SANYU SSXA Series User manual

1
Soft Starter SSXB/SSXA Series
Instrukcja obsługi

2
1. Function and Feature ……………………………………………………………………………… 5
2. Product Type and Inspection……………………………………………………………………… 6
3. Environment and Installation…………………………………………………………………… 7
3.1 Environment…………………………………………………………………………………………… 7
3.2 Installation…………………………………………………………………………………………… 8
4. Operating Principle………………………………………………………………………………… 9
5. Terminals and Wiring………………………………………………………………………………… 10
5.1 Wiring Diagram………………………………………………………………………………………… 10
5.2 External Terminal…………………………………………………………………………………… 11
5.3 Main Circuit Wiring………………………………………………………………………………… 12
5.4 Control Circuit Wiring …………………………………………………………………………… 12
6. Control Mode ………………………………………………………………………………………… 13
6.1 Voltage Ramp………………………………………………………………………………………… 13
6.2 Current Limit………………………………………………………………………………………… 13
6.3 Jogging ……………………………………………………………………………………………… 14
6.4 Heavy Load ……………………………………………………………………………………… 14
6.5 Stopping ………………………………………………………………………………………… 15
7. Operating keyboard………………………………………………………………………………… 16
7.1 Keyboard Description……………………………………………………………………………… 16
7.2 Key Function………………………………………………………………………………………… 16
8. Parameter Table………………………………………………………………………………………… 17
9. Special Parameter…………………………………………………………………………………… 19
10. Display Current Calibration……………………………………………………………………… 20
11. Parameter Details…………………………………………………………………………………… 21
12. Working State………………………………………………………………………………………… 24
13. Fault…………………………………………………………………………… ……………………… 25
14.1 Fault Display and Solutions…………………………………………………………………… 25
14.2 Overload …………………………………………………………………………………………… 26
15. Test running……………………………………………………………………………………… … 27
Appendix1:Specification and Type …………………………………………………………………… 28
SANYU Soft starter SSXB/SSXA serie User Manual

SANYU Soft starter SSXB/SSXA serie User Manual
3
Appendix2:SSXA Series Structure Size(Built-in bypass contactor)………………………… 29
Appendix3:SSXB Series Structure Size(bypass up)……………………………………………… 30
Appendix4:Keyboard Shape and Dimension…………………………………………………………… 31
Appendix6:SSXB Series Typical Wiring Diagram …………………………………………………… 32
Appendix7:SSXA Series Typical Wiring Diagram ……………………………………………………… 33
Appendix9:Communicate protocol………………………………………………………………………… 36

4
Manual File Number:SSXB /SSXA-V3.7.3
Version Number: V3.7
Revision Number:314
Issuance Date: 2019-10-15
1. Overview
This manual is applicable to SSXA/SSXB series products.
This manual is intended to guide qualified personnel in the installation and operation of
this product.
In the case of a registered trademark and business ownership, final interpretation right to
this manual is belonged to SANYU . Any unreasonable application, especially in
reproduction and release by the third parties, is not allowed
Although the information in this manual is checked carefully, but there may be some mistakes.
If you find them, please phone us as soon as possible.
Because this product is improved continuously, so user should regard this manual as the
reference.
The parameters in the manual are only used to describe the product.In order to meet the needs
of the customers, we will improving our products continuously to meet the latest technical
criteria.
2. Safety
Pay attention to the note, warning and tips mentioned in this manual.
Only professional technician can be permitted to install or guide the installation of this
product.
Ensuring the power and specification of the motor is matched to those of this product;
The capacitor is prohibited strictly to be connected with the output terminal (U.V.W) of this
production
The cables connecting to the input and output terminals of this product should be packed well
by insulating tape;
The shell of this product must be connected to the ground reliably;
Make sure the power of this product must be cut off before it is maintained.
This manual is packed with the product. Operator must take it as the guide of this product.
Please read it carefully before using this product.
3. Safety Mark
Attention, Warning and Notes
◆ Attention Something can lead to personal injury or death.
◆ Warning Something can lead to damage of the device or software.
◆ Note Remind user something related.
SANYU Soft starter SSXB/SSXA serie User Manual

