Samwha DSP DSP-DVR User manual

Digital 3 phase Voltage Relay
<DSP-DVR/DVR-M,DM II Meter>

Contents
1. Abstraction
2. Main Features
3. Operation Time
4.Technical Specification
5.Preset Description
6. The order of Rotated Mode
7.PIN Assignment
8.Indication
9.Control Key Operation
10.Over voltage trip time characteristic
11.Trip Indication
12.Rotated Indication
13.Time-Voltage based Trip Output
14.Application Sequence Diagram
15.Dimension
16.Order Form

Digital 3 phase Voltage Relay
<DSP-DVR/DVR-M,DM II meter>
1.Abstraction
Installation
Model
Protection
Indication
Panel Mounting
Type
DSP-DVR
*Over Voltage
*Under Voltage
*Phase Loss
*Reverse Phase
*Line/Average Voltage
*Frequency
Panel Flush
MountingType
DSP-DVR-M
Panel Mounting Type
Panel Flush Mounting Type

2.Main Features
MCU based control, 8 Pin Type Compact size
Easy Installation
: Panel Mounting Type →DSP-DVR
: Panel Flush Mounting Type →DSP-DVR-M
Operation based on direct line voltage detection
: Protection : Over/Under voltage, Phase Loss, Reverse Phase, Voltage Unbalance
: Indication : Voltage[Line/Average], Frequency
:Time-Voltage operational characteristic → Definite / Inverse
Over/Under Voltage Protection
:Rated Line Voltage → 100 ~ 500VAC
:Over Voltage protection Range → within (+) 20% to line voltage
: Under Voltage protection Range →above (–) 20% to line voltage
Possible to preset operation time for over/under voltage each, repectively
Perfect check for initial line state
a)”dt”(trip delay time) mode is preset “OFF”
▸Preset “a”in “out”mode
:Main trip output(95-98) is energized (Open → Close ) in case the rated line voltage with normal
forward phase state is sensed initially
: Main trip output(95-98) is trip(Close →Open) within 0.5sec after energizing(Open→Close)
if the initial state is under phase loss
: Main trip output(95-98) is trip(Close →Open) after operational preset time is elapsed from
instant energizing point(Open→Close) as showing a trip cause if the initial line state is under
over/under voltage,reverse phase, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
while the normal operation is doing.
▸Preset “b” in “out” mode
:Main trip output(95-98) is not energized (Open → Open ) even if the rated line voltage with
normal forward phase state is sensed initially
: Main trip output(95-98) is trip(Open →Close) within 0.5sec if the initial state is under phase loss
: Main trip output(95-98) is trip(Open →Close) after operational preset time is elapsed as showing
a trip cause if the initial line state is under over/under voltage,reverse phase, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
b)”dt”(trip delay time) mode is preset a value(time)
▸Preset “a”in “out”mode
: Main trip output(95-98) is energized (Open → Close ) after “dt”is elapsed in case the rated line
voltage with normal forward phase state is sensed initially
: Main trip output(95-98) is still opened(not trip) even after “dt”is elapsed if the initial state
is under phase loss,also “PL’is shown
: Main trip output(95-98) is energized (Open →Close) right after “dt”is elapsed if the initial line
state is under over/under voltage, voltage unbalance, and then it is trip(Close →Open) after
operational preset time is elapsed from energizing point(Open→Close) as showing a trip cause

: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
while the normal operation is doing.
:”rP” is shown as main trip output(97-98) is still opened(not trip) after operational trip time
(0.5sec) without concerning with “dt”if reverse state is sensed initially
▸Preset “b” in “out” mode
: Main trip output(95-98) is not energized (Open → Open ) in any case
: Main trip output(95-98) is trip (Open →Close) after “dt”is elapsed if the initial state is under
phase loss as “PL’is shown
:Main trip output(95-98) is trip (Open →Close) right after “dt”is elapsed as showing a trip cause
if the initial line state is under over/under voltage, voltage unbalance
: v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0)
:”rP” is shown as main trip output(97-98) is still closed(not trip) after operational trip time
(0.5sec) without concerning with “dt”if reverse state is sensed initially
Trip cause is shown by characters and/or numbers
: 4 Digit Window/DVR Type
: 5 Digit Window/DVR-M Type
3 phase line voltage/average voltage and /or frequency is shown ordery in every 3sec
Stored the information for latest 8 trip event.
Reset after a trip : auto or manual
Self-diagnostics to check if this relay is ready to work or not.
3.Operation Time
Over Voltage
*definite :0.2~20sec
*Inverse :1~10 Class
*ovt” mode
Under Voltage
1~20sec : “uvt” mode
Reverse Phase
Within 0.5sec/initial phase state
Phase Loss
0.5~5sec : “PL” mode
Voltage Unbalance
1~10sec :” v-ut” mode

4.Technical Specification
DIV
Description
Line Voltage
Line Input:V1,V2,V3
100 ~500VAC,50/60Hz
Protection range
Over voltage
Under 20% based on the line voltage
Under voltage
Over 20% based on the line voltage
Time preset
Protection delay time(dt)
1~60 sec/definite
Over voltage trip delay
time(ovt)
*0.2~20 sec/definite
*1~10 Class/inverse
Under voltage trip delay
time(uvt)
1~20 sec/definite
Reverse Phase(RP)
Within 0.5 sec
Phase Loss(PL)
0.5~5sec/definite
Voltage unbalance
1~10sec
Allowable tolerance
Voltage
±3%
Time
*t<=2sec:± 0.2sec, t>2sec:±10%
*Reverse phase:+10%
Control power
*AC 85V∼AC260V,50/60Hz (DC90V∼DC370V)
*DC24V(Optional)
Trip output relay
95-96-98
1c(1-SPDT),5A/Resistive
Application
environment
Temperature
Operation
-25OC∼+70OC
Storage
-40OC∼+80OC
Humidity
30∼85% , relative/non-condensing
Insulation Resistence/IEC-60255-5
Case–Circuit: 10Mohm/500VDC
High Voltage Withstand Test/
IEC-60255-5
*Case–Circuit:AC2000V,60Hz,1 min
*Contact-Contact:AC 1000V,60Hz,1 min
Lightning Impulse Voltage Withstand Test/ IEC-
60255-5
*Circuit-Ground,Circuit-Circuit: 1.2/50(uS),5KV
*Control Circuits:1.2/50(uS), 5KV
1 MHz Burst Immunity Test:IEC 61000- 4-18
2.5KV,Positive/Negative under 2sec
Electrostatic Discharge:IEC-61000-4-2
Air :Level 3, 8KV,
Contact:Level 3, 6KV
Radiated Electromagnetic Field
Disturbance:IEC-61000-4-3
Level 3, 10V/m
Electric Fast Transient Burst :IEC-61000-4-4
Power,trip output:Level 4,4KV
Surge Immunity test:IEC-61000-4-5
trip output :1.2X50uS,2KV(0O,90O, 180O , 270O)

Conducted Disturbence Test
:IEC-61000-4-6
10V, Level 3
Screw Torque
Max0.6N.m
Consuming power
4W Max
5.Preset description
▶Main Mode
Press "SET" key to enter into setting mode ,then enter password. The more detail is
described in "Operation of Control key "
Mode
Function
Description
Factory
Default
P***
Password input
* "P000"(factory default password) is shown
*Move cursor from first digit to right end digit by
pressing "CLR" key,finally press once more if
password is not changed from factory default value, but
if password is changed, then make required digit by
using "UP","DN" key untill operator meets changed
password.
*Make power-on again as keeping both “UP” and
“DN” key pressed under power-off in order to make an
initialization to factory default
000
Out/a/b
to select initial
state of main
trip output
* initial state of main trip output is defined as followed
condition.
▸a : main trip output/95-98(1a) is energized
(open→close) in case normal forwarded voltage is
sensed after control power is loaded
▸b : main trip output/95-98(1a) is not energized
(open→open) in case normal forwarded voltage is
sensed after control power is loaded
* initial trip is happened without concerning with above
definition for initial state if one of over/under
voltage,voltage unbalance,phase loss and reverse
phase is sensed
▸phase loss : trip right after sensing.
▸reverse phase,voltage unbalance,over/under
voltage : trip after preset time is elapsed.
a
LInE/OFF/
setting Value
to select line
voltage
*OFF:the sensed voltage is only shown as trip output is
not come out
* to define the value of incoming line voltage:100~
500VAC
440

PhAS/
1P/3P
to select
phase of power
line
*1P:single phase motor/disable for phase loss & reverse
phase, voltage unbalance /voltage must be loaded
between L1 and L2
*3P:3 phase motor protection
3P
trAn/L/A
to select a base
to display
incoming
voltage
*L : to show line voltage
*A : to show average voltage
L
dt/OFF/setting
value
to preset a time
to stop
protection
function
*OFF : disable
*1~60sec/definite,adjustable
*all protective function except reverse state is stopped
during “dt”,but detected voltage is shown
OFF
ov/OFF/setting
value
to protect over
voltage
*OFF : disable
*to protect over voltage according to preset value in
"LInE" mode
*protection range : under 20% based on line input
voltage
*Auto reset is possible only after a sensed voltage
is dropped under preset valued voltage after a time
of “AUo”mode is elapsed continuously
*Auto reset is done in case line voltage is not loaded
*This mode is not available in case initial PL(phase loss)
is happened
OFF
Otc/dEF/Inv
to define
voltage-trip
time
charateristics
*dEF : definite
*Inv : Inverse
dEF
ovt/setting
value
to preset trip
delay time to
protect over
voltage
*to preset trip delay time after sensed voltage is over
preset value
*definite : 0.2∼20sec/adjustable
*inverse : 1~10 Class
1
uv/OFF/
setting
value
to preset trip
delay time to
protect ubder
voltage
*OFF : disable
*to protect under voltage according to preset value in
"LInE" mode
*protection range:over 20% based on line input voltage
*Auto reset is possible only after a sensed voltage is
risen over preset valued voltage after a time of “AUo”
mode is elapsed continuously
*This mode is not available in case initial PL(phase loss)
is happened
OFF
uvt/setting
value
to preset trip
delay time to
protect under
voltage
*to preset trip delay time after sensed voltage is under
preset value
*1∼20sec/definite,adjustable
10

PL/oFF/ setting
value
to protect phase
loss by
incoming line
voltage
*OFF : disable
*trip in case voltage unbalance rate is over 45%
:[(max-min)/max]*100[%]
* 0.5 ~ 5 sec/definite,adjustable
*In case 3 phase is normal power-off state, this mode is
not worked.
*This protection is not available for the load such as a
motor which the reversed voltage can be created by the
internal common point of 3 phase line ,but available for
initial phase loss
*This mode is not available for single phase line.
OFF
RP/oFF/ setting
value
to protect
reverse phase
by incoming
line voltage
*OFF : disable
* within 0.5sec
*In case 3 phase is normal power-off state or phase
loss state , this mode is not worked.
*Auto reset is not possible,but manual reset.
*”dt”is not interfaced with this mode
OFF
v-Ub/oFF/
setting value
to preset
voltage
unbalance
protection
rate(%)
*trip in case preset rate condition is kept on preset time
or more
*rate:[(Max V-Min V)/Max V]*100 [%]
*adjustable range:5%~30%
oFF
v-Ut/setting
value
to preset
operating trip
delay time for
voltage
unbalance
* to preset a operating trip time for voltage unbalance
*Adjustable range: 1~10 sec
3초
rESt/Hr/Er
to decide how
to reset trip
state
*to decide how to reset in case of trip
*Hr : manual reset by key touch
→Password Input :rP ,PL/trip state is still remained
even in case of power OFF-ON,but possible only
by password input
→”CLR”key: OV,UV,v-UB
→not possibl to preset setting value under trip state
*Er : electrical reset
→"CLR" Key
→Control power off
→Auto reset
: “OV”, “UV”, “v-Ub”
:possible to reset naturally after preset time by
“AUT”mode is elapsed if trip cause is clear
→not possibl to preset setting value under trip state
Er

