1.6 Warning about misuse
In case of inadequate or improper use or manipulations of
the safety-monitoring module, personal hazards or damage
to machinery or plant components cannot be excluded.
The relevant requirements of the standards ISO 14119 and
ISO 13850 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly
forbidden; the manufacturer shall accept no liability for damages
resulting from such invasive work, arbitrary repairs, conversions and/or
modifications to the device.
The safety-monitoring module must only be used when the enclosure is
closed, i.e. with the front cover fitted.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
SRB 200X2
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Purpose
The safety-monitoring modules for integration in safety circuits are
designed for fitting in control cabinets. They are used for the safe
evaluation of the signals of positive break position switches or magnetic
safety sensors for safety functions on sliding, hinged and removable
safety guards as well as emergency stop control devices and AOPD's.
The safety function is defined as the opening of the enabling circuits 13-
14 and 23-24 when the inputs S11 - S12 and/or S11 - S22 are opened
or when the supply voltage A1 is disconnected. The safety-relevant
current paths with the output contacts 13-14 and 23-24 meet the
following requirements under observation of a B10D value assessment
(also refer to "Requirements of DIN EN ISO 13849-1"):
– Control category 4 - PL e to DIN EN ISO 13849-1
– SIL 3 to DIN EN 61508-2
– SILCL 3 to DIN EN 62061 (meets the requirements of control
category 4 to DIN EN 954-1)
To determine the Performance Level (PL) of the entire safety function
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all
relevant components is required.
The entire concept of the control system in which the safety
component is integrated, must be validated to the relevant
standards.
2.4 Technical data
General data:
Standards: IEC/EN 60204-1, EN 60947-5-1;
EN ISO 13849-1, IEC/EN 61508
Climate resistance: EN 60068-2-78
Mounting: Snaps onto standard DIN rail to EN 60715
Terminal designations: EN 60947-1
Material of the housings: Plastic, glass-fibre reinforced
thermoplastic, ventilated
Material of the contacts: AgSnO, self-cleaning, positive drive
Weight: 230 g
Start conditions: start button (monitored)
Feedback circuit (Y/N): yes
Drop-out delay: 1-channel input circuit: typ. 50 ms
2-channel input circuit: typ. 20 ms
Pull-in delay: typ. 20 ms
Bridging in case of voltage drops: typ. 50 ms
Mechanical data:
Connection type: Screw connection
Cable section: min. 0,25 mm² / max. 2,5 mm²
Connecting cable: rigid or flexible
Tightening torque for the terminals: 0.6 Nm
With removable terminals (Y/N): Nein
Mechanical life: 10 million operations
Electrical life: Derating curve available on request
Resistance to shock: 10 g / 11 ms
Resistance to vibrations to EN 60068-2-6: 10 ... 55 Hz,
amplitude 0.35 mm
Ambient conditions:
Ambient temperature: –25 °C … +60 °C
Storage and transport temperature: –40 °C … +85 °C
Protection class: Enclosure: IP40
Terminals: IP20
Clearance: IP54
Air clearances and creepage distances to IEC/EN 60664-1: 4 kV/2
(basic insulation)
EMC rating: to EMC Directive
Electrical data:
Contact resistance in new state: max. 100 mΩ
Power consumption: max. 1.5 W / 3.0 VA
Rated operating voltage Ue:24 VDC –15% / +20%,
residual ripple max. 10%
24 VAC –15% / +10%
Frequency range: 50 / 60 Hz
Fuse rating for the operating voltage: Internal electronic trip,
tripping current > 1 mA,
reset after approx. 1 sec.
Current and voltage at: S11-S12: 24 VDC,
continuous current: 40 mA,
start impulse: 700 mA / 5 ms
S21-S22 24 VDC, continuous current: 40 mA,
start impulse: 700 mA / 5 ms
S33-S34: 24 VDC,
start impulse: 200 mA / 5 ms
Monitored inputs:
Short-circuit recognition (Y/N): Yes (if dual-channel)
Wire breakage detection (Y/N): Yes
Earth leakage detection (Y/N): Yes
Number of NO contacts: 0
Number of NC contacts: 2
Cable length: 1-channel without cross-wire short detection:
– 1,500 m = 1.5 mm²
– 2,500 m = 2.5 mm²
2-channel without cross-wire short detection
Conduction resistance: max. 40 Ω
Outputs:
Number of safety contacts: 2
Number of auxiliary contacts: 0
Number of signalling outputs: 0