off until the temperature cools below the value defined in frs.
Range: : –50 to 120 °C (-58 to 248°F)
fdl
Fan maximum delay after draining – to assure product integrity, the
fan output will be unconditionally turned on after the time programmed
in fdl, regardless of the fact that the evaporator temperature may not
have reached the temperature value defined in frs
Value in minutes, 0 to 999.
foc
Fan behavior during refrigeration .
0Fan is active only whenthe compressor is on..
1Fan is active during the complete refrigeration cycle, even when the
compressor is turned off.
fod
Fan behavior during defrost.
0Fan is off during the defrost cycle.
1Fan is active during the defrost cycle.
fss
Fan deactivation due to evaporator heating – evaporator temperature
that turns the Fan off when the evaporator heats up (above temperature
defined in fss), improving system efficiency and protecting the
compressor. The fan is allowed to turn on again when the temperature
drops 2 degrees below the value defined in this parameter.
Coe
Compressor function during a probe failure: This parameter fixes the
compressor operating mode in the event of the main probe failure.
0Compressor is deactivated when probe 1 is in error.
1Compressor is activated when probe 1 is in error
Dfh
defrost hold
Defrost hold time (temperature indication hold): This is the time
interval following the end of the defrost cycle for the controller to display
actual control temperature. During the defrost cycle and the time defined
by dfh, the display will be showing the last measured temperature prior
to the start of the defrost cycle.
0 : function disabled (shows actual temperature during the
defrost cycle);
1 to 250 : Time interval (sec., min. or hours) after the end of defrost for
the display to show the actual control temperature.
Level 3 – Calibration level
The controller is factory calibrated. The following parameters should be accessed only
by experienced personnel. To enter this cycle, the key must be kept pressed for 4
seconds.
Don’t press the and keys if you are not sure of the calibration
procedures. Just press the key a few times until the temperature
measurement level is reached again.
Pas Password - Enter the correct password to unlock write operations for
the parameters in the following levels.
[l1 Calibration low input 1 – Zero value of the input 1. It adjusts the
lower measurement range of Probe 1.
[k1 Calibration High input 1 – Gain calibration. It adjusts the full scale
measurement range of the Probe 1.
[l2 Calibration low input 2 – Zero value of the input 2. It adjusts the
lower measurement range of of Probe 2.
[k2 Calibration High input 2 – Gain calibration. It adjusts the full scale
measurement range of the Probe 2.
FA( Factory Calibration – Restores factory calibration parameters.The
value 1restores the calibration parameters to the factory values.
Prt Protection – Defines the levels of parameters that will be password
protected. See “Configuration Protection Usage” for details.
Pa( Password Change - Allows changing the current password to a new
one. Values from 1 to 999.
Sn2 Serial number - First part of the instrument serial number.
sn1 Serial number - Second part of the instrument serial number.
sn0 Serial number - Third part of the instrument serial number.
CONTROLLER OPERATION
The controller turns on and off the compressor output such as to maintain the
temperature at the selected Setpoint. The front panel display shows the symbol
whenever the compressor is active.
Defrost
Function to eliminate the ice accumulated on the evaporator, for improving system
efficiency. The duration and interval of the defrost cycles are user configurable.
However, it may be unconditionally terminated depending on the evaporator
temperature as measured by Probe 2 (refer to the dfs parameter)
The defrost can be achieved by: 1) compressor deactivation; 2) electrical heater or
3) heat pump inversion.
In the first case, the refrigeration is turned off and the defrost happens naturally. In the
second case the defrost output drives an electrical resistance to generate heat and so
melt the ice. In this mode, the compressor output is also deactivated. In the third case,
heat pump inversion, the compressor is kept active and the defrost output commands
the valve that inverts the heat cycle.
During defrost, the case of coldroom temperature may be forced to reflect the last
temperature measured prior to entering the defrost cycle (refer to the dfh parameter).
The df1 and dft parameters define, respectively, the time interval between defrosts
and the duration of the defrost cycle. The controller display shows the symbol to
indicate that a defrost cycle is in progress.
Manual defrost: The key allows that a defrost cycle be initiated of terminated
immediately. Pressing this key for 3 seconds will toggle the current defrost status.
Definition of the evaporator temperature that terminates the defrost. (dfs
parameter)
- Wait for ice building on the evaporator;
- Start a defrost cycle manually;
- Visually monitor the evaporator until there is no more ice onit.
- Check the Probe 2 temperature (momentary press on the key). This is the
correct temperature setting for the dfs.parameter.
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters
is implemented. The level of protection can be selected from partial to full. The following
parameters are part of the protection system:
Pas When this parameter is presented, the correct password must be entered to
allow changes of parameters in the following levels.
Prt Defines the level of parameters that will be password protected:
1 - Only calibration level is protected (factory configuration);
2 - Calibration and Configuration levels areprotected;
3 - All levels are protected - calibration, Configurationand setpoints.
PA( Parameter for definition of a new password. Since it is located in the
calibration level, can only be changed by a user that knows the current
password. Valid passwords are in the range 1 to 999.
CONFIGURATION PROTECTION USAGE
The PAS parameter is displayed before entering a protected level. If the correct
password is entered, parameters in all following levels can be changed. Ifwrong or no
password is entered, parameters in the following levels will be read only.
Important notes:
1- After five consecutive attempts to enter a wrong password, new tentative will be
blocked for the next 10 minutes. If the current valid password is unknown, the master
password can be used only to define a new password for the controller.
2 - The password for a brand new device is 111.
MASTER PASSWORD
The master password allows user to define a new password forthe controller, even if
the current password is unknown. The master password is based in the serial number
of the controller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]
for example the master password for the device with serial number 987123 465 is: 1 9 3 6
as follows: 1 + sn2= 987; sn1= 123; sn0= 465 = 1 9 3 6
How to use the master password:
1- Enter the master password value at PaS prompt.
2- Go to PA( parameter and enter the new password, which must not be zero (0).
3- Now you can use this new password to access all controller parameters with modify
rights.
ERROR MESSAGES
Probe measurement errors force the controller outputs to be turned off. The cause for
these errors may have origin in a bad connection, sensor defect (cable or element) or
system temperature outside the sensor working range. The display signs related to
measurement errors are shown below
Measured temperature exceeded maximum allowed range for the
sensor. Broken Pt100, Pt1000 or T/C. Short circuited NTC sensor.
Measured temperature is below minimum measurement range of the
sensor.Short circuited Pt100, Pt1000 or T/C. Broken NTC.
PRODUCT IDENTIFICATION
The label attached to the controller case identifies the model and the optional present in
the product, as described below: