Seav LR 2299 Series User manual

LRX 2299 / 2212 NEW
ELECTRONIC PANEL
Single-phase electronic control unit for the automation of swing
and sliding 230V gates with incorporated radio receiver and
Obstacle detection system.
- Mod. LG 2299 : Without radio receiver
- Mod. LRS 2299 : 433.92 Mhz
- Mod. LRS 2299 SET : 433.92 Mhz “narrow band”
- Mod. LRH 2299 : 868.3 Mhz “narrow band”
Single-phase electronic control unit for the automation of swing
and sliding 230V gates with incorporated radio receiver.
- Mod. LG 2212 New : Without radio receiver
- Mod. LRS 2212 New : 433,92 Mhz
- Mod. LRS 2212 New SET : 433,92 Mhz “narrow band”
- Mod. LRH 2212 New : 868,3 Mhz “narrow band”
IMPORTANT FOR THE USER
- The device can be used by children over 8 years of age
and persons with reduced physical or psychological
abilities or with little knowledge and experience only if
supervised or educated in its operation and safe use, in
order to also understand the dangers involved in its use.
- these instructions are also available at the website
www.seav.com
- Do not allow children to play with the device and keep
the remote controls out of their reach.
- Frequently examine the system to detect any signs of
damage. Do not use the device if it is in need of repair
work.
-Always remember to disconnect the power supply before
carrying out any cleaning or maintenance.
- Cleaning and maintenance must not be carried out by
unsupervised children
- ATTENTION: keep this instruction manual safe and
observe the important safety requirements contained
herein. Failure to comply with the requirements may
cause damage and serious accidents.
IMPORTANT FOR THE INSTALLER
Before automating the gate, check that it is in good
conditions, in compliance with the Machinery Directive
and with EN 12604.
Check that the location where the installation is
located enables compliance with operating temperature
limits specified for the device.
The safety of the final installation and compliance with
all prescribed Standards (EN 12453 - EN 12445) is the
responsibility of the person who assembles the various
parts to construct a total closing.
Once installation is finished, it is recommended that
all necessary checks be performed (appropriate
programming of the control panel and correct installation
of safety devices) to ensure that compliant installation
has been performed.
The control unit does not have any type of isolating
device for the 230 Vac line. It is therefore the
responsibility of the installer to set up an isolating device
inside the system. It is necessary to install an omnipolar
switch, surge category III. It must be positioned to
provide protection from accidental closing, pursuant to
point 5.2.9 of EN 12453.
For the power supply cables, use flexible cables in an
insulating sheath in harmonised polychloroprene
(H05RN-F) with a minimum conductor section of 1mm2
The various electrical components external to the
control unit must be cabled in accordance with standard
EN 60204-1 as amended, and as set forth in point 5.2.7
of EN 12453. Power cables may have a maximum
diameter of 14 mm. The fixing of power and connection
cables must be secured through the use of "optional"
cable glands supplied. Pay careful attention when
fastening the cables so that they are anchored in a stable
manner.
Furthermore, care is required when drilling holes in the
outside casing where connecting and power supply
cables will pass, and when assembling the cable glands,
so that everything is installed so as to maintain the
panel's IP protection characteristics.
The assembly of a push button panel for manual
control must be completed positioning the push button
panel in such a way that the user is not placed in a
dangerous position.
The rear part of the casing is equipped with
fittings for wall mounting (it is possible to drill holes for
installation with plugs, or there are already holes
available for installation with screws). Plan and
implement all necessary measures to achieve an
installation that does not alter the IP protection.
The gear motor used to move the gate must comply
with the requirements of point 5.2.7 of EN 12453.
The 24V Photocells Supply output must be dedicated
to the power supply of the photocells only. It cannot be
used for other applications.
With every operation cycle, the control unit performs
the photocell operating test, ensuring protection against
the rupture of Category 2 crush-proof devices, in
accordance with point 5.1.1.6. of EN 12453. Accordingly,
if the safety devices are not connected and/or are not
working, the control unit is not enabled for operation.
The safety function ensured by the control unit is
active only during closing, therefore, protection on
opening must be ensured in the installation phase with
measures (guards or safety distances) independent of
the control circuit.