caused by “PL”and “RP”,but possible to preset
under trip state caused by “OV”, “UV”and “v-Ub
Aut
to decide auto
reset time
*possible to preset auto reset time in case “Er”is preset
in “rESt”mode
*1sec~10 sec
3
rotA/ON/OFF
to decide
additional
factor besides
basic factor to
indicate value
in the order
*OFF/basic factor : line voltage/average voltage
[L1,L2,L3] to indicate orderly in every 3 sec.
*ON : frequencty is added to basic factor
*possible to fix one of rotated factor or to release as
pressing "CLR" key repeatedly
OFF
trIP /8 ~1/trip
cause / trip
value
to show latest
8 trip cause
orderly
*to check latest 8 trip cause
*press "UP" or "DN" in the "trip" mode, then trip cause
and value is shown alternatively
*press "CLR" or ""SET" to check next event or previous
event
*In order to enter setup state on the way of trip condition
check, press "DN" or "UP"
- -
v-ot/oFF/
setting
value
to preset delay
time to show
“v-oFF’ if
voltage is not
detected while
working
*oFF : disable for this mode
*preset time:1sec~10sec
*”v-ot” is shown initially if voltage is not detected
during an operation, but finally ”v-oFF’ is shown after
preset time is elapsed
*operational condition for “v-oFF” in “out” mode
shall be applied for this mode as well
Test
*to check if this relay is ready to work normally or not.
*"tESt" is appeared in case the operator press "CLR" key for 3 sec or more,
then release pressed "CLR" key when “tESt”is shown
*Trip output(95-98) will be energized after counting down preset ovt-time
*press “CLR”key to reset after test trip
▶Cab(calibration) Mode
This mode is appeared as pressing "SET" key for 10 sec or more ,and is disappeared
as "SET'key once more
Mode
Function
Description
Factory
Default
P***
Password
Input
*need to input password to adjust this mode group so that
authorized person may be able to adjust.
*How to input is aame as it of main mode
000
vrPE
to have a
*to show present sensed voltage
0

calibration for
phase "L1"
voltage
*Possible to adjust with +,- 1V step size with 100V adjust
range
vsPE
to have a
calibration for
phase "L2"
voltage
0
vtPE
to have a
calibration for
phase "L3"
voltage
0
`
to change
Password
*Possible to enter new digit by using "UP" or "DN" key
after positioning a cursor on the required digit
*Press both "SET" & "CLR" key in order to come out
setting mode and the changed password is stored.
000
6. The order of Rotated Mode

7.PIN Assignment
DIV
Socket Pin
Description
Input
2
* Control Voltage/AC 85V∼AC260V,50/60Hz
(DC90V∼DC370V)
7
5
3 Phase application
Phase L1 voltage
4
Phase L2 voltage
3
Phase L3 voltage
5
1 phase application
Phase L1 voltage
4
Phase L2 voltage
Output
6-8-1
Main trip/95-96-98,1c(SPDT)
8. Indication feature

9.Control key Operation
*Note: trip will be occurred after completing preset process if trip condition is happened
during preset process
1.”SET” key
*Press "SET" Key to enter into setting mode, then "P000"/”P0000”(factory
default password) is shown
*Move cursor from first digit to right end digit by pressing "CLR" key,
finally press once more if password is not changed from factory default
value, but if password is changed, then make required digit by using
"UP","DN" key untill operator meets changed password.
*If there is no input for 15sec or pressing both "SET" and "CLR"key, it can
be entered into operating condition.
2. Changed
feature of Setting
Key
*After entering into possible state for preset , each key acts its job as
follows :SET→backward direction ,CLR→foward direction ,UP,DN→
able to select number or character in preset mode.
*The previous mode based on setting mode is come out as pressing "SET"
key during doing a prest job
3."SET" Key &
"CLR" Key/ to
select MODE
*Possible to select Mode by using "SET" or "CLR" key
4."UP" key &
"DN"Key/Adjust
*Possible to preset required value as selection a character or number by
using UP/DOWN
5."SET" &
"CLR"Key/
Store
*The storage for preset data is completed by pressing both SET and CLR
key in the same time or after 15sec is elapsed
*The character and/or a number that is already preset in the above preset
process is stored in one times.
6.“CLR" key
*While each factor is rotated, one of rotated factor is fixed by pressing
"CLR" key and released as pressing once more
*After fixing a operating factor, the operator is able to rotate manually one
by one as pressing "UP"(forwardly), "DN" (reversely)
*Average voltage is shown without rotating if average voltage is selected.
To check and/or
change preset
value of each
mode during
operation
*possible to check preset and/or change value of each mode as pressing
“SET” key once during operation,
*”P000”/”P0000”is shown as pressing “SET”key
*preset value and mode are appeared alternatively and to check an/or change
preset value
*next mode as pressing “CLR” Key

