Santerno ASAB Technical specifications

INSTALLATION AND PROGRAMMING
INSTRUCTIONS
English
•This manual is integrant and essential to the product. Carefully read the instructions contained herein as
they provide important hints for use and maintenance safety.
•This device is to be used only for the purposes it has been designed to. Other uses should be considered
improper and dangerous. The manufacturer is not responsible for possible damages caused by improper,
erroneous and irrational uses.
•Elettronica Santerno is responsible for the device in its original setting.
•Any changes to the structure or operating cycle of the device must be performed or authorized by the
Engineering Department of Elettronica Santerno.
•Elettronica Santerno assumes no responsibility for the consequences resulting from the use of non-original
spare parts.
•Elettronica Santerno reserves the right to make any technical changes to this manual and to the device
without prior notice. If printing errors or similar are detected, corrections will be included in new releases of
the manual.
•The information contained herein is the property of Elettronica Santerno and cannot be reproduced.
Elettronica Santerno enforces its rights on the drawings and catalogues according to the law.
Elettronica Santerno S.p.A.
S.S. Selice, 47 – 40026 Imola (BO) Italy
Tel. +39 0542 489711 – Fax +39 0542 489722
www.santerno.com [email protected]
ASAB
ADVANCED SOFT STARTER
Issued on 22/05/13
R. 03
• 15P0078B1 •

ASAB
1/66
Contents
1About This Manual .....................................................................................................................................................3
2Caution Statements....................................................................................................................................................3
2.1 Electrical Shock Risk.....................................................................................................................................................................3
2.2 System Design and Safety of Personnel.......................................................................................................................................3
2.3 Disposal Instructions .....................................................................................................................................................................4
3Introduction ................................................................................................................................................................5
3.1 Feature List ...................................................................................................................................................................................5
3.2 Specifications ................................................................................................................................................................................5
4Installation ................................................................................................................................................................11
4.1 Physical Installation.....................................................................................................................................................................11
4.2 Control Terminals........................................................................................................................................................................11
4.3 Control Voltage............................................................................................................................................................................12
4.4 Control Wiring..............................................................................................................................................................................12
4.5 Relay Outputs..............................................................................................................................................................................12
4.6 Motor Thermistors .......................................................................................................................................................................12
4.7 Power Terminations ....................................................................................................................................................................13
4.8 Power Input and Output Configurations......................................................................................................................................14
4.9 Schematic Diagrams ...................................................................................................................................................................15
5Power Circuits ..........................................................................................................................................................16
5.1 Motor Connection........................................................................................................................................................................16
5.2 Bypass Contactor........................................................................................................................................................................19
5.3 Main Contactor............................................................................................................................................................................19
5.4 Circuit Breaker.............................................................................................................................................................................19
5.5 Earth Terminals...........................................................................................................................................................................19
5.6 Power Factor Correction .............................................................................................................................................................19
5.7 Power Supply Fuses ...................................................................................................................................................................19
6Operation ..................................................................................................................................................................24
6.1 Keypad and Feedback ................................................................................................................................................................24
6.2 Start, Stop and Reset Commands ..............................................................................................................................................26
6.3 Soft Start Methods.......................................................................................................................................................................26
6.4 Stop Methods ..............................................................................................................................................................................29
6.5 Jog Operation..............................................................................................................................................................................31
6.6 Inside Delta Operation ................................................................................................................................................................32
7Programming Menu..................................................................................................................................................33
7.1 Quick Setup.................................................................................................................................................................................34
7.2 Standard Menu............................................................................................................................................................................35
7.3 Extended Menu ...........................................................................................................................................................................36
7.4 Parameter Descriptions...............................................................................................................................................................38
7.5 Adjustment Lock..........................................................................................................................................................................49
7.6 Access Code ...............................................................................................................................................................................49
7.7 Setup Tools .................................................................................................................................................................................49
8Logs Menu ................................................................................................................................................................51
8.1 Trip Log .......................................................................................................................................................................................51
8.2 Event Log ....................................................................................................................................................................................51
8.3 Performance Counters ................................................................................................................................................................51
9Application Examples..............................................................................................................................................52
9.1 Installation with Main Contactor ..................................................................................................................................................52
9.2 Installation with Bypass Contactor ..............................................................................................................................................53
9.3 Emergency Run Operation..........................................................................................................................................................54
9.4 Auxiliary Trip Circuit ....................................................................................................................................................................55
9.5 DC Brake with External Zero Speed Sensor...............................................................................................................................56
9.6 Soft Braking.................................................................................................................................................................................57
9.7 Two Speed Motor........................................................................................................................................................................58
10 Troubleshooting.......................................................................................................................................................59

2/66
ASAB
10.1 Protection Responses .................................................................................................................................................................59
10.2 Trip Messages.............................................................................................................................................................................59
10.3 General Faults.............................................................................................................................................................................62
11 Accessories ..............................................................................................................................................................64
11.1 Communication Modules.............................................................................................................................................................64
11.2 Remote Control Panel (RCP)......................................................................................................................................................64
11.3 Finger Guard Kit..........................................................................................................................................................................64
11.4 PC Software ................................................................................................................................................................................64
12 Busbar Adjustment Procedure ...............................................................................................................................65

