Samwha DSP DSP-VIP-PL User manual

Voltage-Current based Digital
Multi-function Motor Protection Relay
DSP-VIP-PL/PM


Content
1. System Construction
2. Detailed Structure
3. Main Feature
4.Specialized Point
5.Function List
6.Technical Specification
7.Protection List
8.Indication List
9.Auxiliary Function
10.Self-diagnostics table
11.Input-Output Terminal
12.Relay Output
13.Presetting Description
14.Control Key Operation
15.Time based Trip Relay Output
16.Trip Indication
17.Current Range Table for external CT
18.Time-Current Characteristics
19.Application Sequence Diagram
20.Rotated Indication
21.Example forApplied Communication
22.PC Operation Program/”SamdspR”
23.Dimension
24.Order Form
25. Guide for user

DSP-VIP-PL/PM
Voltage-Current based Digital Multi-function Motor Protection
Relay
1.System Construction
○DSP-VIP-PL/Panel Mounting Type
○DSP-VIP-PM/ Panel Flush Mounting Type
Cable/RS232
Comm.Module
Converter
Display Meter
#1
#2
#32
RS232
OR
RS232
RS232
Converter
Comm.Module
OR
#1
#2
#32
Loader

2.Detailed Structure
○Converter
○Loader
CT Block
3 Colour LED/Power(G),Operating(R),Trip(Y)
Functional DIP SW
9 PIN D-SUB/RS-232< > Loader
Test/Reset
9 PIN D-SUB/
RS-232< >Comm. Module
Air Vent
Screw Hole
DIN Rail Moving Tip
IN-OUT Termial
Lock Holder
Wire Turn Hole
Wire Terminal

○Display Meter
○Communication Module
RJ45 Connector Hole
With Cover/Input
10P Terminal
/5P-In,5P-
Out
Screw
Hole
9PIN D-Sub/
RS-232
<>Converter
DIP SW/4P:Termination
Resistence,485-422
Outside View
Inside View
Status
LED
9 PIN D-Sub/
RS232< > Converter
by Cable Connector
Menu Bar
5 Digit Display
OFF
Phase LED
ON
Control Key:w/Back
Light UP
CLR
SET
Mode
DN
Front View
Key Cover
Lock Cover
Back View
Round Bar Grapgh

3.Main Feature
Easy Handling
Incoming voltage is indicated orderly while a motor is stopped
To give a guarantee to exclusive operator:Password Input
To realize convenient and various data input
•Loader: DSP-VIP-PL
•Display Meter: DSP-VIP-PM
•Note Book PC: DSP-VIP-PL,VIP-PM
Main/Sub/Cab Menu:Three devided menu group according to usage and the frequency of data input
•Main menu:Data input frequency is rather higher
•Sub menu:Ratherly common application for all kind of motor
•Cab (calibration) menu :adjustable for indicating value within narrow range
(
±
12.7%) /This menu is appeared when "SET" key is pressed for 5 sec or more
and disappeared right after pressing again.
Beautiful inside lighting by every touch button:Easy handling in dark space of the panel.
To Indicate a necessasary information in every 3 sec
•Basic Factor circulating indication:V,I,KW,GR(Ec)/ “OFF” must be set in ”rota” mode
•Basic Factor + PF,Temp,KWH,AWT(Accumulated Working Time)/“ON” must be
set in ”rota” mode/ Possible to fix one of circulated factor or to release:one touch
for CLR Key
•To show load factor(actual/setting)/65% ~ 100%:Line Type/DSP-VIP-PL
,Round Type/DSP-VIP-PM
•
To check preset value during motor run:done by adjusting "SET" & "Mode" key
*Press "SET" key during a motor run,then search mode neccessary to check
, consequently name of mode & preset value is shown alternatively
*not possible to change preset value,only to show preset state.
Duplex Alarm:Higher Alarm,Lower Alarm to OC/Lower Alarm is only possible in case “LinE”
mode is preset for “OFF”
ON-OFF switch/DSP-VIP-PM:to save wiring and labor inside panel
Convenient installation:65Phi circle or rectagular hole(48*96)/DSP-VIP-PM:Display Meter.
To indicate trip number of main contactor:contributing to check a replacing term and
effective maintenance.
To keep a stable operation under frequency variation of Inverter:1Hz ~ 400Hz
To call initialized factory setting value:press test button before power-on,then keep
pressing state for 3 sec after power-on.
Indication for a position of “ON”-"OFF' command to run a motor:in case motor is run or
stopped during the ation by "OFF" or "Auto sensor",a position message like LOP,MCC(Display
meter),rcs(Remote control sensor),out-F(external fault input) and PC that such command
was originated to is appeared in front message window.
Multi-complexed Function
Power type protection relay based on Voltage and Current
To indicate RMS value/Voltage,current:RMS chip adopted in every input/to contribute
to check an exact condition of motor

