Sdataway EasyBus3 Series Guide

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 1 / 38 Revision 1 / April 2019
Easy3 System –Technical documentation
Easy3-H –Easy3-M
230 VAC Power Line Communication system
Interactive colour touch screen 4”
Easy-to-Use graphical interface
Up to 128 devices on each Sub-Network
Up to 1000m length by Sub-Network
Up to 3 Sub-Networks on the same display
oUp to 384 devices in one installation
oUp to 3000m total network length installation
Advanced power line communication
o255 communication channels
oUp to 28800 bps
oAutomatic adaptive modulation
Configurable inputs and outputs
o8 universal digital inputs/outputs
o2 output relays
oConfigurable I/O functions
Integrated 2 ports ethernet switch
Monitoring function with USB or SD card
Integrated filter
Device groups
o2 groups on each network
oGroup by priority or function
Group control/monitoring with digital I/Os
Modbus RTU/RS-485 and TCP/IP
BACnet MS/TP or BACnet IP by gateway
DIN rail or screw fixation

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 2 / 38 Revision 1 / April 2019
Table of content
Table of content ............................................................................................................................................... 2
1Safety instructions.................................................................................................................................... 3
2General Information................................................................................................................................. 3
Compliance ............................................................................................................................................... 3
Disposal instructions................................................................................................................................. 3
Symbol instructions .................................................................................................................................. 4
Operating conditions ................................................................................................................................ 4
Storage and transport conditions ............................................................................................................. 4
Copyright © .............................................................................................................................................. 4
3Technical characteristics........................................................................................................................... 5
4System overview ...................................................................................................................................... 6
5EasyBus3® Network.................................................................................................................................. 7
Topologies................................................................................................................................................. 7
Distance between networks cables .......................................................................................................... 7
Minimum / Maximum Configuration........................................................................................................ 8
Remote Easy3-M devices.......................................................................................................................... 9
Electrical connection to mains network ................................................................................................. 10
Power Line Networks.............................................................................................................................. 11
6Easy3-H................................................................................................................................................... 12
X1 –Power supply 24Vdc........................................................................................................................ 13
X2 –Modbus RS-485............................................................................................................................... 14
X3 –USB.................................................................................................................................................. 15
X4 –Configurable 2x output relays......................................................................................................... 16
X5, X6 –TCP/IP ethernet ports ............................................................................................................... 17
X7 –Configurable 8x Inputs / Outputs.................................................................................................... 18
X8 –Easy3-Master bus............................................................................................................................ 19
Micro SD card.......................................................................................................................................... 20
7Easy3-M.................................................................................................................................................. 21
X1–USB................................................................................................................................................... 22
X2 –EasyBus3® Sub-Network 230 Vac ................................................................................................... 23
X3, X4 –EasyBus3®-Master..................................................................................................................... 24
X5 –Mains 230Vac input ......................................................................................................................... 25
8Mechanical fixations............................................................................................................................... 26
9Dimensions............................................................................................................................................. 27
11 ModBus Register .............................................................................................................................. 28
EaysBUS3® Easy3-M(Master).................................................................................................................. 28
EaysBUS3® ModBus RTU information..................................................................................................... 29
EaysBUS3® ModBus B24/B230 Fire damper ........................................................................................... 32
12 Contact............................................................................................................................................. 38

