Sanken S06-4A005-B User manual

High Performance Vector Control Multifunction Inverter
S06
Instruction Manual

- 1 -
ThankyouforpurchasingtheSankenHighPerformanceVectorControlInverter .
[For Safe Use]
Please read the instructions thoroughly and use it correctly before using this product.
After reading, please keep this manual near to the machines for convenient reference.
Expressions and meanings of safety notes
Danger This symbol indicates a hazard that could lead to death or serious injury if the warning is ignored and the
product is handled incorrectly.
Caution This symbol indicates a hazard that could lead to injury or damage to property if the warning is ignored and
the product is handled incorrectly.
Furthermore, even an instruction marked [Caution] can also cause serious consequences under certain circumstances. Be sure to
abide by all instructions in this manual, irrespective of the degree of danger.
Meanings of graphic symbols
This symbol indicates a potential danger.
The specific content of danger is indicated within Ì. (this example indicates a general danger.)
Gengeral danger
Electric shock
danger
Fire danger
This symbol indicates the need for caution.
The specific content of caution is indicated within Ì. (This example indicates a general caution.)
Gengeral danger
Caution: risk of
electric shock
Caution:risk of
rotating objects
This symbol indicates a prohibition (strictly prohibited).
The specific content of prohibition is indicated within . (This example indicates a general
prohibition)
General prohibition
Disassembly is
prohibited
The use of open
fire is prohibited.
This symbol indicates an action that must be performed (the project that must be performed).
The specific content is indicated within. (This example indicates a general compulsory item.)
General
compulsory item
Must be grounded

- 2 -
CONTENTS
1. Safety Notes ...................................................................................... - 5 -
1-1 Important notes .......................................................................... - 5 -
1-2 Notes on Use ............................................................................. - 5 -
1-3 Notes on Installation .................................................................... - 5 -
1-4 Notes on Handling and Moving ............................................................. - 6 -
1-5 Notes on Wiring .......................................................................... - 6 -
1-6 Notes on Operation ....................................................................... - 7 -
1-7 Notes on Maintenance and Inspection ...................................................... - 7 -
1-8 Disposal ................................................................................. - 7 -
1-9 Others ................................................................................... - 7 -
2. Product Validation and Precautions on Use................................................... - 8 -
2-1 Product validation ....................................................................... - 8 -
2-2 Example of nameplate label ............................................................... - 8 -
2-3 The meanings of the model ................................................................ - 8 -
2-4 Precautions on Use ....................................................................... - 8 -
3. Installation............................................................................... - 10 -
3-1 Installation Location and Storage ....................................................... - 10 -
3-2 Installation Direction and Space ........................................................ - 10 -
3-3 Sketch of Front Cover Removal and Installation .......................................... - 11 -
4. Wiring..................................................................................... - 12 -
4-1 Connection with peripheral devices ...................................................... - 12 -
4-2 About Wiring ............................................................................ - 13 -
4-3 Terminal Wiring Diagram ................................................................. - 14 -
4-4 Composition of Main Circuit Terminals ................................................... - 15 -
4-4-1 Description of Main Circuit Terminals ............................................ - 15 -
4-4-2 Connection Diagram of Main Circuit Terminals ..................................... - 16 -
4-4-3 External brake resistor selection example ........................................ - 17 -
4-4-4 Capacities of MCCB and MC as well as Wire Size ................................... - 17 -
4-5 Composition of Control Circuit Terminals ................................................ - 18 -
4-5-1 Wire size and terminal arrangement ............................................... - 18 -
4-5-2 Schematic of control circuit terminal wiring ..................................... - 18 -
4-5-3 Functional list of control circuit terminals ..................................... - 18 -
4-5-4 Descriptions on control circuit terminal wiring .................................. - 20 -
4-6 Installation and Wiring of Optional Board ............................................... - 22 -
4-6-1 Overview of Optional Board ....................................................... - 22 -
4-6-2 Installation Method of Optional Board ............................................ - 22 -
5. Operation Panel............................................................................ - 23 -
5-1 Names and Functions of Parts of the Operation Panel ..................................... - 23 -
5-2 Description of keys on operation panel .................................................. - 24 -
5-3 Display mode of operation panel ......................................................... - 24 -
5-3-1 Version Display .................................................................. - 24 -
5-3-2 Inverter status mode ............................................................. - 25 -
5-3-3 Alarm display .................................................................... - 27 -
5-3-4 Frequency input .................................................................. - 27 -
5-4 Basic operation ......................................................................... - 28 -
5-4-1 Setting function code ............................................................ - 28 -
5-4-2 Confirming operation ............................................................. - 28 -
5-4-3 Signed operation ................................................................. - 29 -
5-5 Special functions ....................................................................... - 29 -
5-5-1 Copy function operation .......................................................... - 29 -
5-5-2 Changed code display operation ................................................... - 30 -
5-5-3 Function code initialization operation ........................................... - 30 -
5-5-4 Alarm contents reading operation ................................................. - 31 -
5-5-5 Alarm status confirmation operation .............................................. - 31 -
5-5-6 List of 7-segment monitor display ................................................ - 32 -

- 3 -
6. Operation.................................................................................. - 33 -
6-1 Operation steps ......................................................................... - 33 -
6-2 Test run ................................................................................ - 34 -
6-2-1 Confirmation before power input .................................................. - 34 -
6-2-2 Confirmation after power input ................................................... - 34 -
6-2-3 Basic setting (1) ................................................................ - 34 -
6-2-4 Motor control setting ............................................................ - 34 -
6-2-5 Basic setting (2) ................................................................ - 35 -
6-2-6 Motor parameter auto tuning ...................................................... - 35 -
6-2-7 Basic setting (3) ................................................................ - 38 -
6-3 Special functions ....................................................................... - 40 -
6-3-1 JOG operation .................................................................... - 40 -
6-3-2 Hold operation ................................................................... - 41 -
6-3-3 Notes on free run stop terminal (MBS) ............................................ - 41 -
7. Function Code .................................................................................... - 44 -
7-1 Representation and Description of Function Codes ........................................ - 44 -
7-2 Function Code List ...................................................................... - 44 -
7-3 Description of Functions ................................................................ - 62 -
7-3-1 Basic functions .................................................................. - 62 -
7-3-2 Input/Output-Related Functions ................................................... - 89 -
7-3-3 System functions ................................................................ - 100 -
7-3-4 Special functions ............................................................... - 109 -
7-3-5 Multi-speed Function ............................................................ - 115 -
7-3-6 PID Function .................................................................... - 128 -
7-3-7 Communication function .......................................................... - 143 -
7-3-8 Motor parameters ................................................................ - 145 -
7-3-9 Vector Speed Control ............................................................ - 147 -
7-3-10 Torque control .................................................................. - 155 -
7-3-11 Single-Inverter Multi-Pump Water Supply ......................................... - 161 -
7-4 Serial Communication Function .......................................................... - 164 -
7-4-1 Outline ......................................................................... - 164 -
7-4-2 Terminal functions and wiring methods ........................................... - 165 -
7-4-3 Operation and function code setting by serial communication ..................... - 165 -
7-4-4 Communication with dedicated protocol (SANKEN communication protocol) ........... - 167 -
7-4-5 Programming Design .............................................................. - 168 -
7-4-6 ModBus-RTU Communication ........................................................ - 181 -
8. Protection & Error Function............................................................... - 190 -
8-1 Operation error ........................................................................ - 190 -
8-2 Conflict & interference error .......................................................... - 190 -
8-3 Warning Status ......................................................................... - 194 -
8-4 Alarm Status ........................................................................... - 194 -
9. Fault Analysis............................................................................ - 198 -
10.Maintenance & Inspection ........................................................................ - 199 -
10-1 Precautions on Checking and Maintenance ................................................ - 199 -
10-2 Inspection Items ....................................................................... - 199 -
10-3 Part Replacement ....................................................................... - 200 -
10-4 Megger Test ............................................................................ - 200 -
10-5 Electrical measurement of main circuit ................................................. - 201 -
11.Specification Parameters ........................................................................ - 203 -
11-1 Standard specification ................................................................. - 203 -
11-2 Inverter general specification ......................................................... - 204 -
11-3 Communication function specification ................................................... - 205 -
11-4 Storage Environment .................................................................... - 205 -
12.Overall Dimension ............................................................................... - 206 -
12-1 Mainbody dimension ..................................................................... - 206 -
12-2 Operation panel ........................................................................ - 206 -

- 4 -
12-2 Operation panel ........................................................................ - 207 -
13.Peripheral Equipments & Options ................................................................. - 208 -

- 5 -
1. Safety Notes
1-1 Important notes
Danger
Caution: risk of electric shock
The disassembly of cover is absolutely probibited, otherwise the risk of electric shock and casualty may
exist.
Caution: Fire Hazard!
Immediately shut down the power supply and contact with the Seller when peculiar smell, abnormal noise,
smoke or sparks, etc. are found in the device.
In case of a fire, please use the extinguisher for electrical fire (dry powder), but do not use water for fire
fighting.
1-2 Notes on Use
Caution
Before starting the inverter, confirm the safety status of the load first, and then start running operation following
the instruction manual.
Failure to observe this may result in the danger of electric shock and other accidents.
Do not smoke or use fireworks around the inverter.
Failure to observe this may result in personalinjury and fire.
Do not keep containers which contain water above the equipment, such as vase, etc.
The water may infiltrate into the equipment interior and cause a fire.
Do not sit or stand on top of the equipment, and do not lean on it or treat it as a footboard.
Failure to observe this may overturn the equipment and result in personal injury.
Do not insert sticks, fingers etc. into the fan.
The rotating fan would cause personal injury.
During operation, do not short-circuit the input terminal and output terminal.
The current return will result in electric arc, which can cause personal burns and visual impairment.
Its use in the following applications is absolutely prohibited.
a) Medical equipment which are directly related to life.
b) Trolley buss which may lead to personal injury.
c) Important computer systems for the community and public utilities.
d) Equipment with these as standards.
Otherwise it may have significant impact on personal safety and the maintenance of public functions.
Please consult the Company in advance when it is used in the above-mentioned load equipment.
1-3 Notes on Installation
Caution
It is absolutely prohibited to store or use the inverter under the environmental conditions described below.
Failure to observe this warning may result in a fault, damage or deterioration, which could lead to fire.
yVery hot, cold, humid or outdoor locations, of which the environmental conditions are beyond that recorded
in the instruction manual.
yLocations which are in direct sunlight or near a heater or other heat sources.
yLocations subject to vibration or physical shock.
yLocations near machinery that generates sparks.
yLocations subject to dust, corrosive gas, salt, inflammable gas and water droplets.
yLocations higher than 3000 meters above sea level.
yOther similar environments.

- 6 -
Mount the inverter on a metal surface or other non-flammable surfaces.
Failure to observe this may result in a fire.
Install the inverter in a location that can bear its weight according to the instruction manual.
Failure to observe this may result in injuries as the inverter falls down.
Do not plug up the air inlet/exhaust.
Failure to observe this may result in a fire due to internal temperature rise of the equipment.
Do not place the inverter near flammable materials.
Failure to observe this may result in a fire.
Do not allow foreign objects into the inverter or attach to the cooling fans.
Failure to observe this may result in a fire or an accident.
Do not operate an inverter which is damanged, lacking parts or dented.
Failure to observe this may result in an electric shock, injury, fire or other accidents.
1-4 Notes on Handling and Moving
Caution
During handling and moving, do not tilt the equipment.
Failure to observe this may result in personal injury due to falling down of equipment.
Prior to handling and moving, confirm the weight marking attached to the equipment first; please prepare
alternative handling machine for work as necessary.
Failure to observe this may result in personal injury.
1-5 Notes on Wiring
Danger
Wiring must be performed by qualified personnel.
Improper wiring may result in electric shock or fire.
Do not connect AC power to an output terminal (U, V or W).
Failure to observe this may result in personal injury or fire.
Do not use if rated voltage is exceeded.
Failure to observe this may result in personal injury or fire.
Do not connect a resistor directly to the DC terminals (P and X).
Failure to observe this may result in a fire.
Connection between the ground terminals must be reliable.
Failure to observe this may result in an electric shock.
Please tighten the terminal block screws according to specified tightening torques.
Failure to observe this may result in a fire.
Check that the AC power voltage is consistent with the rated voltage of the inverter.
Failure to observe this may result in personal injury or fire.
For cable types and diameters, please use the cables specified in the instruction manual.
Failure to observe this may result in a fire due to wire heating.
Secure the inverter before wiring.
Failure to observe this may result in personal injury or fire.
Caution
The inverter, motor or wiring may cause interference. Please note misoperation of peripheral devices.
Failure to observe this may result in accidents.
If the input and output are terminal blocks, the wire heads must be connected with crimp terminals.
Failure to observe this may result in personal injury or fire.

- 7 -
1-6 Notes on Operation
Danger
Connect the input power only after attaching the front cover, and never remove the cover when the power is on.
Failure to observe this may result in an electric shock.
Do not touch any switch with wet hands.
Failure to observe this may result in an electric shock.
Do not touch any inverter terminal when the inverter is energized, even if the motor is not running.
Failure to observe this may result in an electric shock.
Do not get close to the motor when the restart function is enabled, as it will re-start suddenly after the alarm stops.
(Design the system to ensure personal safety at restart.)
Failure to observe this may result in personal injury.
Provide a separate emergency stop switch.
Failure to observe this may result in personal injury.
If the alarm is reset with the operation signal set, the equipment will restart suddenly. Therefore, please cut off the
operation signal before releasing an alarm.
Failure to observe this may result in personal injury.
Caution
Do not touch the radiator fins or DC reactor, beacause they become very hot.
Failure to observe this may result in burns.
It is easy to set the inverter drive speed from low to high, so be sure to confirm the allowable operating range of
the motor or machinery before the operation.
Failure to observe this may result in personal injury.
Please set separate brake if it is required to keep braking.
Failure to observe this may result in personal injury.
Do not start or stop the inverter by turning the main circuit ON or OFF.
Failure to observe this may result in equipment faults.
1-7 Notes on Maintenance and Inspection
Caution
Works such as maintenance, inspection and replacement of parts can only be carried out by professional
electricians.
[Take off any metal item (such as watch, bracelet, etc.) before working on the equipment.]
[Use insulated tools]
Failure to observe this may result in electric shock or burns.
Cut off the input power (OFF) for maintenance and inspection; only carry out the works with the voltage between
DC terminals P and X less than 30VDC after the [CHARGE] indicator lamp goes out.
Failure to observe this may result in electric shock and personal injury.
1-8 Disposal
Caution
When disposing this product, please entrust a specialized industrial waste disposal service.
If it is not handled by professionals, personal injury may be caused by capacitor explosion or the generated
harmful gas.
1-9 Others
Danger