For proper functioning of the radio receiver, if using
one or more control units, the installation at a minimum
distance of at least 3 metres one from the other is
recommended.
The full text regarding the EU Declaration of Conformity is
available from the following Internet address:
http://www.seav.it
GB

TECHNICAL DATA:
- Power supply 230 Vac 50-60Hz 2000W max.
- Flashing light output : 230 Vac 50Hz
100W Resistive Load max.
50W Inductive Load max.
- Motor outputs : 230 Vac 50/60 Hz. 750 W max.
- Electric lock output : 12 Vdc 15 W max.
- Indicator light output : 24 Vdc 4 W max.
- Power supply to photocells : 24 Vac 6 W max.
- Safety devices and controls in BT : 24 Vdc
- Operating temperature : -10 55 °C
- Radio receiver : see model
- Op. transmitters : 12-18 Bit or Rolling Code 64-80 bit
-TX max codes in memory : 150 (CODE or PED CODE)
- Board dimensions : 170x145x55 mm.
- Container dimensions : 240x185x110 mm.
- Protection rating : IP 65
TERMINAL BOARD CONNECTIONS:
CN1 :
1 : Grounding Connection.
2 : Grounding Connection.
3 : Grounding Connection.
CN2 :
1 : 230 Vac line input (Phase).
2 : 230 Vac line input (Neutral)
3 : 230 Vac Flashing light Output (Neutral).
4 : 230 Vac Flashing light Output (Phase).
5 : Motor 1 Output opening 230Vac.
6 : Motor 1 Output common 230Vac.
7 : Motor 1 Output closing 230Vac.
8 : Motor 2 Output opening 230Vac.
9 : Motor 2 Output common 230Vac.
10 : Motor 2 Output closing 230Vac.
CN3 :
1 : Electric lock output 12 Vdc 15 W ( +12V ).
2 : Common lock output – indicator light ( GND ).
3 : 24 Vdc 4 W Indicator light output ( + 24V ).
4 : Photocell control and power supply ( 24Vac 6W ).
5 : Photocell Control and power supply ( GND ).
6 : Open-close push button control PUL input (NA).
7 : Pedestrian push button control PUL PED input (NA).
8 : Common GND input.
9 : BL Blocking Device Input (NC).
10 : Safety device DS1 input (NC).
11 : Safety device DS2 input (NC).
12 : Common GND input.
13 : Motor 1 Opening Limit Switch Input (NC).
14 : Motor 1 Closing Limit Switch Input (NC).
15 : Motor 2 Opening Limit Switch Input (NC).
16 : Motor 2 Closing Limit Switch Input (NC).
17 : Antenna earth input.
18 : Antenna hot pole input.
OPERATING CHARACTERISTICS:
Automatic Operation:
By using both the radio control ( CODE LED on ) and the low
voltage push button panel ( PUL ) to activate the gate, the
following functioning is obtained:
the first impulse commands the opening mechanism until motor
time expires. The second impulse commands gate closing. If
an impulse is sent before the motor time has expired, the
control unit will reverse motion direction both for opening and
closing.
Step-by-step operation:
By using both the radio control ( CODE LED on ) and the low
voltage push button panel ( PUL ) to activate the gate, the
following functioning is obtained:
the first impulse commands the opening mechanism until the
motor time expires. The second impulse commands gate
closing. If an impulse is sent before the
motor time has expired, the control unit will stop the motion
during opening and closing phase. An additional control re-
starts motion in the opposite direction.
Automatic closing :
The control unit closes the gate automatically without sending
additional commands.
Selecting this operating mode is described under the
instructions for setting the pause time.
Pedestrian Passage:
The control unit allows only Motor 1 to be activated using either
the radio control ( CODE PED. LED on) or the push button
panel ( PED ), for the programmed time. ( T.MOT. PED. ).
Blocking Device Input :
The control unit allows the blocking button connection (NC).
Tripping during any operating phase of the control unit causes
movement to stop immediately. An additional movement control
will be valid as long as you have disabled the blocking input,
and, in any case, the unit will carry out the opening stage
automatism with pre-flashing for 5 seconds. If the automation is
fully open, in this case, it will carry out the closing phase.