5
1.Function and Feature
SSXA/SSXB series LED AC motor soft starter is new type starting equipment with advanced
international level. This equipment designed and manufactured by the technique of power
electronics microprocessor and modern control theory. This equipment can limit the start current
efficiently when the asynchronous motor starts. It is widely applied in the field such as winding
machine, pump, transition and compressor etc. It is the ideal product to replace the traditional
voltage dropping start equipment such as star/triangle conversion, self-coupling voltage dropping,
magnetic control dropping voltage etc.
Function
◆ Reduce the starting current of motor; reduce capacity of power distribution; reduce the
investment cost;
◆ Reduce the start stress; prolong the operation lifetime of the motor and correspond equipment;
◆ Smooth and steady starting and soft stopping; The Water hammer and surge can be avoid;
◆ Several sorts of starting mode, wide range setting of the current and voltage. It can be used
in a lot of load conditions, so the technic can be improved;
◆ Perfect and reliable protection; The safeguard of the motor and relative equipment can be
achieved effectively;
◆ It can be used in the state in which motor should star and stop frequently。
Feature
◆ Starting Mode:Based on the load characteristics, different starting mode can the related
parameters can be selected. So the best starting effect can be gained;
◆ Technical Performance:The higher performance microprocessor and software are used, so the
control circuit is simplified. The best perform speed can gained without the adjustment of the
circuit parameters;
◆ Reliability:All the electronic components of this product are selected strictly. Additionally,
the main control board is tested in high temperature environment above seventy-two hours. The
reliability of this product can be guaranteed
◆ Structure:The modularization structure and up-in-down-out wiring mode are adopted. It is
easy to used and integrated;
◆ Multi-Protection:The motor protection circuit is not be added if the single product is in
used. Because of this product have multiple protection functions (Such as over-current,
overload, phase-fault, overheat and so on). So the cost can be reduced, the circuit can be
simplified.
◆ Keyboard:Operation of the keyboard is easy. User can set and modify the parameters (for
example: starting, stopping, running, protection) by this keyboard according to different load
SANYU Soft starter SSXB/SSXA serie User Manual

6
conditions.
◆ Analog signal output:4-20mA analog sign output l is provided;
◆ RS485 provide RS485( Modbus communication protocol)communication;
◆ Actual power setting:When the rate power of Soft Starter is higher than the power of actual
load, soft starter can be matched to the actual load by modifying the actual current parameter.
So the parameters about starting、running and protection are correct
2.Product Type and Inspection
Each SSXA/SSXB series soft starter is tested. Only the starter that passes the function and
running test can leave the factory. After receiving the equipment, the user should inspect it
according the steps described below. Please notify the supplier immediately if you find any problem
◆ Check the nameplate:Check the item(s) nameplate catalog number against the purchase order.
Make sure that the equipment you received is matched with the product you ordered。
◆ Inspect whether or not the product is damaged through the delivery, for example: Inner parts
fall off, She11 is deformed or depressed, the wires are loose etc.
◆ Quality certificate and user manual: The package of each soft start includes quality
certificate and user manual.
◆ SSXA series soft starter has built-in bypass contactor.
series motor soft starter
Type:
Voltage: 3φAC380V
Motor Power: KW
Rated Current:A
Factory Number:
SANYU Soft starter SSXB/SSXA serie User Manual
SSXA/SSXB
SSXA/SSXB