- 8 -
Reformation of the product without authorization is strictly prohibited.
Failure to observe this may result in the risks of electric shock, personal injury, fault, damage or fire.
This product is designed for operation of a three-phase induction motor. Therefore it can not be used for
single-phase motor or other purposes.
Failure to observe this may result in a fire or an accident.
Do not use this product for life-support equipment, or other purposes directly related to dangers to human.
Failure to observe this may result in an accident.
Install a safety device when the failure of this product may cause a serious accident or damage.
Failure to observe this may result in an accident.
2. Product Validation and Precautions on Use
2-1 Product validation
After unpacking the product, please check the followings:
Check that the product has not been damaged during delivery,
such as depression of casing etc.
In case such problems are found, please contact the retailer.
S06 series product body (take S06-4A019-B** for example)
Inverter body
As shown on right
Instruction Manual
this manual
2-2 Example of nameplate label
2-3 The meanings of the model
2-4 Precautions on Use
1. Use the product in a location satisfying the standard environmental specifications (temperature, humidity, vibration, dust,
water drop, toxic gases, etc.).
2. Before starting up the product for the first time, carefully check the wiring. Make sure that the power cable (input) and
Warning
identification LED monitor
Multifunctional
numeric ke
y
s
Nameplate label
Wiring hole
Cooling fan
Series name
Voltage class
4: 3-phase 400V
Internal code
Rated current calibration
For example: A019 represents the motor
capacity corresponding to the rated
current of 18.5A is 7.5kW
Overload mode
B stands for light overload which can
work for 1 minute @ 120%

- 9 -
motor cable (output) are connected correctly. Otherwise, the inverter will be damaged.
3. Since the service life of the inverter is greatly affected by the ambient temperature of the installation location, it is
recommended to lower the ambient temperature before operation.
4. When installing the product in a control cabinet, check the cabinet size and ensure sufficient ventilation.
5. When the capacitors and surge suppressors used for improving the power factor are connected to the inverter’s output
terminal, the inverter may be heated or even damaged bacause of the high-order harmonic components. Therefore, do not
connect the capacitors and surge suppressors to the output terminal of the inverter. To increase the power factor, you can
install the DC reactor at the DC side or install the AC reactor at the primary side (i.e. input terminal) of the inverter.
6. When implementing a megger test, follow the method given in this instruction manual (10-4 “Megger Test”).
7. When using leakage circuit breaker protection switch, select a product for corresponding high-order harmonic and surge.
8. In principle, there is no magnetic contactor between the inverter and the motor. However, if the magnetic contactor is
turned ON and OFF while the inverter is operating, an excess current will be generated.
9. Select larger capacity since the operating characteristics of full electromagnetic-type MCCB changes with high-order
harmonic current.