Warning: Jumper this input if not used.
Safety device 1 :
The control unit allows Photocells to be powered and
connected in accordance with directive EN 12453.
If the device trips during opening, it is ignored. If it trips during
closing, gate motion is reversed.
The control unit compulsorily requires the use of photocells,
connected to dedicated inputs, otherwise the unit is not
enabled for operation.
Safety device 2:
The control unit allows Photocells to be powered and
connected in accordance with directive EN 12453.
If the device trips during opening, the gate stops momentarily.
Once freed, the control unit continues the opening phase. If the
device trips during closing, gate motion is reversed.
The control unit compulsorily requires the use of photocells,
connected to dedicated inputs, otherwise the unit is not
enabled for operation.
SENSOR 1 ( Operating logic RTX 2278 Sensor 1 ) :
The control unit enables connection of wireless safety devices
in accordance with Directive EN 12453.
The control unit is factory supplied with the following operating
logic installed for Sensor 1 operation: it is not considered if it is
triggered in the opening phase, whereas in the closing phase it
causes a change in direction, if, naturally, module RTX 2278 is
installed on the control unit.
The electronic control unit:
LG 2299 - LRS 2299 - LRS 2299 SET - LRH 2299
LG 2212 New - LRS 2212 New - LRS 2212 New SET
LRH 2212 New
they comply with the specifications of the Directives
RED 2014/53/EU, EMC 2014/30/EU, LVD 2014/35/EU.

SENSOR 2 ( Operating logic RTX 2278 Sensor 2 ) :
The control unit enables connection of wireless safety devices
in accordance with Directive EN 12453.
The control unit is factory supplied with the following operating
logic installed for Sensor 2 operation: when it is triggered, it
causes the gate to stop and change direction briefly in both
opening and closing phases, if, naturally, module RTX 2278 is
installed on the control unit.
Opening and Closing Limit Switch:
The control unit allows the Opening and Closing Limit Switch
connection (NC). When it is triggered during the respective
operating phases, movement stops immediately.
Warning: Leave these inputs free if not used.
Adjusting Power and Initial Surge:
The electronic control unit is equipped with a "POWER "
trimmer to adjust motor Power and Speed, fully managed by
the microprocessor. The adjustment can be made within a
range of 50% and 100% of the Maximum Power.
Nevertheless, every movement has an initial surge, powering
the motor for 2 seconds at the maximum power even if motor
power adjustment is enabled.
Warning: You will need to repeat the Motor Time
programming procedure if you wish to adjust the "POWER",
as operation and deceleration times may be affected.
Obstacle detection: ( Valid only for LRX 2299 )
The electronic control unit is equipped with a "SENSITIVITY"
trimmer to adjust the Counter Power required to detect the
obstacle, fully managed by the microprocessor.
The adjustment can be made by setting a time interval
between a minimum of 0.1 seconds and a maximum of 3
seconds.
Note: by setting the "SENSITIVITY" trimmer at the minimum,
the obstacle detection function is excluded.
Warning:
- During the slowed motion phase the obstacle detection
function is always disabled.
- The obstacle detection function always causes motion
reversal during the closing phase (except in the last 5
seconds of operation, in which case it stops) and reversal for
2 seconds during the opening phase (except in the last 5
seconds of operations, in which case it stops).
Deceleration:
The motor deceleration function is used on the gates to stop
them from reaching their final position at a high speed in the
opening and closing phases.
The control unit allows deceleration to be programmed for the
desired points (before the gates are completely open or closed)
during Motor Timer programming (see Main menu). It is also
possible to select the motor power to which the deceleration
phase between 6 different levels of power is carried out (see
Extended menu 3). The intermediate level is set during factory
configuration.
Warning light :
The control unit enables connection of a 24Vdc light to view the
status of automation. Light: off, automation closed; on, open;
slow flashing, opening motion; fast flashing, closing motion.
Flashing beacon function:
The electronic control unit is equipped with an output for the
management of the flashing beacon 230 Vac. Its function is
conditioned by motor motion and automatic closing which if
activated, enables the flashing beacon even during pause time.