To act as actual complexed meter:V,I,KW,PF,KWH,Temp
*Voltage Select:110V/220V/380V/440V/480V(110V is secondary voltage of PT)
*Current Meter with CT:0.5A~3600A(Auto Range for decimal point)
*KW Meter:0.1~60000KW(Auto Range)
*Power Factor Meter:
±
0%~100%
*KWH Meter:1KWH~99999999KWH(used "K" unit LED)
*Temperature Meter:0OC ~ 150OC
*Auto Range: to indicate decimal point in conjunction with "K/Test" LED in Loader and DM
To cover a wide current range
*70 Type:0.2A ~70A/0.2A ~ 6A(0.2KW~4.4KW/AC480V) with external CT
*With external CT :0.5~3600A
High sensitive Level and Wide range for ground fault protection:30mA~ 10A
*Standard type/with external ZCT : need to use shield wire for connection between ZCT and
Z1,Z2 terminal of DSP
*Optional type : ZCT embedded
*Alarm to disconnection with ZCT:In case ZCT is disconnected with Z1,Z2 of the
converter after the control power is on,not while operating,the preset process is not
gone ahead anymore as flickering "Ec-ct"/"Off" in "Ec" mode to clear this alarm.
To realize Short,Ground fault protection by instant trip time:0.05 sec
To be acceptable for various rating of ZCT: 200/1.5mA or 200/100mV,selectable in DIP SW
Temperature arising protection of case,winding of motor:sensed by PT100:0C~150OC
*If sensed temperature is greater than preset value, motor can not start
*if PT100 is not connected and the value except "OFF" in "TEP" mode is preset ,alarm
is shown and motor can not start. hence need to preset "OFF" in "TEP" mode to make
a motor start
Various and multiple trip output of Main and Aux relay
*Main/1a(97-98):energized(trip) with an output of C-SC/F-MC/R together
*AUX/1a(07-08):acts same as main trip or one of Shoc/Ec/Uc/AL/Temp/Ec-tE/SS-tr
/Ec-ta/Ec-tb selected in "Au-o" mode
*1a(27-28):trip for Voltage protection,but possible to change into "ALLc"(lower level
alarm) in "Line" mode
To memorize 8 events of the latest trip : to contribute analyzing trouble cause and motor working
condition in conjunction with a number of lighted LED in bar graph to show a order of tripped event.
Main contactor Auto Close:In case a line power is "on" within a preset time(SDDT) after a line power
is "OFF" during a normal operation,main contactor is closed automatically after another preset time
(DOMT)
*Shut Down Delay Time:1~5sec/Adjustable
*Delay On Make Time:0(instant)~25sec/Adjustable by 5 sec unit
*Expression in mode/eg,2-3:in case power is on within 2sec after power-off,motor starts
after 15sec(3 is matched with 15sec) from the instant of power-on
Self-diagonostics:in case of pressing "test" sw in converter or pressing "CLR" key for 3 sec
or more,main trip output is tripped after counting down o-time of definite T-I characteristic or
a time of 550% to "OC" preset value in Inverse T-I Curve ,hence % of bar graph LED shows how
much time is counted down
To have safe operation ,the alarm and the execution not to start motor is done in case as follows:
*PT100 is not connected in case the value is preset in "tEP' mode
*The latest measured temperature is greater than preset value

Remote Control through RS-485/422 digital communication
Various communication module function
* CM44 : 485/422,Modbus/RTU
* MWR-S : 485,Modbus/RTU, 1 month data record/recording interval:50msec/max
Basically 4~20mA output : 20mA for maximum current value among 3 phase
To realize effective system for digital comminication:possible to combine a module simply
if necessary
To response for RS-485/422,Modbus/RTU
To select one of RS 485 and 422 :Simply selectable in DIP SW inside communication module:CM-44
To put easily terminattion resistence in extreme end unit:Simply selectable in DIP SW
inside communication Module
To monitor and input a data by using "samdsp" in the field:Note PC < > Converter of DSP
*PC<RS232>VIP converter:not to need a communication module
*PC<Comm. Module>VIP converter:need 485(Comm. Module)/USB(PC): Protocol
Converter/ DSP-CMB
4.Specialized Point
Power Type= Incoming Line Voltage <==>Load Current

Acceptable with both rating of ZCT
High Level Protetion Class

Convenient Communication Module : DSP-CM-44, MWR-S
a. the interface between Note PC and DSPdirectly by RS232
Note:If DSP is connected through a 9 pin port in PC, the wiring must be changed as follows:
b.Communication module(CM-44)

※Note:The detail about MWR-S(485 & recorder) is described in the
manual for MWR-S
Various and Multiple Indication

5.Function List
Function
DSP-VIP-PL DSP-VIP-PM
Converter
+ Loader Comm.
Module Converter+
D. Meter Comm.
Module
Protection
Over Load/
Over Current
O
O
Under Load/
Under Current O
O
Over Voltage
O
O
Under Voltage
O
O
Phase Loss by
Line Voltage O
O
Phase Loss
by Load Current
O
O
Phase Reverse
by Line Voltage
O
O
Phase Reverse
by Load Current
O
O
Current
Unbalance
O
O
Voltage
Unbalance
O
O
Locked Rotor
O
O
Shock/Stall
O
O
to sense
slight
mech.
Shock
Duplex
Alarm/
Higher/
Lower

Short/Available for Type 10
O
O
Ground Fault
O
O
Over temperature
O
O
Indication
Line Voltage
O
O
Loaurent
O
3 Phase power
O
O
Power factor
O
O
KWH
O
O
Accumulated
working time
O
O
Load factor
/Bar graph O
O
Auxiliary
Y-D Timer
O
O
2 Level Alarm
O
O
Forward-Reverse
O
O
ON-OFF
X
O
Man cntacor
Auto Close O
O
Communication
4~20mA
O
O
RS 485,Modbus
X O X O
RS 232
O
O
Interface with Note PC
O
O
6.Technical
Specification
Division
Description
Line Voltage
3 phase ,AC 100V ~ 600V,50/60Hz
Voltage setting
range
AC 110V
over:110V~150V ,under:70~110V
AC 220V
over:220V~290V ,under:150~220V
AC 380V
over:380~450V ,under:310~380V
AC 440V
over:440V~510V ,under:370~440V
AC 480V
over:480V~550V ,under:410~480V
Current setting
range
70 Type
0.2 ~ 70A/0.2KW ~52.4KW(AC 480V) /0.2 ~
6A(0.2KW~4.4KW/AC480V) with external CT
External CT
Refer Table
Ground protection
Zero Sequence
Current
30mA~10A
Time setting
Starting delay
time(dt)
OFF,0.1 ~300 sec/def, "OFF" selection means
inverse curve