7
3. Environment and Installation
3.1 Environment
The environment is important to the equipment life. So please install the soft starter on the
site described below
◆Operation Condition for the standard products
Power Supply: Urban power, self-provided substation, diesel generating sets
Three-phase AC: 380V or 660V or 1140V (-10%, +15%), 50Hz.
(note:voltage level should be matched to the rate voltage of the actually motor, user should
explain the voltage level in the purchase order if it is special.)
Motor: Squirrel cage asynchronous motor. (Please explain in the purchase order if it is special)
Start frequency: less than 20 times per hour for Standard products (Please explain in the purchase
order if the motor should be start more frequent)
Cooling: Natural air-cooled or Fan air cooling
IP Code: IP20
Environment condition: If the altitude is above 2000 M, user should select the higher power
product.
Environment Temperature: -25℃ to +40℃.
Relative humidity: ≤95% (20℃士5℃) non-condensing, no inflammable,explosive gases, no
conducive dust.
Install in an enclosure with good ventilation. The vibration is less than 0.5G
Structure Form: For the SSXB series product, bypass contactor should be allocated by user
For the SSXA series product, there is inner bypass contactor
◆Special conditions
If unconventional products using in the special conditions is needed, please explain in the
purchase order
SANYU Soft starter SSXB/SSXA serie User Manual

8
3.2 Installation
◆Direction and Distance
The product must be vertically installed. There should be enough space to dissipate the heat,
as shown in figure 3-1. For the cabinet product, there should be a certain distance between back
door of the product and wall. Therefore it is easy to maintain.
3030
120
120
Figure 3 1-
S
V
A
FU NC TI ON DA TA UN ITU
I
%
PR G
ST OP
RU N
◆Cabinet installation
If the product is installed in the cabinet, make sure there are good ventilation in the cabinet.
The products can be installed vertically or horizontally. Horizontal layout shows in Figure 3-2.
Vertical layout shows in Figure 3-3. User can adopt any of them.
Note: If the vertical layout is adopted (especial in fan air cooling mode), clapboard should be
installed between them to avoid that the upper starter is affected by heat generated by the lower
starter.
Hot airHot air Hot airHot air
Cool air
Ventilation
Figure3-2
Horizontal layout
Figure3-3
Vertical layout
Soft Starter Soft Starter
SANYU Soft starter SSXB/SSXA serie User Manual

9
4. Operating principle
There are three pairs of anti-parallel thyristors connected to the stator of motor. Using
the electric switch feature of the thyristors, the voltage of the motor can be controlled by
changing the triggering angel of the thyristors. The triggering angel of the thyristors is
controlled by microprocessor. So the motor can be started softer and smooth. After the equipment
is up to full voltage, it outputs a bypass signal. User can use this signal to control the bypass
contactor to supply the motor. See figure4-1.
Moter
R.S.T
3-phase AC power supply
AC 380V/660V/1140V
KM
Votage
detecting drive circuit Current
detecting
Computer fuzzy control
Keyboard 、display
U.V.W
Figure 4-1
SANYU Soft starter SSXB/SSXA serie User Manual

10
5. Wiring and terminal
5.1 Wiring diagram
Note:
1. There are two wiring ways to control starting and stopping the starter externally. They are three-line and
two-line wiring. (See ①and② in the figure above).Start signal is given by connecting terminal RUN and COM.
Stop signal is given by disconnecting terminal RUN and COM
Connect according the figure①,free stop
Connect according the figure②,soft stop
2. In the SSXA series product, there is no terminals U1,V1,W1.Because there is built-in bypass contactor.
3. In the SSXA series product dose no have the output terminal(K22/K24).It can be replaced by the programmable
control terminals (K32/K34).The parameter “K3” should be set “bypass”.
4. SSXA series product needs external AC220V power supply. SSXB series product dose not have external AC power
terminals (L/N).
SANYU Soft starter SSXB/SSXA serie User Manual

