ø28 ø28 ø28 ø28 ø28 ø28 ø28
Leaving Water
Temperature
Heating °C 15~65 15~65 15~65 15~65 15~65 15~65 15~65
Cooling °C 5~25 5~25 5~25 5~25 5~25 5~25 5~25
Refrigerant
Connections
Liquid Pipe Φ, mm 6.35 6.35 6.35 6.35 6.35 6.35 6.35
Φ, inch 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
Gas Pipe Φ, mm 15.88 15.88 15.88 15.88 15.88 15.88 15.88
Φ, inch 5/8" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8"
Installation
Limitation
Max. Length m30 30 35 35 30 30 35
Max. Height m20 20 20 20 20 20 20
Chargeless Length m15 15 15 15 15 15 15
Operating
Temp. Range
Heating °C -25~35 -25~35 -25~35 -25~35 -25~35 -25~35 -25~35
Cooling °C 10~46 10~46 10~46 10~46 10~46 10~46 10~46
D.Hot Water °C -25~43 -25~43 -25~43 -25~43 -25~43 -25~43 -25~43

General Overview
Samsung Electronics 11
10 Samsung Electronics
Model Name
Indoor Unit
AE200RNWSEG AE200RNWSEG AE200RNWSEG AE260RNWSGG AE260RNWSEG AE260RNWSEG AE260RNWSEG
Outdoor Unit
AE040RXEDEG AE060RXEDEG AE090RXEDEG AE090RXEDGG AE040RXEDEG AE060RXEDEG AE090RXEDEG
Hydro
Unit
Power Supply Φ, #, V, Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 3Ф, 4Line, 380~415V, 50Hz
1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz
Water
Pump
Type (Model Name) - Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Motor Input (Max) W 100 100 100 100 100 100 100
Number of Unit EA 1111111
Flow SENSOR
Type (Model Name) - FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR
Min. flow rates LPM 7.0 7. 0 7.0 7.0 7.0 7. 0 7.0
Electric Heater W2,000 2,000 2,000 6,000 2,000 2,000 2,000
Expansion Vessel Liter 8888888
Pressure Relief Valve bar 2.9 2.9 2.9 2.9 2.9 2.9 2.9
Air Purge Valve Ф, inch BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8"
Sound *3
Sound
Pressure
Heating Std dB(A)
26 26 26 26
26 26 26
Cooling Std dB(A)
26 26 26 26
26 26 26
Sound Power Heating Std dB(A)
40 40 40 40
40 40 40
External
Dimension
Net Weight kg 136 136 136 146 146 146 146
Shipping Weight kg 148 148 148 158 158 158 158
Net Dimensions (WxHxD) mm 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700
Shipping Dimensions (WxHxD) mm 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780
Outdoor
Unit
Power Supply Φ, #, V, Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 3Ф, 4Line, 380~415V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz
Compressor
Type -BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary
Model -UB4TN8200FE4SS UB4TN8200FE4SS UB8TN8265FJWSG UB8TN8265FJWSG UB4TN8200FE4SS UB4TN8200FE4SS UB8TN8265FJWSG
Oil Type -POE POE POE POE POE POE POE
Condenser Size -2RX28S 2RX28S 2RX46S 2RX46S 2RX28S 2RX28S 2RX46S
Motor
Type (Model) -SIC-67FV-F135-2 SIC-67FV-F135-2 FMDC531SSA FMDC531SSA SIC- 67FV-F135-2 SIC-67FV-F135-2 FMDC531SSA
Quantity EA 1111111
CODE No -DB31- 00492A DB31-00492A DB31-00579A DB31-00579A DB31-00492A DB31-00492A DB31-00579A
Fan Air Flow Rate Cooling CMM 40 43 66 66 40 43 66
Number of Unit EA 1 1 1 1 1 1 1
4-Way Valve Type (Model)
SHF-7H-34U SHF-7H-34U SHF -11H SHF -11H SHF-7H-34U SHF-7H-34U SHF-11H
Base Heater Power Input W
N/A N/A 150 150 N/A N/A 150
Sound*3
Sound
Pressure
Heating Std dB(A)
44 47 49 49 44 47 49
Cooling Std dB(A)
46 47 49 49 46 47 49
Night Mode dB(A)
-35 35 35 -35 35
Sound Power Heating Std dB(A)
58 60 64 64 58 60 64
Cooling Std dB(A)
61 62 63 63 61 62 63
External
Dimension
Net Weight kg
46.5 46.5 73.0 72.0 46.5 46.5 73.0
Shipping Weight kg
49.5 49.5 81.5 80.5 49.5 49.5 81.5
Net Dimensions (WxHxD) mm
880 x 638 x 310 880 x 638 x 310 940 x 998 x 330 940 x 998 x 330 880 x 638 x 310 880 x 638 x 310 940 x 998 x 330
Shipping Dimensions
(WxHxD) mm
1,023 x 742 x 413 1,023 x 742 x 413 995 x 1,178 x 426 995 x 1,178 x 426 1,023 x 742 x 413 1,023 x 742 x 413 995 x 1,178 x 426
Refrigerant
Type -
R32 R32 R32 R32 R32 R32 R32
Control Method -
EEV EEV EEV EEV EEV EEV EEV
Factory Charging g
1,200 1,200 1,400 1,400 1,200 1,200 1,400
*1) A2W Condition #1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB; (Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃[DB].
*2) A2W Condition for ESEER(Cooling) at Water Out 18℃.
*3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
Night mode : Water In/Out 30℃/35℃, Outdoor Air : 7℃[DB]/6℃[WB], Measure point from unit : 3m.
Product Specifications (cont.)