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 3 / 38 Revision 1 / April 2019
1Safety instructions
Please read the safety precautions carefully before EasyBus3® system installation and maintenance.
Please follow the instructions below.
- The installation or maintenance must accord with the instructions.
- Comply with all national electrical codes and local electrical codes.
- Pay attention to the warnings and cautions in this manual.
- All installation and maintenance shall be performed by distributor or qualified person.
- All electric work must be performed by a licensed technician according to local regulations and
the instructions given in this manual.
- Be caution during installation and maintenance. Prohibit incorrect operation to prevent electric
shock, casualty and other accidents.
The EasyBus3® system (including all EasyBus3® modules) must be:
- Installed, commissioned, maintained, repaired and removed by a qualified installer or qualified
service person. When any of these jobs is to be done, ensure that only qualified installer or
qualified service person is performing it. A qualified installer or qualified service person is an
agent who has the mandatory qualifications and appropriate knowledge to perform the task(s)
required.
For all the tasks related to the 230VAC power supply:
- Installation and maintenance must be performed by a skilled electrical installer ensuring all legal
and official regulations compliance.
- All wiring & connections must be done with the power off and according to the local energy
supplier's instructions.
2General Information
Compliance
The EasyBus3® system (including all EasyBus3® modules) complies with the following standards:
EN 60730-1
https://ec.europa.eu/eip/ageing/standards/home/sensors-actuators-and-
alarms/en-60730_en
CENELEC EN50065-1
https://www.cenelec.eu/standardsdevelopment/ourproducts/europeanstandards.h
tml
Disposal instructions
Unit Disposal Instructions
The EasyBus3® modules contain electronics. Please do not discard with
regular waste. Return to SDATAWAY or dispose according to local guidelines
for disposing of electronics. Dispose according to Waste Electrical and
Electronic Equipment (WEEE) directive in European Union.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 4 / 38 Revision 1 / April 2019
Symbol instructions
Electrical Shock or Burn Hazard (230 VAC)
All electric work must be performed by a licensed technician
according to local regulations and the instructions given in this
manual.
Caution Hot surface
Warning to catch your attention to important points, the non-respect
of these points could:
- Impact / Reduce the system functionalities.
- Damage the modules and / or the entire installation.
Operating conditions
Minimum / Maximum ambient temperature:
5 –40 0C
Humidity
0 –95% RH, non-condensing
Operating
Indoor Use only
Storage and transport conditions
The EasyBus3® modules should be stored and transported in environmental conditions of -10OC to 60
OC, 0 to 95% RH, non-condensing.
Copyright ©
This documentation and its contents are the property of SDATAWAY SA.
Reproduction, in whole or in part, is permitted only for the use of EasyBus3® products.
The author and SDATAWAY SA are not responsible for any errors contained in this document and their
potential consequences. These potential errors include errors in writing, translations and transcripts.
© 2018 SDATAWAY All Rights Reserved - Non-contractual pictures, technical specifications might
change at any time.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 5 / 38 Revision 1 / April 2019
3Technical characteristics
Description
Name
Min.
Typ.
Max.
Unit
Electrical characteristics
Easy3-H supply voltage
VEASY3-H
21.6
24
26.4
Vdc
Easy3-H power consumption
PEASY3-H
10
W
Easy3-M power consumption (Note 1)
PEASY-M
10
W
Easy3-M supply voltage
VEASY3-M
230
Vac
Easy3-M high voltage power consumption
PEASY3-M-HV
5
VA
Easy3-M maximum load power
PEASY3-M-LOAD
2000
VA
Easy3-H digital inputs/outputs
Input maximum voltage
VIN-MAX
30
Vdc
Input low level voltage
VIN-LOW
0
4
Vdc
Input high level voltage
VIN-HIGH
10
24
Input pull-up resistor
RIN
3.3
kΩ
Output voltage
VOUT
21.6
24
Vdc
Maximum output current (each output)
IOUT-MAX
100
mA
Easy3-H output relays
Switching voltage
VREL-MAX
230
Vac
Switching current
IREL-MAX
10
A
Power-line communication
Frequencies
fPLC
100
240
kHz
Modulations
Mod
PSK/FSK
Baud rate
-
2400
28800
Bps
Number of slave devices per Easy3-M
NSLAVES-MAX
128
Communication time per slave
tCOM-SLAVE
40
ms
Cycle time 128 devices
tCYCLE
7s
Maximum cycle time for 8 slave devices in
high priority group
tCYCLE-8
1
s
Connections distances
Easy3-H to Easy3-M
LMASTER
100
m
Sub-Network total length
LNETWORK
1000
m
Network total length
L3NETWORKS
3000
m
Certification
EN 60730-1
CENELEC EN50065-1
Protection class
IP20
Note 1: The Easy3-M(s) is powered by 24V from the Easy3-H. Then the Easy3-M(s) power
consumption must be added to the Easy3-H power consumption and taken in consideration
to calculate the 24V power supply power.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 6 / 38 Revision 1 / April 2019
4System overview
The EasyBus3® system is designed to remotely control slave devices over a proprietary power line
communication (PLC). The slave devices are specifically designed to match building automation
ventilation system needs such as fire dampers, variable valves, general purpose inputs and outputs,
and more…
The system is composed of three types of devices which are described here below.
Easy3-H
The Easy3-H device is the main controller of the system. It is the communication gateway between the
building automation control system and the Easybus3® network. It is capable to manage up to three
Easy3-M devices.
Easy3-M
The role of the Easy3-M device is to communicate with the remote slave devices using powerline
communication over the mains network (230 VAC). One Easy3-M is able to control up to 128 slave
devices. The Easy3-M device must be connected to an Easy3-H using a dedicated cable.
Slave devices
Different types of slave devices are available. Each type is designed for a specific function such as fire
damper motor control, variable valve control, general purpose inputs and outputs, and more… They are
connected to the mains network and communicate with the Master using powerline communication over
the mains network.
Please refer to specific EasyBus3® slave devices product specification for complete
description.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 7 / 38 Revision 1 / April 2019
5EasyBus3® Network
Topologies
The EasyBus3® Sub-Network supports the following topologies:
Star Tree Bus
Line
Distance between networks cables
To avoid any communication interference between the different network, it is required to keep a
minimum distance of 5cm between all the EasyBus3® network cables.
>5cm
>5cm
EasyBus3®
Sub-Network 1
EasyBus3®
Sub-Network 2
EasyBus3®
Sub-Network 3