ASAB
3/66
1About This Manual
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is
subject to change at any time and without prior notice. In no event will responsibility or liability be accepted for direct, indirect or
consequential damages resulting from the use or application of this equipment.
WARNING
Indicates a hazard that may cause personal injury or death.
CAUTION
Indicates a hazard that may damage the equipment or installation.
NOTE
Provides helpful information.
2Caution Statements
This symbol is used throughout this manual to draw attention to topics of special importance to the installation and
operation of equipment.
Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the
installer's responsibility to read and understand all instructions in this manual prior to installing, operating or maintaining the equipment,
to follow good electrical practice including applying appropriate personal protective equipment and to seek advice before operating this
equipment in a manner other than as described in this manual.
NOTE
The ASAB soft starter is not user serviceable. The unit should only be serviced by authorised service personnel.
Unauthorised tampering with the unit will void the product warranty.
2.1 Electrical Shock Risk
The voltages present in the following locations can cause severe electric shock and may be lethal:
AC supply cables and connections
Output cables and connections
Many internal parts of the starter, and external option units
The AC supply must be disconnected from the starter using an approved isolation device before any cover is removed from the starter or
before any servicing work is performed.
WARNING - ELECTRICAL SHOCK HAZARD
Models ASAB-0500B~ASAB-1600C: The busbar and heatsink must be treated as live whenever the unit has mains voltage
connected (including when the starter is tripped or waiting for a command).
SHORT CIRCUIT
The ASAB is not short circuit proof. After severe overload or short circuit, the operation of the ASAB should be fully tested by
an authorised service agent.
GROUNDING AND BRANCH CIRCUIT PROTECTION
It is the responsibility of the user or person installing the ASAB to provide proper grounding and branch circuit protection
according to local electrical safety codes.
2.2 System Design and Safety of Personnel
The starter is intended as a component for professional incorporation into complete equipment or a system. If installed incorrectly, the
starter may present a safety hazard.
The starter uses high voltages and currents, carries stored electrical energy, and is used to control equipment which can cause injury.
Close attention is required to the electrical installation and the system design to avoid hazards either in normal operation or in the event
of equipment malfunction. System design, installation, commissioning and maintenance must be carried out by personnel who have the
necessary training and experience. They must read this safety information and this guide carefully.
None of the starter functions must be used to ensure safety of personnel, ie they must not be used for safety-related functions.
Careful consideration must be given to the functions of the starter which might result in a hazard, either through their intended behaviour
or through incorrect operation due to a fault. In any application where a malfunction of the starter or its control system could lead to or
allow damage, loss or injury, a risk analysis must be carried out, and where necessary, further measures taken to reduce the risk.

4/66
ASAB
The system designer is responsible for ensuring that the complete system is safe and designed correctly according to the relevant safety
standards.
2.2.1 STOP function
The STOP function does not remove dangerous voltages from the starter, the motor or any external option units.
2.3 Disposal Instructions
Equipment containing electrical components may not be disposed of together with domestic
waste.
It must be collected separately as electrical and electronic waste according to local and
currently valid legislation.

ASAB
5/66
3Introduction
The ASAB is an advanced digital soft start solution for motors from 11 kW to 850 kW. ASAB soft starters provide a complete range of
motor and system protection features and have been designed for reliable performance in the most demanding installation situations.
3.1 Feature List
Extensive starting and stopping options
Adaptive control
Constant current
Current ramp
Timed voltage ramp soft stop
Brake
Models for all connection requirements
23 A to 1600 A (nominal)
200 VAC to 525 VAC
380 VAC to 690 VAC
Internally bypassed options
In-line or inside delta connection (auto-detect)
Inputs and outputs
Remote control inputs
(3 x fixed, 1 x programmable)
Relay outputs
(3 x programmable)
Analog output
DeviceNet, Modbus, Profibus, Ethernet (Ethernet IP, Modbus
TCP, Profinet) or USB communication modules (optional)
Easy-to-read display with comprehensive feedback
Multi-language feedback
Multiple status screens and performance graphs
Date and time stamped event logging
Operational counters (number of starts, hours run,
kWh)
Performance monitoring (current, voltage, power
factor, kWh)
User-programmable monitoring screen
Customisable protection
Motor overload
Excess start time
Undercurrent
Instantaneous overcurrent
Current imbalance
Mains frequency
Input trip
Motor thermistor
Power circuit
Phase sequence
3.2 Specifications
3.2.1 Model Code
ASAB-
–
–
–
Control voltage
12 = 110~120 VAC or 220~240 VAC
14 = 24 VAC/VDC
Mains voltage
5 = 200 ~ 525 VAC
7 = 380 ~ 690 VAC
Bypass
B = internally bypassed
C = non-bypassed (continuous connection)
Nominal current rating
3.2.2 Current Ratings
Contact your local supplier for ratings under operating conditions not covered by these ratings charts.
Current Ratings for Bypass Operation
80 A
:
AC-53b
3.5
-
15
:
345
Off time (seconds)
Start time (seconds)
Start current (multiple of motor full load current)
Starter current rating (amperes)
NOTE
Models ASAB-0255C~ASAB-1600C must be externally bypassed.