Operation with TIMER:
The control unit can have a timer set up instead of an open-
close ( PUL ) control button.
Example: at 08:00 the timer closes the contact and the control
unit opens the gate. At 18:00 the timer opens the contact and
the control unit closes the gate. During the interval between
08:00 and 18:00, at the end of the opening phase, the control
unit disables the flashing beacon, automatic closing and radio
controls.
PROGRAMMING :
SEL key: selects the type of function to be stored, selection is
indicated by a flashing LED.
Repeatedly press the key to select the desired function. The
selection remains active for 10 seconds, (indicated by the
flashing LED); after 10 seconds, the control unit returns to its
original status.
SET key: this programs the information according to the type of
function previously selected with the SEL button. IMPORTANT:
The function of the SET key can be replaced with the radio
control, if programmed previously (CODE led on).
MAIN MENU
The control unit is supplied by the manufacturer with the
possibility of selecting a number of important functions.
---------------------- MAIN MENU -----------------
LED Reference LED off LED On
1) 1-2 MOTORS Automation 1 Motor Automation 2 Motors
2) AUT / S-S Automatic Step by Step
3) CODE No code Code entered
4) INB.CMD.AP Disabled Enabled
5) T. MOT. 30 sec. motor time Programmed time
6) T.MOT.PED. Mot. Time Ped. 10 sec. Programmed time
7) T. PAUSA No auto close With auto close
8) RIT. ANTE No gate delay. Programmed time
1) 1 – 2 MOTORS :
For ease of installation, the control unit has, by default, two
automations with 1 or 2 motors.
The control unit has, by default, typical operation of automation
with 1 motor (e.g. sliding gate). To enable, by default, operation
of an automation to 2 motors (e.g. gate with doors), proceed as
follows: press the SEL key until the 1-2 MOTORS LED flashes,
then press the SET button. At the same time, the 1-2
MOTORS LED remains steady and the procedure is
completed.
Repeat the procedure to restore the previous configuration.
With 1 Motor, if required, it is possible to have Motor 1 and 2
outputs in parallel to double the applicable load (one Motor up
to 1.5 HP).
2) AUTOMATIC / STEP BY STEP:
The default settings of the control unit have " Automatic "
operating logic enabled (AUT/S-S LED off), if you want to
enable the operating logic "Step by Step" (AUT/ S-S LED on), it
is necessary to enable it; use the SEL key to move to the
flashing AUT/S-S LED then press the SET key. AUT/S-S will
light up steadily. Repeat the procedure to restore the previous
configuration.
3) CODE: (Radio control code)
The control unit can store up to 150 radio controls with different
fixed or rolling codes.
Programming.
The transmission code is programmed in the following way:
using the SEL key to move to the flashing CODE LED, at the
same time send the pre-selected code from the radio control
you wish to use; when the CODE LED stays on steadily,
programming is finished. If all 150 available codes have been
memorised, by repeating the programming operation, all
programming LEDs will start to flash, indicating that it is not
possible to memorise any more codes.

PED/Single Door Radio Control code programming
If you want to program the Radio Control transmission code
referred to Pedestrian or Single Door operation, repeat the
above operation by pressing the SEL key twice (the CODE LED
flashes rapidly) instead of once. Repeat the operation to
restore the initial configuration.
Deletion.
All the stored codes are deleted as follows: press the SEL
button until the CODE LED** flashes, then press the SET
button and the CODE LED turns off and the codes are deleted.
4) INB. CMD. AP: (Command inhibition during opening and
pause time, if entered)
The command inhibition function during opening and pause
time, if entered, is used when automation includes a loop
detector. During the opening or pause phase the control unit
does not receive the commands sent by the loop detector with
every passage.
The default settings of the control unit have disabled command
inhibition during opening and pause time. If it is necessary to
enable it, do the following: use the SEL key to move to the
flashing INB.CMD.AP LED then press the SET key. The
INB.CMD.AP LED will light up steadily. Repeat the procedure to
restore the previous configuration.
5) T. MOT and DECELERATION: (Programming a motor operation
time of max 4 minutes)
The control unit is supplied by the manufacturer with a default
motor operation time of 30 seconds, without deceleration.