General Overview
Samsung Electronics 13
12 Samsung Electronics
Product Specifications (cont.)
Model Name
Indoor Unit
AE200RNWMEG AE200RNWMEG AE200RNWMEG AE200RNWMEG AE260RNWMGG AE260RNWMGG AE260RNWMGG
Outdoor Unit
AE050RXYDEG AE080RXYDEG AE120RXYDEG AE160RXYDEG AE080RXYDGG AE120RXYDGG AE160RXYDGG
Outdoor Unit & Tank Hydro Unit Figure
System
Mode Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W) Heat Pump (A2W)
A2W
Condition #1.
(H A7/W35
C A35/W18)*1
Nominal
Capacity
Heating W5,000 8,000 12,000 16,000 8,000 12,000 16,000
Btu/h 17,10 0 27,30 0 40,900 54,600 27,3 00 40,900 54,600
Cooling W5,000 7,50 0 12,000 14,000 7,50 0 12,000 14,000
Btu/h 17,10 0 25,600 40,900 47, 80 0 25,600 40,900 47,8 00
Power Input
(Nominal)
Heating W1,030 1,770 2,650 3,620 1,770 2,650 3,620
Cooling 1,140 1,900 2,770 3,280 1,900 2,770 3,280
Current Input
(Nominal)
Heating A4.9 8.5 12.2 17. 0 2.8 4.1 5.7
Cooling 5.4 9.1 13.2 15.7 3.0 4.4 5.3
COP (Nominal Heating) W/W 4.85 4.52 4.53 4.42 4.52 4.53 4.42
EER (Nominal Cooling) W/W 4.39 3.95 4.33 4.27 3.95 4.33 4.27
PdesignH (LWT 35℃) W 5,500 8,000 13,000 16,000 8,000 13,000 16,000
SCOP (35℃) - 4.46 4.44 4.69 4.48 4.44 4.69 4.48
SEER *2 -3.98 4.52 5.22 5.31 4.52 5.22 5.31
A7/ W45 Capacity Heating W4,800 7,4 00 11,70 0 15,400 7,4 00 11,70 0 15,400
COP W/W 3.69 3.49 3.68 3.43 3.49 3.68 3.43
A7/ W55 Capacity Heating W4,300 7,100 11,3 00 15,000 7,10 0 11, 30 0 15,000
COP W/W 2.83 2.81 3.03 2.90 2.81 3.03 2.90
Performance
(A2/W35)
Capacity Heating W4,800 7,000 10,800 13,200 7,000 10,800 13,200
COP W/W 3.31 2.98 3.27 3.00 2.98 3.27 3.00
Performance
(A-7/ W35)
Capacity Heating W5,100 7, 350 12,000 14,600 7, 350 12,000 14,600
COP W/W 2.71 2.43 2.55 2.43 2.43 2.55 2.43
Field
Wiring
Tank
Integrated
Hydro Unit
MCA A22.70 22.70 22.70 22.70 3Φ 8.7 / 1Φ 14.0 3Φ 8.7 / 1Φ 14.0 3Φ 8.7 / 1Φ 14.0
Max Current A22.70 22.70 22.70 22.70 3Φ 8.7 / 1Φ 14.0 3Φ 8.7 / 1Φ 14.0 3Φ 8.7 / 1Φ 14.0
MFA A28.38 28.38 28.38 28.38 3Φ 10.9 / 1Φ 17.5 3Φ 10.9 / 1Φ 17.5 3Φ 10.9 / 1Φ 17.5
Outdoor Unit
MCA A16.0 22 28 32 10 10 12
Max Current A16.0 22 28 32 16.1 16.1 16.1
MFA A20.0 27. 5 35 40 16.1 16.1 16.1
Water
Connections
Water Flow Rate
(Heating/Cooling) LPM 14.4/14.4 23.1/21.6 34.6/34.6 46.2/40.4 23.1/21.6 34.6/34.6 46.2/40.4
Water Pressure (Max) bar 3333333
Water Pipe Inlet Φ, mm ø28 ø28 ø28 ø28 ø28 ø28 ø28
Outlet Φ, mm ø28 ø28 ø28 ø28 ø28 ø28 ø28
Leaving Water
Temperature
Heating °C 15~65 15~65 15~65 15~65 15~65 15~65 15~65
Cooling °C 5~25 5~25 5~25 5~25 5~25 5~25 5~25
Refrigerant
Type -R32 R32 R32 R32 R32 R32 R32
Control Method -EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED EEV INCLUDED
Factory Charging g1,000 1,150 2,200 2,200 1,150 2,200 2,200
Hydro
Unit
Power Supply Φ, #, V, Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 3Ф, 4Line, 380~415V, 50Hz
1Ф, 2Line, 220~240V, 50Hz
3Ф, 4Line, 380~415V, 50Hz
1Ф, 2Line, 220~240V, 50Hz
3Ф, 4Line, 380~415V, 50Hz
1Ф, 2Line, 220~240V, 50Hz
Water
Pump
Type (Model Name) - Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
"Centrifurugal
(UPMM 25-9.5)"
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Centrifurugal
(UPMM 25-9.5)
Motor Input (Max) W 100 100 100 100 100 100 100
Number of Unit EA 1111111
2-2-2 Outdoor Unit (Mono)