over/under voltage
trip delay time
(ouPt )
0.1~30 sec/def
over load/current
trip delay time(ot )
0.1~60 sec/def,5~30class/inv:refer curve
under
load/current trip
delay time(ut )
0.1~30 sec/def
Shock/stall trip
delay time(st)
0.05 sec/instant, 0.1 ~ 3 sec/def
Ground fault
starting delay
time(Edt)
OFF,1 ~ 25 sec/def
Ground fault trip
delay time(Eot)
*0.05(instant),0.1~ 30 sec/def
*1~10 Class/Inverse,refer curve
Voltage Unbalance
0.5~10sec/Adjustable
SC/F-MC/R
starting transfer
time(ydt)
1 sec~5 min/def(Transit interval time/SC-
end~MC-start:0.2 sec)
Main contactor
Auto Close
*Shut down delay Time:1 sec~5 sec
*Delay On Make Time:0(instant)~25 sec
Phase loss trip
delay time(PLc)
*based on load current
*1~5sec/definite
Allowable tollerance
Voltage
+.- 3%
Current
C<=2A:0.1A,C>2A:+,- 5%
Time
t<=2 sec:+,-,0.1sec, t>2 sec:+,-,5%
Power factor
+,- 5%
KW,KWH
+.-5% , Cos Phi>0.6
Control power
*85VAC~260VAC,50/60Hz(90VDC~370VDC)
*24VAC/DC(optional)
Trip Relay
C1-SC/F-MC/R
1a *2(2-SPST),3A/Resistive
Main
1a(1-spst),3A/Resistive
Aux
1a(1-spst),3A/Resistive
OV/UV
1a(1-spst),3A/Resistive
/possible to use for 2nd alarm(lower level alarm
to "OC") under "Line" mode is OFF or
short circuit trip under both OP & UP is OFF
GR
1a,3A/Resistive(Aux output must be set "GR" in
"Au-o" mode)
Application
environment
Temperature
Operation
-25OC ~ +70 OC
Storage
-40 OC ~ +80OC
Relative
humidity
30 ~ 85%,non-condensing
Current tollerance against changeable
frequency in inverter
Avg ±3% in 1Hz ~ 400Hz
Logic Input
*220VAC:150∼260VAC,50/60Hz(220∼370
VDC)/Standard

*110VAC:75∼150VAC,50/60Hz(110∼220
VDC)/Optional
Max Conductor Size
25sq
Screw Torque
Max 0.6 N.m
Insulation Resistence/IEC-60255-5
10Mohm or more/500VDC,circuit-case
High Voltage Withstand Test/
IEC-60255-5
*circuit-case:AC 2000V,60Hz, 1 min
*contact-contact:AC 1500V,60Hz,1 min
Lightning Impulse Voltage Withstand
Test)/ IEC-60255-5
*Circuit-Ground,Circuit-Circuit:1.2/50uS,5KV
*Control Circuits:1.2/50uS, 3KV
1 MHz Burst Immunity Test: IEC- 60255
-
22-1
2.5KV,Positive/Negative under
2sec
Electrostatic Discharge:IEC-60255-22-2
Air:Level 3, 8KV,Contact:Level 3,6KV
Radiated Electromagnetic Field
Disturbance:IEC-60255-22-3
Level 3, 10V/m
Electric Fast Transient Burst:IEC-60255-
22-4
Power,Realy output:Level 4,4KV
Surge Immunity test:IEC- 60255-22-5
Relay output:1.2X50uS,2KV(0O,90O,180O,270O)
Conducted Disturbence Test:
IEC-60255-22-6
10V,Level 3
Digital
Communication with
communication
module/recorder
Physical feature
*RS 485/ RS 422 : CM-44
8*RS485 : MWR-S
Address
1 ~ 250
Speed
*MWR-S:9.6/19.2/38.4/57.6/76.8/115.2kbps
*CM44: 9.6/19.2/38.4kbps
wiring
connection
*Input/Output:RJ 45 ot Screw Terminal
*RJ45 and Screw Terminal(5P) is commoned
Physically
*RJ45 is recommended for the test by "Samdsp"
Termination
resistence
*DIP S/W selection / 200 Ohm
Cable
Sheathed cable,2 Pair
Current Loop Communication:4 ~
20mA
Maximum value in 3 phase current
Consuming power
10W max
7. Protection List
Item Description Remarks
Over Voltage
*110V:110~150
*220V:220~290
*380V:380~450
*440V:440~510
*480V:480~550
*The 3 phase voltage over upper level of
each range makes trip by over voltage.
*The trip caused by a voltage is reset
automatically after reaching over preset
value
*Only 110V is based on a secondary
voltage of PT
*If line voltage is under preset value in
initial starting state,motor can not start.