11
5.2 External terminals
Table 5-1
Terminal Name Terminal function Explanation
Main
circuit
R.S.T Input Connect to three-phase power source through
breaker (QF)
U.V.W Output Connect to three-phase asynchronous motor
U1.V1.W1 Bypass See figure F-6 ⑤
Control circuit
Digital input
SS Soft stop Connect SS and COM directly, Soft stop①
RUN Start Connect RUN and COM directly, Start①
STOP stop Connect STOP and COM directly, Stop①
S1 jog Connect JOG and COM directly, jog
RET reset Connect Reset and COM directly, reset the
fault
COM common Logic Ground
Communi
-cation
485+ RS485 + RS485 communication
(Modbus communication protocol)
485- RS485 -
analog
output
I
4-20Ma output
Load input resistance≤
400Ω
Im=Ie(I-4)/8
COM 4~20mA output reference
Relay output
K14 NO
Fault output
terminals②
In Fault:
K14-K12 close ; K11-K12 open
Contacts capacity
AC:10A/250V DC:10A/30V;
K11 NC
K12 COM
K24 NO Bypass
terminals②
Starting end:K24-K22close;
Contacts capacity:
AC:10A/250V or 5A/380V DC:10A/30V ③
K22 COM
K34 NO
Programmable
terminals②
Optional items: starting;running;bypass;
fault;soft stopping
Contacts capacity:
AC:10A/250V or 5A/380V DC:10A/30V
K31 NC
K32 COM
Contro
l power
L
AC220V Control power Built-in bypass contactor control power④
N
Note ①:There are two connecting mode, see figure 5-1
Note ②:Fault, bypass and programmable output terminals are all dry contact。
Note ③:SSXA series product dose not have terminals (K22/K24).
Note ④:SSXB series product dose not have control power terminals (L/N).
Note ⑤:SSXA series product dose not have bypass contactor main circuit terminals (U1/V1/W1).
Im:motor output current(A)
Ie: motor rate current(A)
I:4-20mA output current(mA)
SANYU Soft starter SSXB/SSXA serie User Manual

12
5.3 Main circuit wiring
There are nine power terminals for SSXB series product. R, S, T (Power line) and U, V, W (Motor
line) and U1, V1, W1 (Bypass line).See figure F-5.
There are six power terminals for SSXA series product. R, S, T (Power line) and U, V, W (Motor
line).See figure F-5
5.4 Control circuit terminals
There are control circuit terminals on the main control board. This control circuit terminal
provides convenience for the user to realize remote control and external signal control. User
can connect the corresponding terminals according to the actual state. By setting the parameter,
user can select keyboard mode or terminal mode by to control product to start and stop. The
terminals of SSXBseries show in figure 5-2. The terminals of SSXA series show in figure 5-3.The
terminals meaning shows in table 5-1.
Note: SSXB series product dose not have terminals” L/ N”. SSXA series product dose not have terminals”
K22/K24”.The programmable terminals”K32/K34” can be set “bypass” in parameter “K3”.
SANYU Soft starter SSXB/SSXA serie User Manual

13
6. Control mode
This product has three start modes: Voltage Ramp and Current Limit and jogging. These start
modes is independent. Only one of them can be chosen. Text below introduce that the different
of them and which mode should be selected.
6.1 Voltage Ramp
The waveform of the voltage shows in Figure 6-1. U1 in figure is initial output voltage. When
starting, the output voltage is up to U1 immediately, and then ramps up gradually according to
the parameter Start Time t setting in advance. Then the motor accelerates continuously. When the
output voltage reaches the rate value Ue, the speed of motor reaches the rate speed. Starting
process is finished. The Initial Voltage U1 and the Start Time t can be set according to the load.
The range of U1 is 5~75% Ue, and the range of t is 1~200s.
This mode is used in the state with large inertia load, or in the state in which the current
is not the important parameter but the stability is important. Using the mode, the mechanical
stress and starting striking may decreased greatly. The bigger the initial voltage is, the more
the initial torque and starting striking is. The time of starting is related to the parameter
of Starting Time and load. It is unconcerned with current limited. For detail see chapter 8 and
chapter 9.
6.2 Current Limit
At the Current Limiting mode, the output voltage increases quickly until the output current
reaches the limited current value Im. See figure 6-2. And then the output current maintains below
this limited value. Then the output voltage is increased gradually, and the motor accelerate
gradually; when the motor's speed is close to the rated,the output current decreases quickly
to the rated value Ie, the starting is over. The limited current value can be set according to
the load instance. The range of this parameter is 0.2-4Ie.
This mode is used in the state in which the current is very important parameter. Special in the
state in which the grid capacity is small. The parameter of the current limit multiples should
be set 2.5-3Ie. If this value is small, the starting will be abnormal. At this mode, the time
of starting is concerned to the parameter of the Current Limit Multiples. The more this value
电压斜 坡起动
Ue
U
U1
t1 t 2 t 3
t
图 6-1
Voltage Ramp
Figure 6-1
SANYU Soft starter SSXB/SSXA serie User Manual