6/66
ASAB
In-line connection
AC53b 3.0-10:350
40 ºC <1000 metres
AC53b 3.5-15:345
40 ºC <1000 metres
AC53b 4.0-20:340
40 ºC <1000 metres
AC53b 4.5-30:330
40 ºC <1000 metres
ASAB-0023B
23 A
20 A
17 A
15 A
ASAB-0043B
43 A
37 A
31 A
26 A
ASAB-0053B
53 A
53 A
46 A
37 A
AC53b 3.0-10:590
40 ºC <1000 metres
AC53b 3.5-15:585
40 ºC <1000 metres
AC53b 4.0-20:580
40 ºC <1000 metres
AC53b 4.5-30:570
40 ºC <1000 metres
ASAB-0076B
76 A
64 A
55 A
47 A
ASAB-0097B
97 A
82 A
69 A
58 A
ASAB-0100B
100 A
88 A
74 A
61 A
ASAB-0105B
105 A
105 A
95 A
78 A
ASAB-0145B
145 A
123 A
106 A
90 A
ASAB-0170B
170 A
145 A
121 A
97 A
ASAB-0200B
200 A
189 A
160 A
134 A
ASAB-0220B
220 A
210 A
178 A
148 A
ASAB-0255B
255 A
231 A
201 A
176 A
ASAB-0255C
255 A
231 A
201 A
176 A
ASAB-0350B
350 A
329 A
284 A
244 A
ASAB-0380C
380 A
380 A
359 A
299 A
ASAB-0425B
425 A
411 A
355 A
305 A
ASAB-0430C
430 A
430 A
368 A
309 A
ASAB-0500B
500 A
445 A
383 A
326 A
ASAB-0580B
580 A
492 A
425 A
364 A
ASAB-0620C
620 A
620 A
540 A
434 A
ASAB-0650C
650 A
650 A
561 A
455 A
ASAB-0700B
700 A
592 A
512 A
438 A
ASAB-0790C
790 A
790 A
714 A
579 A
ASAB-0820B
820 A
705 A
606 A
516 A
ASAB-0920B
920 A
804 A
684 A
571 A
ASAB-0930C
930 A
930 A
829 A
661 A
ASAB-1000B
1000 A
936 A
796 A
664 A
ASAB-1200C
1200 A
1200 A
1200 A
1071 A
ASAB-1410C
1410 A
1410 A
1319 A
1114 A
ASAB-1600C
1600 A
1600 A
1600 A
1353 A
Inside delta connection
AC53b 3.0-10:350
40 ºC <1000 metres
AC53b 3.5-15:345
40 ºC <1000 metres
AC53b 4.0-20:340
40 ºC <1000 40 ºC <1000
metres
AC53b 4.5-30:330
40 ºC <1000 metres
ASAB-0023B
34 A
30 A
26 A
22 A
ASAB-0043B
64 A
59 A
51 A
44 A
ASAB-0053B
79 A
79 A
69 A
55 A
AC53b 3.0-10:590
40 ºC <1000 metres
AC53b 3.5-15:585
40 ºC <1000 metres
AC53b 4.0-20:580
40 ºC <1000 metres
AC53b 4.5-30:570
40 ºC <1000 metres
ASAB-0076B
114 A
96 A
83 A
70 A
ASAB-0097B
145 A
123 A
104 A
87 A
ASAB-0100B
150 A
132 A
112 A
92 A
ASAB-0105B
157 A
157 A
143 A
117 A
ASAB-0145B
218 A
184 A
159 A
136 A
ASAB-0170B
255 A
217 A
181 A
146 A
ASAB-0200B
300 A
283 A
241 A
200 A
ASAB-0220B
330 A
315 A
268 A
223 A
ASAB-0255B
382 A
346 A
302 A
264 A
ASAB-0255C
382 A
346 A
302 A
264 A
ASAB-0350B
525 A
494 A
427 A
366 A
ASAB-0380C
570 A
570 A
539 A
449 A
ASAB-0425B
638 A
617 A
533 A
458 A
ASAB-0430C
645 A
645 A
552 A
464 A
ASAB-0500B
750 A
668 A
575 A
490 A

ASAB
7/66
ASAB-0580B
870 A
738 A
637 A
546 A
ASAB-0620C
930 A
930 A
810 A
651 A
ASAB-0650C
975 A
975 A
842 A
683 A
ASAB-0700B
1050 A
889 A
768 A
658 A
ASAB-0790C
1185 A
1185 A
1071 A
868 A
ASAB-0820B
1230 A
1058 A
910 A
774 A
ASAB-0920B
1380 A
1206 A
1026 A
857 A
ASAB-0930C
1395 A
1395 A
1244 A
992 A
ASAB-1000B
1500 A
1404 A
1194 A
997 A
ASAB-1200C
1800 A
1800 A
1800 A
1606 A
ASAB-1410C
2115 A
2115 A
1979 A
1671 A
ASAB-1600C
2400 A
2400 A
2400 A
2030 A
Current Ratings for Continuous Operation (Not bypassed)
351 A
:
AC-53a
3.5
-
15
:
50
-
6
Starts per hour
On-load duty cycle (%)
Start time (seconds)
Start current (multiple of motor full load current)
Starter current rating (amperes)
In-line connection
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres
ASAB-0255C
255 A
222 A
195 A
171 A
ASAB-0380C
380 A
380 A
348 A
292 A
ASAB-0430C
430 A
413 A
355 A
301 A
ASAB-0620C
620 A
614 A
515 A
419 A
ASAB-0650C
650 A
629 A
532 A
437 A
ASAB-0790C
790 A
790 A
694 A
567 A
ASAB-0930C
930 A
930 A
800 A
644 A
ASAB-1200C
1200 A
1200 A
1135 A
983 A
ASAB-1410C
1410 A
1355 A
1187 A
1023 A
ASAB-1600C
1600 A
1600 A
1433 A
1227 A
Inside delta connection
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres
ASAB-0255C
382 A
334 A
293 A
257 A
ASAB-0380C
570 A
570 A
522 A
437 A
ASAB-0430C
645 A
620 A
533 A
451 A
ASAB-0620C
930 A
920 A
773 A
628 A
ASAB-0650C
975 A
943 A
798 A
656 A
ASAB-0790C
1185 A
1185 A
1041 A
850 A
ASAB-0930C
1395 A
1395 A
1200 A
966 A
ASAB-1200C
1800 A
1800 A
1702 A
1474 A
ASAB-1410C
2115 A
2033 A
1780 A
1535 A
ASAB-1600C
2400 A
2400 A
2149 A
1840 A