Under Voltage
*110V:70~110
*220V:150~220
*380V:310~380
*440V:370~440
*480V:410~480
*The 3 phase voltage under lower level of
each range is not sensed,but assumed
zero.
*The trip caused by a voltage is reset
automatically after recovering to level of
preset value
*If line voltage is under preset value in
initial starting state,motor can not start.
Over Load(KW)
Trip is done if the load(KW)
greater than preset value is
kept over preset o-time
Over Current
Trip is done if the load
current greater than preset
value is kept over preset
o-time
Under Load(KW)
Trip is done if the load(KW)
smaller than preset value is
kept over preset u-time
Under Current
Trip is done if the load
current greater than preset
value is kept over preset o-
time
Current
Unbalance
*Trip is done if the preset
current unbalance rate is
kept over 8 sec.
*rate=[(max curr.-min
curr.)/max curr.]*100[%]
Voltage
Unbalance
*Trip is done if the preset
voltage unbalance rate is
kept over preset time.
*rate=[(max voltage-min
voltage)/max voltage] * 100
[%]
Preset time:0.5~10sec/adjustable
Locked Rotor
Trip is done if 300% current
greater than preset “oc” is
kept for d-time plus 0.1 sec.
Shock/Stall
(instant over
current/shock)
*Trip is done if a current
greater than preset value
during working is happened
for preset time.
*Preset range:180%~700%
to “OC”
*upper limit for 70 type is based on
[(200/OC setting value)*100(%)]
Short
*If load current is greater
than preset value,output
relay is trip within 0.05 sec
*Preset range:800%~2000%
to "OC"
*Trip time : within 0.05sec
*Available “OC” preset range in 70 type
is 0.2A~10A for shot protection
*Available ”OC” range in the usage of
external CT is 0.2A~6A
*AUX(07-08) output is available to
Operate MCCB with enough current
capacity as SS-tr is selected in “Auo”
mode

Ground Fault
Trip is done if a current
greater than preset zero
phase current is kept for
Eot(earth operating time)
*according to selection of DIP SW:ZCT
rating is used for 200mA/1.5mA or
200mA/100mV
Over
temperature
*Trip is done if the
temperature sensed by
PT100 greater than preset
temperature is kept over 8
sec
* If sensed temperature is
greater than preset value,
motor can not start
Phase Loss by
line voltage
*This protection is identified
by line voltage
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If each of 3 phase is a state of phase loss
in the same time,which means normal
"power off", this mode does not response
to such state
*If phase loss is happened, auto reset is
not possible,but manual reset.
Phase Loss by
load current
*This protection is identified
by load current
*Trip time:1~5 sec/definite.
*"OFF" is possible in this
mode
*If phase loss is happened,auto reset is
not possible,but manual reset.
Reverse Phase by
line voltage
*This protection is identified
by line voltage
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If reverse phase is happened ,auto reset
is not possible ,but manual reset.
Reverse Phase by
load current
*This protection is identified
by load current
*Trip time is within 0.5 sec.
*"OFF" is possible in this
mode
*If reverse phase is happened, auto reset
is not possible,but manual reset.
8. Indication List
Item
Description
Remarks
Line Voltage
Incoming Line/V1,V2,V3 or Average
voltage(selected in "trans" mode of
"cab" mode group)
*110V is based on a
secondary voltage of PT
*In case incoming voltage is
zero in the same time:OFF
is shown
Load Current
L1,L2,L3
Temperature/cas
e,winding
1OC ~ 150OC/scale 1OC
Power factor
COS Phi
In case of 110V, it is based
on secondary voltage of PT
for correct calculation