14
is, the shorter the time of starting is, Vice versa. For detail see chapter 8 and chapter 9.
6.3 Jogging
At this start mode, the output voltage reaches the initial voltage U1 quickly, and remains
unchanged. Changing the U1, the output voltage and torque of the motor will change corresponding.
(See figure 6-3). It is convenient to judge the director of the motor.
6.4 Heavy load
The waveform of the voltage shows in Figure 6-1. U1 in figure is initial output voltage. When
starting, the output voltage is up to U1 immediately, and then ramps up gradually according to
the parameter Start Time t setting in advance. Then the motor accelerates continuously. When the
output voltage reaches the rate value Ue, the speed of motor reaches the rate speed. Starting
process is finished. The Initial Voltage U1 and the Start Time t can be set according to the load.
The range of U1 is 5~75%Ue, and the range of t is 1~200s.
This mode is used in the state with large inertia load, or in the state in which the current
is not the important parameter but the stability is important. Using the mode, the mechanical
stress and starting striking may decreased greatly. The bigger the initial voltage is, the more
I
Ie
t
I
m1
I
m2
I
m3
图 6-2
Figure 6-2
图 6-3
U
U
1
'
t
U
1
U
1
''
Figure 6-3
SANYU Soft starter SSXB/SSXA serie User Manual

15
the initial torque and starting striking is. The time of starting is related to the parameter
of Starting Time and load. It is unconcerned with current limited. For detail see chapter 8 and
chapter 9.
6.5 Stop Mode
There are two stop modes. User can set this parameter according to load and working condition.
●Free stop
When receiving the stop signal, the terminals K22, K24 is open, the bypass contactor is disconnected.
The trigger signal of the SCR module is close at the same time. Motor inertia stops according the
load.
●soft stop
At this stop mode, when receiving the stop signal, the bypass contactor is disconnected. At
the same time, motor is controlled through SCR. The output voltage decreases gradually. At last
motor stop completely. The stop time is related to the parameter of load and factor of soft stop
time. To gain the smooth stop effect, the Soft Stop Time should be set carefully.
SANYU Soft starter SSXB/SSXA serie User Manual

16
7. Keyboard
7.1 Keyboard Description
There is a Keyboard on the front of the soft starter. User can operate it to display data,
save data, check data, display fault, reset fault, start or stop the motor etc. The construction
of the keyboard shows in figure 7-1.
F ig u r e 7 1-
RE AD Y
Vol R amp
d i sp l ay a r ea
s ta r t m od e
s ta r t k ey
s top ( r eset )k ey
pr ogr a m m i n g k ey
da t a m od i f i cat io n k eys
7.2 Key Function
There are five key on the keyboard: RUN (start), STOP (stop), PRG (program) ▲(increase), ▼
(decrease)
● RUN (start): When the system is in Ready state, press this key to enable the motor start in the
start mode which user set.
● STOP(stop):When the system is in Starting or Running state, press this key, the motor stops,
then the system enter Ready state. When the system is on Setting state, press this
key, system enter Ready state, and the parameter user modified is saved at the same
time. When the system is on Fault state, the fault code shows on the keyboard. Press
this key, release it 5 seconds later, system enter Ready state if the fault is deal
with.
● PRG(program): On Ready state, press this key, release it 5 seconds later, system enter Setting
state. On setting state, user can switch between different parameters
● ▲(increase): On Setting state, user can increase the parameter value by press this key。
● ▼(decrease): On Setting state, user can decrease the parameter value by press this key。
Note: 1. On Setting state, press PRG key or STOP key, the modified data are saved automatically.
2. If user selects external control, the keyboard can be taken off after all the parameters set.
SANYU Soft starter SSXB/SSXA serie User Manual