8/66
ASAB
Minimum and Maximum Current Settings
The ASAB's minimum and maximum full load current settings depend on the model:
In-line connection
Inside delta connection
Model
Minimum
Maximum
Minimum
Maximum
ASAB-0023B
5 A
23 A
5 A
34 A
ASAB-0043B
9 A
43 A
9 A
64 A
ASAB-0053B
11 A
53 A
11 A
79 A
ASAB-0076B
15 A
76 A
15 A
114 A
ASAB-0097B
19 A
97 A
19 A
145 A
ASAB-0100B
20 A
100 A
20 A
150 A
ASAB-0105B
21 A
105 A
21 A
157 A
ASAB-0145B
29 A
145 A
29 A
217 A
ASAB-0170B
34 A
170 A
34 A
255 A
ASAB-0200B
40 A
200 A
40 A
300 A
ASAB-0220B
44 A
220 A
44 A
330 A
ASAB-0255B
51 A
255 A
51 A
382 A
ASAB-0255C
51 A
255 A
51 A
382 A
ASAB-0350B
70 A
350 A
70 A
525 A
ASAB-0380C
76 A
380 A
76 A
570 A
ASAB-0425B
85 A
425 A
85 A
638 A
ASAB-0430C
86 A
430 A
86 A
645 A
ASAB-0500B
100 A
500 A
100 A
750 A
ASAB-0580B
116 A
580 A
116 A
870 A
ASAB-0620C
124 A
620 A
124 A
930 A
ASAB-0650C
130 A
650 A
130 A
975 A
ASAB-0700B
140 A
700 A
140 A
1050 A
ASAB-0790C
158 A
790 A
158 A
1185 A
ASAB-0820B
164 A
820 A
164 A
1230 A
ASAB-0920B
184 A
920 A
184 A
1380 A
ASAB-0930C
186 A
930 A
186 A
1395 A
ASAB-1000B
200 A
1000 A
200 A
1500 A
ASAB-1200C
240 A
1200 A
240 A
1800 A
ASAB-1410C
282 A
1410 A
282 A
2115 A
ASAB-1600C
320 A
1600 A
320 A
2400 A

ASAB
9/66
3.2.3 Dimensions and Weights
E
087 18.E
A
C
D
B
E
A B
C
D
Model
A
mm (inch)
B
mm (inch)
C
mm (inch)
D
mm (inch)
E
mm (inch)
Weight
kg (lb)
ASAB-0023B
183
4.3
ASAB-0043B
(7.2)
(9.5)
ASAB-0053B
295
278
150
124
ASAB-0076B
(11.6)
(10.9)
(5.9)
(4.9)
4.5 (9.9)
ASAB-0097B
213
5.0
ASAB-0100B
(8.4)
(11.0)
ASAB-0105B
ASAB-0145B
ASAB-0170B
438
380
275
250
250
15
ASAB-0200B
(17.2)
(15.0)
(10.8)
(9.8)
(9.8)
(33.0)
ASAB-0220B
ASAB-0255B
440
392
424
376
296
26 (57.2)
ASAB-0350B
(17.3)
(15.4)
(16.7)
(14.8)
(11.7)
30.2
ASAB-0425B
(66.58)
ASAB-0500B
49.5
ASAB-0580B
(109.13)
ASAB-0700B
640
600
433
320
295
ASAB-0820B
(25.2)
(23.6)
(17.0)
(12.6)
(11.6)
60.0
ASAB-0920B
(132.3)
ASAB-1000B
ASAB-0255C
460 (18.1)
400 (15.7)
390 (15.4)
320 (12.6)
280 (11.0)
24 (52.9)
ASAB-0380C
ASAB-0430C
45.0
ASAB-0620C
689
522
430
320
300
(98.1)
ASAB-0650C
(27.1)
(20.6)
(16.9)
(12.6)
(11.8)
ASAB-0790C
ASAB-0930C
53.0 (116.8)
ASAB-1200C
856
727
585
500
364
117
ASAB-1410C
(33.7)
(28.6)
(23.0)
(19.7)
(14.3)
(257.9)
ASAB-1600C
130 (286.6)
3.2.4 Specifications
Supply
Mains voltage (L1, L2, L3)
5 ......................................................................................................................................................... 200 VAC ~ 525 VAC (± 10%)
7 .................................................................................................. 380 VAC ~ 600 VAC (± 10%) (in-line or inside delta connection)
7 ................................................................................................... 380 VAC ~ 690 VAC (± 10%) (earthed star supply system only)
Control voltage (A4, A5, A6)
12 ......................................................................................................... 110 ~ 120 VAC or 220 ~ 240 VAC (+ 10% / -15%), 600mA
14 ............................................................................................................................................................. 24 VAC/VDC ±20%, 2.8A