General Overview
Samsung Electronics 15
14 Samsung Electronics
Model Name
Indoor Unit
AE200RNWMEG AE200RNWMEG AE200RNWMEG AE200RNWMEG AE260RNWMGG AE260RNWMGG AE260RNWMGG
Outdoor Unit
AE050RXYDEG AE080RXYDEG AE120RXYDEG AE160RXYDEG AE080RXYDGG AE120RXYDGG AE160RXYDGG
Hydro
Unit
Flow SENSOR Type (Model Name) - FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR FLOW SENSOR
Min. flow rates LPM 7.0 7.0 12.0 12.0 7.0 12.0 12.0
Electric Heater W2,000 2,000 2,000 2,000 6,000 6,000 6,000
Expansion Vessel Liter 8888888
Pressure Relief Valve bar 2.9 2.9 2.9 2.9 2.9 2.9 2.9
Air Purge Valve Ф, inch BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8" BSPP male 3/8"
Sound *3
Sound
Pressure
Heating Std dB(A) 26 26 30 30 26 30 30
Cooling Std dB(A) 26 26 30 30 26 30 30
Sound Power Heating Std dB(A) 40 40 44 44 40 44 44
External
Dimension
Net Weight kg 130 130 130 130 140 140 140
Shipping Weight kg 142 142 142 142 152 152 152
Net Dimensions (WxHxD) mm 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700 595x1800x700
Shipping Dimensions
(WxHxD) mm 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780 700 x 2,000 x 780
Power Supply Φ, #, V, Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 1Ф, 2Line, 220~240V, 50Hz 3Ф, 4Line, 380~415V, 50Hz 3Ф, 4Line, 380~415V, 50Hz 3Ф, 4Line, 380~415V, 50Hz
Compressor
Type - BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary
Model -UB4TN8200FE4SS UB8TN8265FJWSG UB5TN5450FJXSG UB5TN5450FJXSG UB8TN8265FJWSG UB5TN5450FJXSG UB5TN5450FJXSG
Oil -POE POE POE POE POE POE POE
Fan Air Flow Rate Cooling CMM 51 66 99 118 66 99 118
Number of Unit EA 1 1 2 2 1 2 2
Base Heater W N/A 150 150 150 150 150 150
Sound*3
Sound
Pressure
Heating dB(A) 45 48 50 52 48 50 52
Cooling dB(A) 45 48 50 54 48 50 54
Sound Power Heating dB 61 63 64 66 63 64 66
Cooling dB 62 64 65 68 64 65 68
External
Dimension
Net Weight kg 58.5 76.0 110.0 110.0 75.0 111.0 111. 0
Shipping Weight kg 62.5 84.5 119.0 119.0 83.5 120.0 120.0
Net Dimensions (WxHxD) mm 880 x 798 x 310 940 x 998 x 330 940 x 1,420 x 330 940 x 1,420 x 330 940 x 998 x 330 940 x 1,420 x 330 940 x 1,420 x 330
Shipping Dimensions
(WxHxD) mm 1,023x904x413 995 x 1,178 x 426 995 x 1,598 x 426 995 x 1,598 x 426 995 x 1,178 x 426 995 x 1,598 x 426 995 x 1,598 x 426
Operating
Temp. Range
Heating ℃-25~35 -25~35 -25~35 -25~35 -25~35 -25~35 -25~35
Cooling ℃10~46 10~46 10~46 10~46 10~46 10~46 10~46
DHW Tank ℃-25~43 -25~43 -25~43 -25~43 -25~43 -25~43 -25~43
*1) A2W Condition #1 : (Heating) Water In/Out 30℃/35℃, Outdoor Air 7℃DB/6℃WB; (Cooling) Water In/Out 23℃/18℃, Outdoor Air 35℃DB.
*2) A2W Condition for ESEER(Cooling) at Water Out 18℃.
*3) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
Product Specifications (cont.)