Accumulated
KWH
*if a current greater than 0.2A is
loaded,KWH is accumulated every 6 min.
*possible to record 99999999 KWH
*to clear existing accumulated KWH: in
"hp-c" mode ,press "DN" under pressing
"UP" at first ,then finally make both
pressing state ,and reversely release "UP"
after releasing “DN” at first
Accumulated
working time
*if a current greater than 0.2A is loaded,
working time is accumulated in every 6
min
*range:0~6553.5 hr,next to zero
*to clear an existed value , use the way to
call initial factory default value
preset time to
make alarm for
working time
*indicating a trip event number of main
contactor
*range:1~65535, next to zero
*to clear existing accumulated number in
“Alt” mode :refer a case of KWH
Trip
number/main
contactor
*indicating trip number of main contactor
*range:1~65535, next to zero
*to clear existing accumulated KWH:refer
a case of KWH
Load factor by
bar graph
*calculating % as followed.
[actual load curr./preset curr.]*100[%] or
[actual load kw/preset load kw]*100[%]
*Line type/DSP-VIP-PL ,round type/DSP-
VIP-PM
*indicating only ALhc(higher level alarm)
Alarm before
trip
*preset "AL" in "Au-o" mode ,then make
level % in "Alhc" mode
*1c is closed(energized) if actual level %
exceeds preset level %/Available even
when a condition is keeping for 3 sec
9.Auxiliary Function
Item
Description
Remarks
SC/F-MC/R
transfer timer
*Providing transfer time from Y to Delta
*Adjustable transfer time:1sec ~ 5 min
*Transit interval time from Y-End to D-Start :0.2
sec
*dt is available for each during Y and D contactor is
"on" state
DC 4~20mA
*To change max current among 3 phase into 20mA
*The receiver for 4-20 signal does not need loop
voltage
Password
*The preset procedure in a mode is possible as
inputing password for a exclusive operator to have
gurantee for operation

Self-diagnostics
*Main trip relay will be trip(energized) after count
down a preset o-time(dt or time of 550% in inverse)
in "Test" SW of converter or in press "CLR" SW
for 3 sec to check if a self-function is normal or
not.
Main contactor
Auto Close
*In case a line power is "on" again within a preset
time after a line power is "OFF" during a normal
operation,main contactor is closed automatically
after another preset time(DOMT)
*Shut Down Delay Time:1~5sec
/Adjustable
*Delay On Make Time:0(instant)~25sec/
Adjustable by 5sec unit
*Expression in mode:eg/2-3:in case power is
"on" within 2sec after power-off,motor starts
after 15sec((3 is matched with 15sec)
from the instant of power-on
10. Self-diagnostics table
Discription
Message display
Initial state display
When the control power is on,the disply is shown in
the order as follows: LOP(default)
tE-no(if PT-
100 is not connected)
version NO.--> ON/OFF
control command position(one of LOP, MCC/display
meter , rcs and PC)
485 communication error
LED on the communication module is not turned on
or not flickered
Fault for internal current board
cu-no
Fault for internal voltage board
vo-no
Fault for GR protection function in
internal main board
Ec-no
ZCT disconnection
Ec-ct
PT100 disconnection
te-no;not possible to rum if a value is preset in"tep"
mode
Latest measured temperature
greater than preset temperature
"tep" and "latest measured value" is appeared
alternatively/not possible to run if preset value is not
changed
Test:by Test SW in converter or
"CLR" SW
Main trip(97-98) is tripped after counting down
preset o-time in definite T-I(550% time in inverse T-
I)/the number of lighted LED is matched with
counted time
This manual suits for next models
1