10/66
ASAB
Mains frequency ................................................................................................................................................................. 45 Hz ~ 66 Hz
Rated insulation voltage to earth ................................................................................................................................................. 600 VAC
Rated impulse withstand voltage ........................................................................................................................................................ 4 kV
Form designation ...................................................................................... Bypassed or continuous, semiconductor motor starter form 1
Short circuit capability
Coordination with semiconductor fuses ............................................................................................................................................. Type 2
Coordination with HRC fuses............................................................................................................................................................. Type 1
ASAB-0023B ~ ASAB-0220B .................................................................................................................. prospective current 65 kA
ASAB-0255B ~ ASAB-1000B .................................................................................................................. prospective current 85 kA
ASAB-0255C ~ ASAB-0930C .................................................................................................................. prospective current 85 kA
ASAB-1200C ~ ASAB-1600C ................................................................................................................ prospective current 100 kA
Electromagnetic capability (compliant with EU Directive 89/336/EEC)
EMC Emissions............................................................................................. IEC 60947-4-2 Class B and Lloyds Marine No 1 Specification
EMC Immunity ....................................................................................................................................................................... IEC 60947-4-2
Inputs
Input rating ................................................................................................................................................... Active 24 VDC, 8 mA approx
Start (54, 55) ...................................................................................................................................................................... Normally Open
Stop (56, 57) .................................................................................................................................................................... Normally Closed
Reset (58, 57) .................................................................................................................................................................. Normally Closed
Programmable input (53, 55) ............................................................................................................................................. Normally Open
Motor thermistor (64, 65) ............................................................................................................................... Trip >3.6 k, reset <1.6k
Outputs
Relay outputs ....................................................................................................... 10A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Programmable outputs
Relay A (13, 14) ..................................................................................................................................................... Normally Open
Relay B (21, 22, 24) ..................................................................................................................................................... Changeover
Relay C (33, 34) .......................................................................................................................................................... Normally Open
Analog output (40, 41) ........................................................................................................................... 0-20 mA or 4-20 mA (selectable)
Maximum load .......................................................................................................................................... 600 (12 VDC @ 20 mA)
Accuracy ................................................................................................................................................................................... ± 5%
24 VDC output (55, 41)
Maximum load.......................................................................................................................................................................... 200 mA
Accuracy ................................................................................................................................................................................. ± 10%
Environmental
Protection
ASAB-0023B ~ ASAB-0105B .................................................................................................................................................... IP20
ASAB-0145B ~ ASAB-1600C ..................................................................................................................................................... IP00
Operating temperature............................................................................................................. -10 ˚C to 60 ˚C, above 40 ˚C with derating
Storage temperature ...................................................................................................................................................... -25 °C to + 60 °C
Operating Altitude ....................................................................................................................... 0 - 1000 m, above 1000 m with derating
Humidity ....................................................................................................................................................... 5% to 95% Relative Humidity
Pollution degree ............................................................................................................................................................ Pollution Degree 3
Vibration (ASAB-0023B ~ ASAB-1000B) ......................................................................................................................... IEC 60068-2-6
Heat Dissipation
During Start .............................................................................................................................................................. 4.5 watts per ampere
During Run
ASAB-0023B ~ ASAB-0053B ................................................................................................................................ ≤ 39 watts approx
ASAB-0076B ~ ASAB-0105B .............................................................................................................................. ≤ 51 watts approx
ASAB-0145B ~ ASAB-0220B ............................................................................................................................ ≤ 120 watts approx
ASAB-0255B ~ ASAB-0500B ............................................................................................................................ ≤ 140 watts approx
ASAB-0580B ~ ASAB-1000B ............................................................................................................................ ≤ 357 watts approx
ASAB-0255C ~ ASAB-1600C ............................................................................................................. 4.5 watts per ampere approx
Certification
C....................................................................................................................................................................................... IEC 60947-4-2
CCC .................................................................................................................................................... GB 14048.6 (CNCA-01C-011:2007)
CE ..................................................................................................................................................................................... IEC 60947-4-2
GOST .................................................................................................................................................................... GOST R 50030.4.1-2002
RoHS ........................................................................................................................................ Compliant with EU Directive 2002/95/EC
UL / C-UL .......................................................................................................................................................................................... UL 508
ASAB-0023B ~ ASAB-0105B............................................................................................................ IP20 & NEMA1, UL Indoor Type 1
ASAB-0145B ~ ASAB-1600C .................................................................................................................... IP00, UL Indoor Open Type
Marine .................................................................................................................................................. Lloyds Marine No 1 Specification

ASAB
11/66
4Installation
4.1 Physical Installation
1
ASAB-0023B ~ ASAB-0220B: Allow 100 mm (3.94 inches)
between soft starters.
ASAB-0255B ~ ASAB-1000B: Allow 200 mm (7.88 inches)
between soft starters.
ASAB-0255C: Allow 100 mm (3.94 inches) between soft
starters.
ASAB-0380C ~ ASAB-1600C: Allow 200 mm (7.88 inches)
between soft starters.
2
ASAB-0023B ~ ASAB-0220B: Allow 50 mm (1.97 inches)
between the soft starter and solid surfaces.
ASAB-0255B ~ ASAB-1000B: Allow 200 mm (7.88 inches)
between the soft starter and solid surfaces.
ASAB-0255C: Allow 100 mm (3.94 inches) between the soft
starter and solid surfaces.
ASAB-0380C ~ ASAB-1600C: Allow 200 mm (7.88 inches)
between the soft starter and solid surfaces.
3
Soft starters may be mounted side by side with no clearance
(that is, if mounted without communications modules).
4
The soft starter may be mounted on its side. Derate the soft
starter's rated current by 15%.
4.2 Control Terminals
Control terminations use 2.5mm2plug-in terminal blocks. Unplug each block, complete the wiring, then reinsert the block.
13 1 4 2 1 22 2 4 33 3 4
40 41 5 3 54 5 5 56 57 5 8 6 4 6 5A4 A 5 A 6
5 4 3 2 1
9 8 7 6
A4 A5 A 6 40 41 53 5 4 5 5 5 6 5 7 5 8 6 4 65
1 3 14 2 1 2 2 2 4 3 3 3 4
1 3 1 4 2 1 22 2 4 3 3 3 4
4 0 4 1 5 3 5 4 5 5 5 6 5 7 5 8 6 4 6 5
A 4 A 5 A 6
5 4 3 2 1
9 8 7 6
5 4 3 2 1
9 8 7 6
1
2
3
4
1
2
3
4
1
Relay outputs
4
Inputs and outputs
13, 14
Relay output A
54, 55
Start
21, 22, 24
Relay output B
56, 57
Stop
33, 34
Relay output C
58, 57
Reset
2
Control voltage (model dependent)
53, 55
Programmable input A
A5, A6
110~120 VAC
64, 65
Motor thermistor input
A4, A6
220~240 VAC
40, 41
Analog output
A5, A6
24 VAC/VDC
55, 41
24 VDC output
3
DB9 connector for remote control panel
NOTE
If you are not using a thermistor, do not short terminals 64, 65.
NOTE
The DB9 connector on the soft starter should only be used to connect to a remote control panel. Connecting other
equipment to this port can damage the soft starter or the equipment.
1
4
3
2
2
1 /L 1 5 / L33/ L 2
2 /T 1 6 / T34/ T 2
1 /L 1 5 / L33/ L 2
2 /T 1 6 / T34/T 2
B
1/L15/L3
3/L 2
2/T16/T3
4/T 2
1 / L 1 5 / L33 / L 2