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 8 / 38 Revision 1 / April 2019
Minimum / Maximum Configuration
The diagram below shows the main network topology in its maximum configuration.
It is composed of a Easy3-H device connected to the building automation system and three Easy3-M
devices.
Each Easy3-M device is powered from the mains network and can control up to 128 slave devices
Total up to 1km –Max 128 Easy3-X
Total up to 1km –Max 128 Easy3-X
Total up to 1km –Max 128 Easy3-X
Electrical panel
230Vac
To building automation
Floor 1
24Vdc
Floor 2
Floor 3
The maximum distance of a Sub-
Network generated by a Master is 1000 m.
This distance is given for information only. It can
varyaccordingtothe numberofslavemodules,the
network but also many external parameters such
as the architecture of the network, the structure of
the building, the cables types, etc...
It is up to the installer to ensure and size the
additional electrical elements to the specific
constraints of the installation.
Maximum EasyBus3® system
configuration:
- 1 Easy3-H
- 3 Easy3-M
-
384 Easy3-X (Slave Modules)
Minimum EasyBus3® system configuration:
- 1 Easy3-H
- 1 Easy3-M
- 1 Easy3-X (module slave)
230Vac
24Vdc
Electrical panel
To function, an EasyBus3® system must get at least the following configuration:

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 9 / 38 Revision 1 / April 2019
Remote Easy3-M devices
In the main topology, the Easy3-M devices are intended to be placed together with the Easy3-H module
in the building electrical panel.
But it is also possible to relocate the Easy3-M modules next to the ventilation systems while
respecting a maximum and total distance of 100 meters between the Easy3-H and the far-most
Easy3-M(s).
In this configuration Easy3-M(s) must be located in a dedicated electrical cabinet.
Total up to 1km
Total up to 1km
Total up to 1km
To building
automation
Electrical panel
24Vdc
230Vac
Floor 1
Floor 2
Floor 3
Total up to 100m

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 10 / 38 Revision 1 / April 2019
Electrical connection to mains network
The 230 Vac inputs of the Easy3-M devices must be protected as a minimum with 13A Type B circuit
breaker.
B13
230Vac
Easybus3®
Sub- Network 1
Easybus3®
Sub-Network 2
B13
It is up to the installer to ensure and size the additional electrical elements
to the specific constraints of the installation.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 11 / 38 Revision 1 / April 2019
Power Line Networks
EasyBus3® Sub-Networks are proprietary powerline networks.
Only EasyBus3® products can be installed on these networks.
EasyBus3® Sub-Network(s) cannot be used as power supply network(s). It is strictly forbidden
to install T13 plugs to supply other equipment.
The addition of supplementary non-compatible products may lead to damage to the modules and / or
the entire installation.
Total up to 1km
Total up to 1km
Total up to 1km
Electrical panel
230Vac
To building automation
Floor 1
24Vdc
Floor 2
Floor 3

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 12 / 38 Revision 1 / April 2019
6Easy3-H
The Easy3-H device is the main controller of the system.
It is the communication gateway between the building automation control system and the EasyBus3®
network.
By design, depending of the installation size, configuration & requirements, it can also operate the entire
EasyBus3® system in autonomous mode.
It is capable to manage up to 3 EasyBus3® Easy3-M devices.
8x Inputs/Outputs
Easy3-Master Bus
2x Ethernet
2x output relays
RS-485
24Vdc
SD card / USB

