Schaffner RWK305 Operating manual

1/4 User and installation manual 3-Phase Load Reactor RWK305
Revision: 04 (June 2023)
English version (original instructions)
Please also read and follow the “General safety notes and installation guidelines” provided with the
product. More technical information of RWK305 can be found from the datasheets of the products
available at schaffner.com.
Version history
Revision
Date
Description
01 (A)
August 2015
Initial version
02 (B)
April 2017
Addition of RWK212 series in the same document
03 (C)
May 2017
Addition of page 2, required drives settings and fPWM vs motor cable
length chart
04 (D)
June 2023
New Schaffner branding template
Removal of EOL RWK212 series
Clarification of the mounting positions
Filter placement and mounting
Lift the heavy reactors which do have lifting eyes with appropriate lifting aids –smaller types may be
lifted manually by two persons (no lifting eye bolt applicable). RWK305 is a 3-phase load reactors device
and should be wired in series and positioned on the output side of the VSD (VFD). All terminals marked.
U1, V1, and W1 are the input terminals where the 3 phases of incoming power are to be wired. As a
result, U2, V2, and W2 are the output terminals.
The mounting of RWK305 shall be made on a metal plate which has a reliable protective
earth
(PE)connection.
Always connect RWK305 to the protective earth (PE) first, and then continue with
the wiring of line terminals. When decommissioning the RWK305 remove the PE
connection at the end.
RWK305 reactors can reach surface temperatures up to 175°C when driven under
maximum allowed load. Avoid burnings by waiting long enough after that the application
is switched off.
Ambient temperature and clearance
RWK305 shall be installed where the ambient temperature does not exceed 100°C. Do not locate the
reactor next to any other component with operating surface temperature above 125°C.
RWK305 reactors can be used to a maximum altitude of 2000m without derating, and with derating
(current and voltage) above 2000m according to IEC 60664-1.

User and installation manual 3-Phase Load Reactor RWK305 2/4
RWK305 reactors are designed to be floor-
mounted or wall-mounted. In principle, the
reactors shall be mounted vertically to respect a
proper heat dissipation flow. To ensure an
optimal ventilation and thermal radiation, it is
recommended to leave enough space towards
surrounding equipment, walls or components in
all directions.
For floor-mounting, clearance above the
filter of >150mm and >50mm aside is
required.
RWK305
Drive
>150mm
>150mm
>50mm
>50mm
The recommended, permitted and prohibited mounting positions are shown in Figure 1 to Figure 4. The
mounting on a vertical plate is limited to products with a maximum weight of 25kg. Larger reactors
must be mounted in a horizontal position.
Figure 1 Recommended mounting positions
(Floor mounting)
Figure 2 Wall mounting
Figure 3 Permitted mounting positions
Figure 4 Prohibited mounting positions
Use all available mounting holes
and select the correct screws and washers (more information please
refer to the product datasheet) to ensure reliable mounting and consider
the weight of these products.
Apply torques appropriate for the strength class of the screws and
washers you are using. Specifications
can be obtained from the supplier of the screws and washers.
< 25 kg

3/4 User and installation manual 3-Phase Load Reactor RWK305
Required drives settings
Ensure the motor drive switching frequency (fPWM) is set to the required switching frequency. Check
the drives manual whether special settings are necessary. For any questions, please contact the drive
manufacturer. Refer to the following “fPWM/motor cable length” diagram:
Figure 5 relation curve between fPWM and motor cable length
If the drives settings are not correct, the dv/dt effect may not be sufficient to protect the
motor winding insulation and the filter may be damaged!

User and installation manual 3-Phase Load Reactor RWK305 4/4
[This page is intentionally left blank]

Schaffner EMV AG
Nordstrasse 11e |4542 Luterbach |Switzerland |Main +41 32 681 66 26 |schaffner.com
The information contained within this document and the functions
offered are solely intended to provide information about products
available for purchase from Schaffner group companies
(“Schaffner”) and do not constitute an offer for purchase or sale
or a recommendation or advice. The content of this document
has been carefully prepared and reviewed and all reasonable
efforts have been made to ensure the accuracy of the
information. However, Schaffner does not warrant the accuracy
and does not assume any liability whatsoever for any errors or
inaccuracies of this document and the consequences there of.
Schaffner accepts no responsibility or liability for any losses or
damages of any kind arising out of the use of this document or
any of its related functions. Further, Schaffner cannot be held
responsible for any errors or unexpected unfulfillment of
shipments. Schaffner reserves the right to make changes to this
document, the products, the published specifications and any
other functions at any time without notice. Product suitability for
any area of application must ultimately be determined by the
customer. In all cases, products must never be operated outside
their published specifications. Schaffner does not warrant,
represent or guarantee the availability of any or all published
products. The latest publications and product specification
sheets as well as the current Schaffner general terms and
conditions and data protection policy apply; these documents
and the complete legal disclaimer can be downloaded from the
Schaffner website. In order to improve readability, the masculine
form is mainly used for people and personal nouns in this
document. All references to persons apply equally to all genders.
The abbreviated language form has only editorial reasons and
does not imply any valuation.
All intellectual property rights, such as trademarks, tradenames,
designs and copyrights, are reserved and are exclusively owned
by Schaffner Holding AG. This document may exist also in other
languages. This version is valid and binding.
This disclaimer shall be governed by substantive Swiss law and
resulting disputes shall be settled by the courts at the place of
business of Schaffner Holding AG.
© 2023 Schaffner Holding AG
Table of contents
Other Schaffner Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Gema
Gema OptiFlex 2 V Operating instructions and spare parts list

TAS
TAS 3012 user manual

Alfalaval
Alfalaval Toftejorg SaniJet 20 instruction manual

Alfalaval
Alfalaval BaseLine M instruction manual

Ebmpapst
Ebmpapst ArgoDrive AD-80.7 installation instructions

woodmizer
woodmizer PD200G19-S Safety, Operation, Maintenance & Parts Manual