12/66
ASAB
4.3 Control Voltage
Different models require control voltage to different terminals:
12 (110~120 VAC) A5, A6
12 (220~240 VAC) A4, A6
14 (24 VAC/VDC) A5, A6
4.4 Control Wiring
The ASAB has three fixed inputs for remote control. These inputs should be controlled by contacts rated for low voltage, low current
operation (gold flash or similar).
1
A
B
A B
C
A
B
C
C
2 3
5 7
5 6
5 5
5 4
5 8
5 7
5 6
5 5
5 4
5 8
5 7
5 6
5 5
5 4
5 8
08721.B
1
Two-wire control
2
Three-wire control
3
Four-wire control
A
Start
B
Stop
C
Reset
CAUTION
Do not apply voltage to the control input terminals. These are active 24 VDC inputs and must be controlled with
potential free contacts.
Cables to the control inputs must be segregated from mains voltage and motor cabling.
4.5 Relay Outputs
The ASAB has three programmable relay outputs.
Operation of the programmable outputs is determined by the settings of parameters 7A~7I.
If assigned to Main Contactor, the output activates as soon as the soft starter receives a start command and remains active
while the soft starter is controlling the motor (until the motor starts a coast to stop, or until the end of a soft stop).
If assigned to Run, the output activates when the soft start is complete (when the starting current falls below 120% of the
programmed motor full load current) and remains closed until the beginning of a stop (either soft stop or coast to stop).
If assigned to a trip function, the output activates when a trip occurs.
If assigned to a flag, the output activates when the specified flag is active (parameters 7J~7L).
CAUTION
Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult the contactor
manufacturer/supplier to confirm suitability.
4.6 Motor Thermistors
Motor thermistors can be connected directly to the ASAB. The soft starter will trip when the resistance of the thermistor circuit exceeds
approximately 3.6 kor falls below 20 .
No motor thermistors
Motor thermistors
65
64
65
64
0 8 7 2 2 .A
Thermistor input
NOTE
If no motor thermistors are connected to the ASAB thermistor input terminals 64, 65 must be open. If 64, 65 are shorted,
the ASAB will trip.
The thermistor circuit should be run in screened cable and must be electrically isolated from earth and all other power and
control circuits.

ASAB
13/66
4.7 Power Terminations
NOTE
For personnel safety, the power terminals on models up to ASAB-0105B are protected by snap-off tabs. When using
large cables, it may be necessary to break off these tabs.
NOTE
Some units use aluminium busbars. When connecting power terminations, we recommend cleaning the surface contact
area thoroughly (using an emery or stainless steel brush) and using an appropriate jointing compound to prevent
corrosion.
Use only copper stranded or solid conductors, rated for 75 ºC or higher.
ASAB-0023B~ASAB-0105B
05 9 6 6 . E
Cable size:
6-50 mm2(AWG 10-1/0)
Torque: 4 Nm (2.9 ft-lb)
1 12 90 .A
14 mm (0.55 inch)
Torx T20 x 150
Flat 7 mm x 150
ASAB-0145B
ASAB-0170B~ASAB-0220B
ASAB-0255B
19 Nm (14.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
ASAB-0350B~ASAB-0425B
ASAB-0500B~ASAB-1000B
ASAB-0255C
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
ASAB-0380C~ASAB-0930C
ASAB-1200C~ASAB-1600C
38 Nm (28.0 ft-lb)
66 Nm (48.7 ft-lb)
6 m m1 9 m m
8 .5 m m
(M 8 )
08351.B
0 8 3 5 2 . B
6 m m1 9 m m
1 0 .5 m m
( M 1 0 )
5 m m
2 8 m m
11 m m
(M 1 0 )
1 3 1 8 1 . B
6 m m
2 8 m m
11 m m
( M 1 0 )
1 4 5 4 3 . A
1 3 m m
3 2 m m
11 m m
( M 1 0 )
09866.B
6 m m
3 2 m m
1 0 . 5 m m
(M 1 0 )
0 8 3 5 3 .B
1 3 m m3 2 m m
1 0 .5 m m
( M 1 0 )
0 8 3 5 4 . B
1 6 m m5 1 m m
1 2 . 5 m m
(M 1 2 )
0 8 3 5 5 .B