16 Samsung Electronics
Item Description Code No. Q’ty Remark
Cap Drain DB63-10355C 3 (5) AE080/090/120/160RX** Model
(AE040/060RX** Model)
Drain Plug DB67-00806A 1AE080/090/120/160RX** Model
Drain Plug D B67-20 011A 1AE040/050/060RX** Model
Rubber Leg DB73-20134A 4AE080/090/120/160RX** Model
Rubber Leg DB67- 01533A 4AE040/050/060RX** Model
Installation Manual
DB68-08375A
1
AE040/060RX** Model
Installation Manual
DB68-08368A
1
AE050RX** Model
Installation Manual DB68-08407A 1AE090RX** Model
Installation Manual
DB68-08408A
1
AE080/120/160RX** Model
Instruction Manual DB68-08423D 1AE040/060RX** Model
Instruction Manual
DB68-08423E
1
AE050RX** Model
Instruction Manual DB68-08409A 1
AE090RX** Model
Instruction Manual DB68-08410A 1AE080/120/160RX** Model
Installation Manual DB68- 08367A 1
AE200/260RNW***Model
Instruction Manual
DB68-08422C
1AE200/260RNW***Model
2-3 Specifications of optional items
2-3-1 Accessories

General Overview
Samsung Electronics 17
Item Description Code No. Q’ty Remark
Zone sensor DB95-04396A 2
AE200/260RNW***Model
Sen Temp-Mixing Valve
DB32- 00213A
1
Sensor holder DB61-40055A 3
Sensor clip DB81-00635A 3
Cable-tie DB65-10088C 6
Aluminum Tape DB72-30040A 3
Rubber Tape DB62-11304A 3
Insulatior DB62-04785A 3
Tube Secondary DB96-24724A 1AE260RNW***Model
Gasket DB63- 04197A 1AE260RNW***Model
Drain Plug Out DB67-20 011A 1AE200/260RNW***Model
Cap Drain DB63-10355C 2AE200/260RNW***Model

18 Samsung Electronics
■Hand Tool sets
3. Disassembly and Reassembly
Item Remark
+Screw Driver
Adjustable wrench
–Screw Driver
Nipper
Electric Motion Driver
L-Wrench
Torque Lench
Latchet Lench

Samsung Electronics 19
No Parts Procedure Remark
1ELECTRICAL
EQUIPMENT PARTS
1) Remove ** screws from the Cabinet.
(Use + Screw Driver)
2) Remove the 4 screws and then separate the
Cover Control Box part.
(Use + Screw Driver)
3) Remove the Power, Pump, 3way valve, Flow
sensor, Booster Heater, Back-up Heater, Sensor
connector of Assy PCB.
3-1 Tank Integrated Hydro Unit
■
AE200RNW
SS
G/AE260RNW
SS
G
Be sure that the power switch is in the OFF and the power source cord shall be unplugged prior to disassembly and reassembly works.

Disassembly and Reassembly
20 Samsung Electronics
No Parts Procedure Remark
4) Remove the 3 screws from the front part.
5) Remove the 2 screw and then open the cover
in the middle position of water tank.
6) Remove the wire of the thermostat and
booster heater.

Disassembly and Reassembly
Samsung Electronics 21
No Parts Procedure Remark
2EXPANSION VESSEL 1) Remove the 2 screw from the front parts.
2) Separate the pipe connected expansion vessel
by 2 nut joints.
3PUMP 1) Disconnect power and communication
connection.
2) Separate the pipe connected Pump by 2 nut
joints.
4Flow sensor
1) Separate the pipe connected flow sensor
by 2 bracket holder.

Disassembly and Reassembly
22 Samsung Electronics
No Parts Procedure Remark
5Back up Heater 1) Remove the 4 screw front the cabi top parts.
2) Separate the pipe connected Back up heater
by 2 nut joints.
6
3way Valve
1) Separate the pipe connected 3way valve
by 3 bracket holder.
7
Anode bar
1) Separate the pipe connected anode bar
by 1 nut joint from top of the tank.

Disassembly and Reassembly
Samsung Electronics 23
No Parts Procedure Remark
8PLATE HEAT
EXCHANGER
1) Remove the 2 screw from the bracket valve.
2) Remove the 2 screw front the cabi top sub.
3) Separate the pipe connected Assy plate heat
exchanger by 2 nut joint.
This manual suits for next models
16
Table of contents
Other Samsung Heating System manuals
Popular Heating System manuals by other brands

Salda
Salda RIS 400 P EKO 3.0 Series MOUNTING AND INSTALLATION INSTRUCTION

Skov
Skov DA 4200 Technical user guide

KLAN
KLAN K-DP-GLV Series Instructions for use

Hotstart
Hotstart OCLE Installation & operation manual

Tecnosystemi
Tecnosystemi HI-TECH PUR 12300012 user manual

Nibe
Nibe UKV 20-220 Installation and operating manual