- 10 -
3. Installation
3-1 Installation Location and Storage
Table 3-1 Work Environment Parameters
Ambient temperature -10℃~+50℃(without freezing); heavy overload, -10℃~+40℃(without freezing); light overload
Storage temperature -20℃~+65℃(short-term preservation during transportation)
Relative humidity Below 95%RH (without dewing)
Altitude Below 3000m (decrease the current when exceeding 1000m)
Vibration Below 5.9m/s2(0.6G) (JIS C 60068-2-6 standard; IEC60068-2-6)
Gaseous media Indoor (free of corrosive gas, flammable gase, oil mist, dust, etc.)
Table 3-2 Storage Environment
Storage temperature -20℃~+65℃
This temperature is for short periods, such as during transportation.
Ambient temperature must be 30°C or lower for more than 3 months of storage in consideration of
the deterioration of the electrolytic capacitor.
Furthermore, energize the equipment once per year when it is stored for more than one year.
Relative humidity Below 95%RH (without frost)
Storage environment Places free of direct sunlight, corrosive or inflammable gases, oil mist, dust, steam, water droplet,
vibration or high salinity.
3-2 Installation Direction and Space
(1) This inverter is of the wall mounting type.
(2) Install the inverter vertically on a flat mounting surface.
(3) Since the inverter generates heat easily, provide adequate space around it to ensure good heat dissipation conditions.
(4) When installing the inverter in a control cabinet, provide a ventilation fan to keep the ambient temperature below 40°C.
(5) When installing the inverter in a control cabinet, mounting the radiator fins outside the control cabinet can help to reduce the
internal temperature of the cabinet.
(6) This inverter is of IP20 structure. Please select according to intended use.
Figure 3-1 Surrounding Space Figure 3-2 Arranging method of radiator fins
outside the cabinet
When several inverters are set in a control cabinet, be sure to locate the ventilation fans properly to allow free air
circulation.
Improper located ventilation fans will rise the ambient temperature, which will affect the cooling of the inverter.
Above 10cm Above 10cm
Above
5cm
Above
5cm
Above 10cm
Heating air
Cooling air
Above 10cm
Inside cabinet Outside cabinet
Heating air
Cooling air
Coolin
g
fan
Coolin
g
fan
Mount bracket
(
o
p
tional
)
Mount
b
racket
(optional)
Inside
cabinet
Outside
cabinet

- 11 -
Figure 3-3 Arranging method inside the cabinet Figure 3-4 Ventilation fan position in cabinet
3-3 Sketch of Front Cover Removal and Installation
(1) Removal of front cover (lower)
Unscrew the M4 screws, and pull the cover toward you while pressing both sides of the front cover (lower).
yOnly carry out this work during the main circuit wiring, control circuit wiring and JP2 switching.
(3) Removal of operation panel
Remove the operation panel and front panel during the installation, and re-install the front panel after the installation.
(2) Installation
When installing, work in reverse order.
Ventilation fan Ventilation fan
Correct Incorrect Correct Incorrect
Overheat
Overheat

- 12 -
4. Wiring
Read the Notes on Wiring (1-5) before wiring.
Failure to observe this may result in personal injury or fire.
4-1 Connection with peripheral devices
Name Purposes and detailed description
Input power
supply
transformer
When there is need for matching the system power
supply voltage with rated inverter input voltage, please
provide the input power supply transformer.
When several inverters are used, please provide the
input power supply transformer to reduce the impact of
high-order harmonic on other load devices.
Circuit breaker
or leakage
circuit breaker
Please connect wiring circuit breaker or leakage circuit
breaker in the overload protection circuit during
protection and wiring of the power supply system.
When using leakage circuit breaker, select a product for
corresponding high-order harmonic.
Electromagnetic
contactor
The coil must be provided with a surge absorber.
Surge absorber
Please install the surge absorber for suppression of
surge generated on opening and closing of
electromagnetic contactors and control relays.
AC reactor
DC reactor
To achieve the following objectives, please install the
reactor
·Improve the inverter’s input power factor
·Reduce the impact on inverter due to unbalance
between phases of power supply voltage
·Prevent tripping of inverter due to action of phase lead
compensation capacitors in the system
·When the capacity of power supply is large (above
500kVA)
Zero-sequence
reactor
Line noise filter
Reduce the interferences coming into input power
supply system of the inverter and generated by wiring.
It is recommended that elements such as zero-sequence
reactor etc. be inserted as close to inverter as possible.
Model name RC5078
RC5096 [SOSHIN Electric Co., LTD]
Radio noise
filter
Used to suppress the radio noise radiating to power
supply side of the inverter.
Model name 200V class: 3XYEB-105•104
400V class: 3XYHB-105•104
[OKAYA Electric Industries Co., LTD]