14/66
ASAB
4.8 Power Input and Output Configurations
4.8.1 Internally Bypassed Models (ASAB-0023B~ASAB-1000B)
Models ASAB-0023B ~ ASAB-0220B have power inputs at the top of the unit and outputs at the bottom of the unit.
Internally bypassed models ASAB-0255B ~ ASAB-0425B have output busbars at the bottom of the unit and input busbars at both the top
and bottom of the unit. The AC supply can be connected 'Top in, Bottom out' or 'Bottom in, Bottom out'.
Internally bypassed models ASAB-0500B ~ ASAB-1000B have input and output busbars at the top and bottom of the unit. The AC
supply can be connected 'Top in, Bottom out', 'Top in, Top out', 'Bottom in, Bottom out' or 'Bottom in, Top out'.
ASAB-0023B~
ASAB-0105B
ASAB-0145B~ASAB-0220B
ASAB-0255B~ASAB-0425B
ASAB-0500B~ASAB-1000B
4.8.2 ASAB-0255C
ASAB-0255C has dedicated bypass terminals at the bottom of the unit.
The bypass terminals are T1B, T2B, T3B.
4.8.3 ASAB-0380C~ASAB-1600C
ASAB-0380C~ASAB-1600C have dedicated bypass terminals, on the input busbars. The bypass terminals are L1B, L2B, L3B.
The busbars on non-bypassed models ASAB-0380C ~ ASAB-1600C can be adjusted for top or bottom input and output as required.
Refer to Busbar Adjustment Procedure for step-by-step instructions. All units are manufactured top in/bottom out.
( L 1 B L 2 B L 3 B )
1 /L 1 3 /L 2 5 / L 3
2 /T 1 4 / T 2 6 /T 3
1 /L 1 3 /L 2 5 / L 3
( L 1 B L 2 B L 3 B )
2 /T 1 4 /T 2 6 /T 3
(L 1 B L 2 B L 3 B )
1 /L 1 3 /L 2 5 / L 3
2 /T 1 4 / T 2 6 /T 3
1 /L 1 3 /L 2 5 / L 3
(L 1 B L 2 B L 3 B )
2 /T 1 4 / T 2 6 /T 3
0 8 7 2 3 . D
1 /L 1 , 3 / L 2 , 5 / L 3
2 /T 1 , 4 / T 2 , 6 /T 3
1 /L 1 3 / L 2 5 /L 3
2 /T 1 4 /T 2 6 /T 3
1 /L 1 3 /L 2 5 / L 3
2 /T 1 4 /T 2 6 /T 3
1 /L 1 3 /L 2 5 / L 3
2 /T 1 4 /T 2 6 /T 3
1 /L 1 3 /L 2 5 / L 3
1 /L 1 3 /L 2 5 / L 3
2 /T 1 4 / T 2 6 /T 3
1 4 7 6 0 . A
Stat us Graph s Logs
Exit Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA Start Stop Re set
Status Graphs Logs
Exit Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInputs
InputA Start Stop Re set
Status Graphs Logs
Exit Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInpu ts
InputA Sta rt Stop Reset
Status Graphs Logs
Exit Enter
Menu
Local
Remote
Local
Read y
Run
Trip
Start
Reset
Stop
RemoteInpu ts
InputA Start Stop Reset
14988.A
Status Graphs Logs
Exit Enter
Menu
Local
Remote
Local
Ready
Run
Trip
Start
Reset
Stop
RemoteInput s
InputA Start Stop Reset
1 /L 1 3 /L 2 5 /L 3
T 1 B T 2 B T 3 B
2 /T 1 4 / T 2 6 /T 3

ASAB
15/66
4.9 Schematic Diagrams
Internally bypassed models
Non-bypassed models
1
Control voltage (model dependent)
54, 55
Start
2
Remote control inputs
56, 57
Stop
3
Motor thermistor input
58, 57
Reset
4
Relay outputs
53, 55
Programmable input A
40, 41
Analog output
13, 14
Relay output A
55, 41
24 VDC output
21, 22, 24
Relay output B
33, 34
Relay output C
NOTE
Different models require control voltage to different terminals:
12 (110~120 VAC) A5, A6
12 (220~240 VAC) A4, A6
14 (24 VAC/VDC) A5, A6
NOTE
* ASAB-0255C current transformers are located on the output. Bypass terminals are labelled T1B, T2B and T3B.
2 2
2 1
6 /T 3
2 /T 1
13
14
4 /T 2
24
3 3
3 4
6 5
6 4
4 1
4 0
56
57
58
53
54
A 6
A 5
A 4
5 /L 3
3 /L 2
55
P E
1 /L 1
2 4 V D C
20 0 m A
0 8 7 2 4 . B
+
4
1
2
3
+
A
6 / T 3
2 /T 1
4 /T 2
5 /L 3
3 /L 2
1 /L 1
L 3B
L 2B
L 1B
4
1
2
3
P E
55
A 4
A 5
A 6
54
53
58
57
56
4 0
4 1
6 4
6 5
3 4
3 3
24
14
13
2 1
2 2
A
08725.A
*
*
*
+
+
2 4 V D C
20 0 m A

16/66
ASAB
5Power Circuits
5.1 Motor Connection
ASAB soft starters can be connected to the motor in-line or inside delta (also called three-wire and six-wire connection). When
connecting in inside delta, enter the motor full load current (FLC) for parameter 1A. The ASAB will automatically detect whether the
motor is connected in-line or inside delta and will calculate the correct inside delta current level.
5.1.1 Testing the Installation
The ASAB can be connected to a small motor for testing. During this test, the soft starter's control input and relay output protection
settings can be tested. This test mode is not suitable for testing soft starting or soft stopping performance.
The FLC of the test motor must be at least 2% of the soft starter's minimum FLC (refer to Minimum and Maximum Current Settings on
page 8).
NOTE
When testing the soft starter with a small motor, set parameter 1A Motor Full Load Current to the minimum allowable
value.
Models which are internally bypassed do not require an external bypass contactor.
5.1.2 In-line installation, internally bypassed
6 /T 3
2 /T 1
5 /L 3
3 /L 2
1 /L 1
1 3
1 4
4 /T 2
E
K M 1
K M 1 F 1
M
3
KM1
Main contactor (optional)
F1
Semiconductor fuses (optional)

ASAB
17/66
5.1.3 In-line installation, externally bypassed
Non-bypassed models have dedicated bypass terminals, which allow the ASAB to continue providing protection and monitoring functions
even when bypassed via an external bypass contactor.
The bypass contactor must be connected to the bypass terminals and controlled by a programmable output configured to Run (refer to
parameters 7A~7I).
KM1
Main contactor
KM2
Bypass contactor (external)
F1
Semiconductor fuses (optional)
NOTE
The bypass terminals on ASAB-0255C are T1B, T2B, T3B. The bypass terminals on ASAB-0380C ~ ASAB-1600C are
L1B, L2B, L3B.
The fuses can be installed on the input side if required.
5.1.4 In-line installation, non-bypassed
6 / T 3
2 / T 1
5 / L 3
3 / L 2
1 / L 1
1 3
1 4
4 / T 2
E
K M 1
K M 1 F 1
M
3
KM1
Main contactor (optional)
F1
Semiconductor fuses (optional)