*return to operating mode as pressing both “SET” and "CLR" key or waiting
for 15sec without any touch
Self-Test/Reset
: "CLR" Key
*to check if this relay is ready to work normally or not.
*"tESt" is appeared in case the operator press "CLR" key for 3 sec or more
only in case control power is loaded,without loading V1,V2,V3 , then
release pressed "CLR" key
*Trip output(95-98) will be trip after counting down preset ovt time as
showing “0-0”
*Make reset a trip as press “CLR” key once more
10.Over voltage trip time characteristic

11.Trip indication
Trip cause and caused value is appeared alternatively
Trip
Display
Cause
Over voltage
*trip caused by over voltage in phase
L1-L2
Under
voltage
*trip caused by under voltage in phase
L1-L2
Reverse
phase
* trip caused initially by reverse phase of
incoming power line
Phase loss
*trip caused by phase loss of incoming power
line, phase L2
*Indication is shown based on “RP”condition if
phase loss is occurred under “RP”state
Volarge
unbalance
*trip caused by voltage unbalance in L1-L2
*The difference value of [max-min] and “vub” is
shown anlternatively
Zero voltage
*to show that voltage is not sensed
*The operation voltage is dropped under 35V
while normal operation is done or zero(0)
initially

12. Rotated indication
▸If line voltage value with normal phase order is sensed after the control power is loaded, then 3
phase line voltage indication is rotated
▸output(95-98) is energized (Open→Close) as normal phase voltage is loaded if out”mode is
preset “a”
▸output(95-98) is not energized (Open→Open) if out”mode is preset “b”
▸however v.oFF is shown if the voltage is not sensed or the voltage is dropped into 0V(Zero Volt)
while normal operation is done
▸If single phase is applied. V-OFF or actual voltage is shown
▸”dt”(trip delay time) mode is preset “OFF”
a)Preset “a”in “out”mode
•Main trip output(97-98) is trip at once in case initial line phase state is phase loss
•Main trip is energized ,then is trip after operational trip time is elapsed in case initial line phase
state is under reverse phase,over/under voltaege and voltage unbalance as each mode is preset
valued condition,also trip cause is shown

b)Preset “b”in “out”mode
•”PL” is shown during “dt” in case initial line phase state is phase loss, consequently main trip
output(97-98) is trip right after “dt”is elapsed
•Main trip output(97-98) is trip after the sum of “dt”and operational time is elapsed in case initial
line phase state is under reverse phase,over/under voltaege and voltage unbalance as each mode
is preset valued condition,also trip cause is shown
▸”rotA”Mode : OFF →voltage of L1, L2, L3
▸”rotA”mode: ON →voltage of L1,L2,L3, Frequency

▸Average voltage : same as a case of line voltage by “rotA”ON,OFF
▸Bar graph indication : DSP-DVR-M Type
Operational state
The ratio of a sensed voltage to preset “ov”value is shown
e.g. preset value for “ov”:400V, sensed voltage :320V, then bar graph:80%
Trip state

13.Time-Voltage based trip output
▸Over Voltage : “out”mode/a, trip caused by over-voltage during a normal operation
▸Over Voltage : “out”mode/b, trip caused by over-voltage during a normal operation

▸Over/Under voltage: “out”mode/a, auto reset after trip during a normal operation
▸Over/Under voltage: “out”mode/b, auto reset after trip during a normal operation