- 13 -
Noise filter
Reduce the interferences coming into input power
supply system of the inverter and generated by wiring.
It is recommended that noise filter be installed as close
to inverter as possible.
EMC filter recommended (please consult otherwise)
4-2 About Wiring
◆Before carrying out wiring work, cut off the inverter’s input power supply, and make sure that no applied voltage
is present.
(1) Be sure to connnect a circuit breaker between the power supply and the input power supply terminals (R, S, T).
(Use a leakage circuit breaker specific to high-order harmonic when necessary.) To ensure the system safety,
connect a MC (electromagnetic contactor) between the circuit breaker and the input power supply.
(2) The phase order does not need to be considered when wiring the input power supply terminals (R, S and T).
(3) Connect the wires between the motor and the output terminals (U, V, W) correctly.
◆The high-order harmonic leakage current increases accordingly when the total length of wiring between inverter
and motor is too long, which causes adverse affects on peripheral devices.
The total length of wiring between inverter and motor shall not exceed the values described in Table 4-1.
Table 4-1 Length of wiring between the inverter and the motor
Length of wiring between the inverter
and the motor
50m 100m 200m
Carrier frequency
(Specified by F1009)
F1009=130 or less F1009=90 or less F1009=40 or less
● When driving several motors at the same time, the total length of wiring to motors shall not exceed the values described
in Table 4-1. However, for vector control, the maximum wiring length shall be controlled within 100m. (For length of
more than 30m, please implement auto detecting mode 2)
● The surge voltage generated by the inverter element switching is superimposed and added to the motor terminal voltage.
The following measures should be considered to prevent deterioration of motor isolation especially for 400V class motors
when the length of wiring between the inverter and the motor is long.
① Use motors with reinforced isolation.
② Shorten the length of wiring between the inverter and the motor as possible (Generally about 10 - 20m).
(4) Refer to 4-5-4 for capacity of MCCB and MC as well as the wire sizes.
Use sleeved crimp terminals for the power and motor cables.
(5) Use shielded or twisted-pair wires for wiring to the control circuit terminals, while keep the wires well away
from the main and high-voltage circuits (including logic circuit of 200 V relay).
(6) Use a micro-signal contact or two-contact relay for the control circuit terminal to prevent poor contact.
(7) Ground the ground terminal ( ) securely.(Never use the casing or the chassis.)
According to technical standards for electrical equipment, 400V series shall be connected to the grounding
electrode for type C grounding.
Table 4-2 Types of grounding
Voltage Types of grounding Grounding resistance
400V series Type C grounding 10Ωor less
● Do not share the grounding wire with the welding machine or the power equipment.
● Use the grounding wire prescribed in the technical standards for electrical equipment, and shorten wiring length as much as
possible.
● Be careful not to loop the grounding wire when using multiple inverters.

- 14 -
(8) During wiring, please note that the inside of inverter shall be free from chips of wires.
◆Control circuit wiring precautions
yUse shielded cable for analog input and output cables as well as the contact input cable (digital multifunctional input
terminals).
yTo prevent misoperation due to interfenrence, the signal cables and power cables should be separated as possible during the
wiring (above 10cm).
yWhen using the operation panel for running, it can be realized only through the main circuit wiring (Without the need to
operate from the outside or by inputting frequency instructions).
yConnect the MCCB (circuit breaker) and other circuit protectors between the power supply and the input terminals.
yWhen the protective function of the inverter is enabled or the occurrence of other accidents, please connect the MC
(electromagnetic contactor) between MCCB and input terminals to cut off the inverter power supply, preventing further
expansion of failure or accident. Furthermore, the MC should be connected as close to the inverter as possible.
4-3 Terminal Wiring Diagram

- 15 -
4-4 Composition of Main Circuit Terminals
4-4-1 Description of Main Circuit Terminals
Terminal symbol Name Description
O
p
tion DC
reacto
r
Brake unit
Brake resisto
r
Main circuit
In
p
ut
p
owe
r
Moto
r
Note: 1※
Control circuit
Multifunctional input
terminal
Note: 5※
Note: 2※
Multifunctional contact output 1
Contact capacity: 250V, 0.3A
Multifunctional contact output 2
Contact capacity: 250V, 0.3A
Open collector
24V 50mA or less
Note: 3※
Drivin
g
1
Consistent
fre
q
uenc
y
Ove
r
load prealarm
si
g
nal
Common
si
g
nal
g
round
Digital signal
common ground
(internally
connected)
24V outside
p
ower out
p
ut
RS485 communication terminal
Potentiomete
r
Notes:
Note: 4※
Fre
q
uenc
y
settin
g
p
ower 12V
Frequency setting terminal
Frequency setting terminal
Terminal resisto
r
Analog signal common terminal 12G
Analog output DC0-10V
Analog output DC0-10V
U
p
date terminal
Note: 6※
Main circuit terminal
Control circuit in
p
ut terminal
Control circuit out
p
ut terminal
Communication circuit terminal
1: Ground※the inverter and motor reliably before use
2: Two groups※of separate multifunctional contact outputs, which can be selected and
set by F1513 & F1514
3: Multifunctional open collector output DO terminal, which can be selected and set b
y
※
F1509-F1511
4: Switch※the function with function code F1002. The terminal can be used as an input
terminal for various feedback signals
5: Multifunctional input terminal, can be assigned with different functions using※
function code F1414 to F1421
6: This jumper terminal is used for version update, never use it under normal※
circumstances
User load