17
8.Parameter table
Table 8-1
NO. Name Range and mean default Remarks
1 Para group 1:base 2:advance 3:communicate
4:Rate current 1
2 Start mode 1:Ramp▲ 2:limit★ 3:jog■
4:heavy load● 1 ▲ ★ ■ ●
3 Initial vol 5%~75%Ue 30 ▲ ●
4 Jog voltage 5%~75%Ue 30 ■ ●
5 Ramp time (1~120)S 30 ▲ ●
6 Limit Start Current. 20%~400%Ie 300 ★ ●
7 Limit start time (1~120)S 30 ★ ●
8 Start C protection 400%~600%Ie 400 ▲ ★ ■ ●
9 unbalance factor 5%~50% of present current 30 ▲ ★ ■ ●
10 Control Mode
1:keyboard 2:external
3:keyboard and external
4:communicate
5:key and communicate
6:external and communicate
7:all
3 ▲ ★ ■ ●
11 SCR trigger select 1: close trigger
2:not close trigger 1 ▲ ★ ●
12 Start overload level 1~84 ▲ ★ ●
13 Running protect current 20%~400%Ie 200 ▲ ★ ●
14 Stop mode select① 1:free stop
2:soft stop(ramp) 1 ▲ ★ ●
15 Soft stop time factor 1~10 5 ▲ ★ ●
16 Running over current ON/OFF 1:ON 2:OFF 1
17 Current unbalance ON/OFF 1:ON 2:OFF 1
18 Programmable output 0:null 1:starting 2:bypass
3:running4:soft stop 5:fault 0
19 Communicate address 1~256 1
20 Communicate baud 0:2400 1:4800 2:9600 3:14400
4:19200 5:28800 2
21 rated current See chapter 10 Motor
current
22 Fault See chapter 14
Note:▲:It is valid at Voltage Ramp mode.
★:It is valid at Current Limit mode.
■:It is valid at Jogging mode.
●:It is valid at Heavy Load mode.
SANYU Soft starter SSXB/SSXA serie User Manual

18
①:Parameter “stop mode select” is valid when control mode is keyboard. If the external control
mode is selected, stop mode is determined by external line. For detail see figure 5-1.
SANYU Soft starter SSXB/SSXA serie User Manual

19
9.Special parameter
●Rate Current
The Rate Current indicate that the output current of the soft starter at the rate power. This
parameter changes with the output power of the soft starter. For detail see chapter 9. User can query
this parameter by the method shows below.
On READY state, press ▼ key and not release, rate current displays on the keyboard, the unit
is ampere. Release this key, system return to READY state.
For Example: rate current is 150A
Figure 10-1
●Last Fault
On READY state, press STOP key and release it 5 seconds later, the last fault displays on the
keyboard. Release the key, return READY state.
For example: the last fault is missing phase
Figure 10-2
Press STOP (maintain 5 seconds)
Press▼
READY
Vol Ramp
Rate Current
150 A
READY
Vol Ramp
Fault
Phase loss
SANYU Soft starter SSXB/SSXA serie User Manual

20
10. Displayed Current Calibration
The displayed current of each Soft starter is calibrated before leave factory. If user finds
the current value showing on the keyboard is not equal to the actual current value, this parameter
can be calibrated again.
WAY1:Set the starting mode to Jogging, and the motor must be connected to its load, the parameter
of Jogging Voltage is set below 40%, keep press RUN key (enter the Jogging state), press PRG
and up or down key at the same time to modify this value until it is equal to the actual current.
Then release the RUN key and PRG key, the modified parameter save automatic.
The other way can be adopted when circumstances permit.
WAY2: At the Bypass state, press RUN+▲ key or RUN+▼ key, this parameter can be modified to match
to the actual current.
SANYU Soft starter SSXB/SSXA serie User Manual
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

Avipas
Avipas AV-3207 user manual

Consort
Consort CRX2-03 Installation and user guide

Phoenix Mecano
Phoenix Mecano LD75E+P Assembly instruction

Kutai electronics
Kutai electronics ADVR-250 Operation manual

Grundfos
Grundfos GI SPC Series Installation and operating instruction

PhaseOne
PhaseOne iX MK 5 Installation and operation guide