18/66
ASAB
5.1.5 Inside delta installation, internally bypassed
0 4 4 7 9 .C
M
3
6 /T 3
2 / T 1
1 3
1 4
4 /T 2
K M 1
U 1 ( 1 ) U 2 ( 4 )
V 1 ( 2 ) V 2 (5 )
W 1 ( 3 ) W 2 ( 6 )
5 /L 3
3 /L 2
1 /L 1
E
K M 1 F 1
KM1
Main contactor
F1
Semiconductor fuses (optional)
CAUTION
When connecting the ASAB in inside delta configuration, always install a main contactor or shunt trip circuit breaker.
5.1.6 Inside delta installation, externally bypassed
Non-bypassed models have dedicated bypass terminals, which allow the ASAB to continue providing protection and monitoring functions
even when bypassed via an external bypass contactor.
The bypass contactor must be connected to the bypass terminals and controlled by a programmable output configured to Run (refer to
parameters 7A~7I).
M
3
6/T 3
2/T 1
5/L 3
3/L 2
1/L 1
13
14
4/T 2
E
K M 1
K M 1 F 1
U 1 (1 ) U 2 (4 )
V 1 (2 ) V 2 (5 )
W 1(3) W 2(6)
L 2 B *
L1B*
L 3 B *
K M 2
34
33
K M 2
KM1
Main contactor
KM2
Bypass contactor (external)
F1
Semiconductor fuses (optional)
NOTE
The bypass terminals on ASAB-0255C are T1B, T2B, T3B. The bypass terminals on ASAB-0380C ~ ASAB-1600C are
L1B, L2B, L3B.
The fuses can be installed on the input side if required.
CAUTION
When connecting the ASAB in inside delta configuration, always install a main contactor or shunt trip circuit breaker.

ASAB
19/66
5.1.7 Inside delta installation, non-bypassed
6 /T 3
2 /T 1
5 /L 3
3 /L 2
1 /L 1
1 3
1 4
4 /T 2
K M 1
K M 1 F1
U 1 (1 ) U 2 ( 4 )
V 1 (2) V 2 (5 )
W 1 ( 3 ) W 2 ( 6 )
M
3
0 4 4 8 3 . C
KM1
Main contactor
F1
Semiconductor fuses (optional)
CAUTION
When connecting the ASAB in inside delta configuration, always install a main contactor or shunt trip circuit breaker.
5.2 Bypass Contactor
Some ASAB soft starters are internally bypassed and do not require an external bypass contactor.
Non-bypassed soft starters may be installed with an external bypass contactor. Select a contactor with an AC1 rating greater than or
equal to the full load current rating of the connected motor.
5.3 Main Contactor
A main contactor must be installed if the ASAB is connected to the motor in inside delta format and is optional for in-line connection.
Select a contactor with an AC3 rating greater than or equal to the full load current rating of the connected motor.
5.4 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter trip. The
shunt trip mechanism must be powered from the supply side of the circuit breaker or from a separate control supply.
5.5 Earth Terminals
Earth terminals are located at the back of the soft starter.
ASAB-0023B ~ ASAB-0105B have one terminal on the input side (top).
ASAB-0145B ~ ASAB-1000B and ASAB-0255C ~ ASAB-1600C have two terminals, one on the input side (top) and one on
the output side (bottom).
5.6 Power Factor Correction
If power factor correction is used, a dedicated contactor should be used to switch in the capacitors.
CAUTION
Power factor correction capacitors must be connected to the input side of the soft starter. Connecting power factor
correction capacitors to the output side will damage the soft starter.
5.7 Power Supply Fuses
Semiconductor fuses can be used for Type 2 coordination (according to IEC 60947-4-2 standard) and to reduce the risk of damage to
SCRs from transient overload currents.
HRC fuses (such as Ferraz AJT fuses) can be used for Type 1 coordination according to IEC 60947-4-2 standard.
CAUTION
Adaptive Control controls the motor's speed profile, within the programmed time limit. This may result in a higher level
of current than traditional control methods.
For applications using Adaptive Control to soft stop the motor with stop times greater than 30 seconds, motor branch protection should
be selected as follows:
standard HRC line fuses: minimum 150% motor full load current
motor rated line fuses: minimum rating 100/150% motor full load current
motor control circuit breaker minimum long time setting: 150% motor full load current
motor control circuit breaker minimum short time setting: 400% motor full load current for 30 seconds
Table of contents
Other Santerno Controllers manuals

Santerno
Santerno ASA 4.0 Advanced Specification sheet

Santerno
Santerno Sinus Penta Quick manual

Santerno
Santerno ASAC-0 User manual

Santerno
Santerno Sinus M User manual

Santerno
Santerno Sinus Penta User manual

Santerno
Santerno ASA 4.0 Advanced User manual

Santerno
Santerno ASAC-0 User manual

Santerno
Santerno SINUS PENTA Series User manual
Popular Controllers manuals by other brands

ICP DAS USA
ICP DAS USA NMC-9181 Faq manual

Techtrol
Techtrol TLIC Instruction and programming manual

RLE Technologies
RLE Technologies SeaHawk LD310 quick start guide

Moretti Design
Moretti Design KEYPRO user manual

Thermo King
Thermo King ClimaAIRE BEA114 Operator's manual

Rodix
Rodix FEEDER CUBE FC-49 Plus quick start guide