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 13 / 38 Revision 1 / April 2019
X1 –Power supply 24Vdc
Easy3-H requires a 24Vdc power supply. The X1 electrical terminal is the 24Vdc power supply input for
the EasyBus3® system.
Pin no.
Description
24V
Positive power supply
0V
0V reference voltage
Description
Min.
Nom.
Max.
Unit
Power supply voltage
21.6
24
26.4
Vdc
Power supply current
2
A
Wire size
0.2
2.5
mm2
The Easy-3M(s) is powered by 24V from the Easy3-H. Then the Easy3-M(s)
power consumption must be added to the Easy3-H power consumption and
taken in consideration to calculate the 24V power supply power.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 14 / 38 Revision 1 / April 2019
X2 –Modbus RS-485
The X2 electrical terminal is the interface connection between the automation building system and the
EasyBus3® system using a Modbus RTU protocol.
Pin no.
Description
A+
RS-485 A+
B-
RS-485 B-
REF
Reference voltage, 0V
Description
Nom.
Unit
Termination resistor
120 (software switchable)
Ohm
Baud rate
9600, 19200, 36400, 56600, 115200
bps
Parity / Stop bits
8-N-2, 8-E-2, 8-O-2
Protocol
Modbus RTU
Wire size
0.75 (max 1.5)
mm2
A+
B-
REF
Bus in
Bus out
A+
B-
REF

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 15 / 38 Revision 1 / April 2019
X3 –USB
The X3 USB connector enables access to system data stored on the SD card data from a computer.
Description
Nom.
Connector type
Mini-USB
Protocol
Proprietary / Maintenance

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 16 / 38 Revision 1 / April 2019
X4 –Configurable 2x output relays
The X4 electrical terminal is used to expose two outputs poles dry contacts. These contacts can be
mapped on several software computed states (damper status, smoke detection, etc.).
Pin no.
Description
Q11
Relay 1 terminals
Q12
Q21
Relay 2 terminals
Q22
Description
Typ.
Unit
Switching voltage
230
Vac
Switching current
10
A
Wire size
0.2 .. 2.5
mm2
230Vac
~

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 17 / 38 Revision 1 / April 2019
X5, X6 –TCP/IP ethernet ports
The X5/X6 RJ45 connectors are the interface connections between the automation building system
and the EasyBus3® system using a Modbus TCP protocol.
These ethernet ports are not
compatible with PoE
Note: Both ports are connected to an ethernet switch and to the internal device. There is no functional
difference between them. They can be used to chain several Easy3-H or to connect a
maintenance device in parallel.
Description
Nom.
Unit
Connector type
RJ45
Speed
10 / 100
Mbit
IP
IPV4
Addressing mode
DHCP, static
Protocol
Modbus TCP

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 18 / 38 Revision 1 / April 2019
X7 –Configurable 8x Inputs / Outputs
The X7 electrical terminal (I/Os) is used to expose 8 configurable inputs/outputs contacts. These
contacts can be mapped on several software computed states (damper status, smoke detection, etc.)
or commands (damper control, fire input, etc.).
Note: The input switches and output loads are shown as an example. Each signal pin can be
configured either in input or output mode.
Pin no.
Description
X1 .. X8
Configurable input / output signal
0V
0V reference voltage
Description
Min.
Typ.
Max.
Unit
Input maximum voltage
30
Vdc
Input low level voltage
0
4
Vdc
Input high level voltage
10
24
Input pull-up resistor
3.3
kΩ
Output voltage
24
Vdc
Maximum output current
100
mA
Wire size
0.2
2.5
mm2
S2
S1
Input switches
Output loads

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 19 / 38 Revision 1 / April 2019
X8 –Easy3-Master bus
The X8 RJ45 connector is a 24 Vdc output power line communication.
It is using a proprietary BUS protocol to communicate and supply power to one or more Easy3-M(s).
Description
Nom.
Unit
Connector type
RJ45
Protocol
Proprietary
Maximum voltage
24
V
Cable type
Min. Cat-5, F/FTP or S/FTP
This port is using a RJ45 connector
but is not compatible with ethernet.
Plugging a RJ45 with PoE can
damage the electronics.

EasyBus3® System
Technical documentation
Property of SDATAWAY SA- © 2018 SDATAWAY SA All Rights Reserved Page 20 / 38 Revision 1 / April 2019
Micro SD card
The Micro SD card holder has been designed to host Micro SD card.
Description
Nom.
Card form factor
Micro-SD
Card type
SDHC
Memory size System capability
2Go to 16Go
Memory Card size
8 Go
File system
FAT32
Each Easy3-H is equipped with an 8 Go Card
memory size
This manual suits for next models
2
Table of contents
Popular Controllers manuals by other brands

Intermatic
Intermatic RC2000 Series Installation, operation & service manual

Sonus
Sonus 5100 Hardware installation guide

Technische Alternative
Technische Alternative UVR16x2***-D Programming guide

AGS
AGS Merlin 1000S Installation, operation and maintenance guide

Denon
Denon MC2000 Quick setup guide

JBL
JBL DSC260 owner's manual