- 16 -
R,S,T Input power supply terminals Terminals connected to a three-phase commercial
power supply
U,V,W Inverter output terminals Terminals connected to a three-phase induction motor
P,P1 DC reactor connection terminals Terminals connected to a DC reactor ※1
P,PR Brake resistor connection terminals Terminals connected to a brake resistor between P-PR
P,X DC side voltage terminals
Terminals connected to a brake unit
P is the DC positive terminal, X the DC negative
terminal
Ground terminal Terminal for grounding of inverter casing
※1When connecting the DC reactor, please remove the jumper between P1 and P.
4-4-2 Connection Diagram of Main Circuit Terminals
(1) S06-4A005~4A076
(2) S06-4A092~4A152
Jumpe
r
DC
reactor
Brake resisto
r
Option
Moto
r
Input powe
r
Jumpe
r
Reacto
r
Brake unit Moto
r
Option
Input powe
r

- 17 -
4-4-3 External brake resistor selection example
External brake resistor (recommended) External brake resistor (limit value)
Model Resistance Capacity ※1 Resistance Capacity ※1
S06-4A005-B** 700Ωor more 100W 420Ωor more 300W
S06-4A006-B** 320Ωor more 200W 190Ωor more 300W
S06-4A009-B** 160Ωor more 400W 130Ωor more 500W
S06-4A014-B** 120Ωor more 600W 80Ωor more 800W
S06-4A019-B** 80Ωor more 800W 52Ωor more 1100W
S06-4A025-B** 60Ωor more 1000W 38Ωor more 1500W
S06-4A032-B** 40Ωor more 1500W 32Ωor more 1800W
S06-4A038-B** 40Ωor more 1500W 32Ωor more 1800W
S06-4A049-B** 40Ωor more 1500W 32Ωor more 1800W
S06-4A061-B** 40Ωor more 1500W 32Ωor more 1800W
S06-4A076-B** 20Ωor more 3000W 16Ωor more 3600W
※1 The above brake resistor is selected by assuming the maximum duty cycle to be 10% ED. When % ED needs to be set above
10%, brake resistor capacity should be increased proportionally.
Example) When setting 20 % ED, the capacity should be doubled that of 10%ED.
4-4-4 Capacities of MCCB and MC as well as Wire Size
MC
(Electromagnetic
contactor)
Main circuit
Recommended wire size [mm2]
Model MCCB
(Circuit
breaker)
[A]
Rated
current
[A]
Rated
making
current
[A]
Input wire P,P1 wires Output wire Ground
wire
Screw
diame
ter
Tighten
ing
Torque
[N•m]
Max. wire
size
[mm2]
S06-4A005-B** 5 7 20 2.0
(
2.0
)
2.0
(
2.0
)
2.0
(
2.0
)
5.5
S06-4A006-B** 15 7 20 2.0
(
2.0
)
2.0
(
2.0
)
2.0
(
2.0
)
5.5
S06-4A009-B** 20 7 20 2.0
(
2.0
)
2.0
(
2.0
)
2.0
(
2.0
)
5.5
S06-4A014-B** 30 7 20 3.5
(
2.0
)
3.5
(
2.0
)
2.0
(
2.0
)
5.5
S06-4A019-B** 30 17 32 5.5
(
2.0
)
5.5
(
2.0
)
3.5
(
2.0
)
5.5
S06-4A025-B** 50 25 50 5.5
(
2.0
)
5.5
(
2.0
)
5.5
(
2.0
)
5.5
M4 1.2 5.5
S06-4A032-B** 60 25 50 8.0
(
3.5
)
8.0
(
3.5
)
8.0
(
3.5
)
14
S06-4A038-B** 70 32 60 14
(
5.5
)
14
(
5.5
)
8.0
(
3.5
)
14
M5 2.0 14
S06-4A049-B** 75 48 80 14(5.5)22
(
14
)
8.0(5.5)14
S06-4A061-B** 100 65 100 22(14)22
(
14
)
8.0(5.5)14
S06-4A076-B** 125 75 135 38(14)22
(
14
)
14(5.5)14
M6 2.03 22
S06-4A092-B** 150 75 135
22×2(22)22
(
14
)
22(8)22
S06-4A115-B** 175 150 200 60(38)38(14)22(14)22
M6 4.52 60
S06-4A152-B** 225 150 200 60(38)60(22)38(14)22 M8 4.52 60
Notes: The values for wires in the main circuit are for 600 V IV PVC-insulated wires (60ºC) when the inverter ambient
temperature is 40ºC. The values in parentheses are for 600 V bridged-polyethylene insulated wires (90ºC). The maximum
wire size indicates the maximum wire cross-sectional area that can be used with the terminal block.

- 18 -
4-5 Composition of Control Circuit Terminals
4-5-1 Wire size and terminal arrangement
Terminal screw diameter:M3
Recommended wire size: 0.75[mm2]
Tightening torque:0.5[N•m]
4-5-2 Schematic of control circuit terminal wiring
4-5-3 Functional list of control circuit terminals
Ty
pe
Terminal
Symbol Terminal Name Function Description Rated Specification
COM
1
COM
2
Digital signal
common terminals
Common terminals for digital input and output
signals and for +24V power supply
Total current consumed:
100mA or less
①Multifunctional input
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Digital
multifunctional input
terminals
(1) The functions selected can be set through
function codes F1414~F1421.
Input resistor: about 6.6kΩ
When short-circuited: aboutDC3~
5mA
(1) Signal input “on” by
short-circuiting either COM1 or
COM2.
(2) Signal input “off” by opening
either COM1 or COM2.
ACM Analog signal
common terminals
Common terminals for analog input and output
signals
Total current consumed: 100mA or
less
+V
Analog input
potentiometer wiring
terminal
Connected to a potentiometer of 5kΩ0.3W or
above
DC 10~12V
※It can not be connected to any
element other than the
potentiometer
②Analog input
VRF1 Analog voltage input
terminal
zCarry out frequency setting through voltage
input
zSet the gain frequency corresponding to 5V
or 10V with voltage input.
zWhen “External analog forward / reverse
run” is selected, set the gain frequency
Input resistor:
about 34kΩ
Maximum allowable voltage:
DC12V
※ The common end of control circuit terminals shall not be grounded to the earth.
※ COM1/COM2 shall not be in common use with ACM. (Because they are insulated with each other).
※ Do not input the voltage to multifunctional terminals (DI1-DI8).
RS485 communication
Frequency
display
RPM
display
Single-
p
hase
Surge suppressor
Emergency stop Reverse Forwar
d
4-20mA input
Potentiometer
frequency setting
Other control
circuits composed
of relay 2-node
output

- 19 -
corresponding to 10V (5+5V) or 0V (5-5V)
with external analog value.
VRF
/IRF
Analog
current/voltage input
terminals
(commonly used for
current/voltage input)
zThe current/voltage in this channel can be
switched separately
zWhen frequency setting is selected, the
current/voltage input can be selected by the
content of F1002.
zWhen carrying out frequency setting through
voltage input, set the gain frequency
corresponding to 5V or 10V with voltage
input.
zWhen “External analog forward / reverse
run” is selected, set the gain frequency
corresponding to 10V (5+5V) or 0V (5-5V)
with external analog value.
zWhen carrying out frequency setting through
current input, set the gain frequency
corresponding to 20mA.
For voltage input:
Input resistor: about 34kΩ
Maximum allowable voltage:
DC12V
For current input:
Input resistor: about 250Ω
Maximum allowable current: 30mA
③Power
su
pp
l
y
24V Power supply output zSupply DC24V power to the user Maximum allowable output current
for DC 24V: 150mA
DOE
Multifunctional
output common
terminal
zThis terminal is DO1~DO3 shared
common terminal
④Multifunctional
out
p
ut
DO1
DO2
DO3
Multifunctional
output terminal
zOpen collector output
zSend signals through functions selected by
function codes
Allowable load: DC48V, 50mA
⑤Analog output
AOU
T1
AOU
T2
Analog output
terminals
zSelect the setting of signal output through
F1501~F1506
zShare the ground terminal with ACM analog
signal
Signal output: DC 0~10V
Maximum output current: 15mA
TRA
RS485
communication
sending & receiving
terminals (+)
zWhen connecting the computer using
RS485 communication interface, connect
the “+” signal terminal
TRB
RS485
communication
sending & receiving
terminals (-)
zWhen connecting the computer using
RS485 communication interface, connect
the “-” signal terminal
Communication speed:
1200-57600bps
Total length: 500m
※When switch JP2 is located at
ON, connect the terminal resistor:
100Ω
⑥Communication terminal
SG
RS485
communication
common terminal
zRS485 communication common terminal
zConnected to SG terminal on the
communication equipment
※Choose the single terminal
grounding on inverter side or
communication equipment side
according to the site conditions
⑦Contact output
FA1
FB1
FC1
FA2
FB2
FC2
Abnormal alarm
signal output and
multifunctional
contact output
zThese contact output terminals indicate that
the enabled protective function has stopped
the inverter.
zF1513, F1504: Select the setting for
multifunctional contact output according to
the relay 1 & 2 contact output
Contact capacity: AC250V/0.3A
When alarm contact is selected:
Normal: FA1,2-FC1,2 open
Abnormal: FA1,2-FC1,2 closed
JP1 Upgrade jumper Used for short-circuiting during version upgrade ※Do not connect anything to this
terminal except when upgrading.
⑧Jumper
JP2
Communication
terminal resistor ON
selector jumper
Choose whether to connect 100Ωterminal
resistor
OFF: terminal resistor is open
ON: terminal resistor is closed
This manual suits for next models
14
Table of contents
Other Sanken Inverter manuals