To modify the operation time of the motors, proceed as follows
when the gate is closed: use the SEL key to navigate to T.
MOT. when the respective LED is flashing , then press the SET
key briefly and Motor 1 will begin its opening cycle; when the
initial point of deceleration is reached press the SET key again:
the T. MOT. LED will start flashing more slowly and Motor 1 will
decelerate; when the desired position is reached, press the
SET key to complete the opening cycle. The T. MOT LED will
now start flashing normally again and Motor 2 will begin its
opening cycle: repeat the operations to program the work time
for Motor 2, After programming the opening times for the
motors, Motor 2 will start its closing cycle: repeat the same
instructions as above for programming the closing cycle of
Motor 2 and then for Motor 1. If you do not want the control unit
to decelerate, when the opening and closing phase is finished,
press the SET key twice during programming, instead of just
once.
During programming the radio control key of the control unit
can be used instead of the SET key, if stored previously.
6) T. MOT. PED: (Programming a pedestrian operating time of 4
minutes max.)
The control unit is factory supplied with a predefined
(Pedestrian) Motor 1 operating time of 10 sec. without
deceleration.
If it is necessary to modify the pedestrian operating time,
programming must be carried out when the gate is closed, as
follows: use the SEL key to move to the flashing T.MOT PED.
LED, then press the SET key briefly. Motor 1 will start the
opening cycle; in correspondence with the point desired to start
deceleration, press the SET key again: the T. MOT. PED. will
start flashing more slowly and Motor 1 will decelerate; when the
desired position is reached, press the SET key to complete the
opening cycle. At this point the T. MOT PED. LED will start
flashing at its standard pace again and the Motor 1 will begin
the closing phase; repeat the above operations for the closing
phase. If you do not want the control unit to decelerate, when
the opening and closing phase is finished, press the SET key
twice during programming, instead of just once.
During programming the radio control key of the control unit
can be used instead of the SET key, if stored previously.
7) T. PAUSA: (Automatic closing time programming max. 4 minutes)
The control unit is supplied by the manufacturer without
automatic closing. If you wish to enable automatic closing,
proceed as follows: using the SEL key to move to the flashing
T. PAUSA LED, press the SET key briefly, then wait for the
amount of time you wish to set for automatic closing; briefly
press the SET key again, and in that moment the automatic
closing time will be stored and the T. PAUSA LED will stay on
steady. If you wish to restore the initial condition ( without
automatic closing ), move to the flashing T. PAUSA LED, then
press the SET key twice within 2 seconds; the LED will shut off
and the operation will be complete.
During programming the radio control key of the control unit
can be used instead of the SET key, if stored previously.
8) T. RIT. ANTE : (Programming door delay of 15 sec. Max.)
The control unit is supplied by the manufacturer without gate
delay during opening and closing. If it is necessary to enter a
gate delay time, programming must be carried out when the
gate is closed, as follows: use the SEL key to move to the
flashing RIT. ANTE LED, press the SET key, wait for desired
interval of time, then press the SET key again: the gate delay
time opening will be stored, at 2 seconds, of the delay time of
the door closing for the time programmed and the RIT. ANTE
LED is steady.
To restore the initial configuration (without door delay), go to
the RIT. ANTE LED when flashing then press the SET key
twice within 2 seconds, the LED goes off and the operation is
completed.
EXTENDED MENU 1
The control unit is supplied by the manufacturer with the
possibility of selecting only the main menu functions.
To enable the functions listed in extended menu 1, proceed as
follows: press the SET button and hold for 5 seconds, after
which the T. PAUSA LED and RIT. ANTE LED will flash
alternately. You have 30 seconds to select the functions of
Extended Menu 1 using the SEL and SET buttons. After
another 30 seconds, the control unit returns to the main menu.
---------------------- EXTENDED MENU 1 ------------------
Reference LED LED Off LED On
A) 1-2 MOTORS remote PGM = OFF remote PGM = ON
B) AUT/S-S Test Photocell = ON Test Photocell= OFF
C) CODE Mant. Pressure = OFF Mant. Pressure = ON
D) INB.CMD.AP Water Hammer = OFF Water Hammer = ON
E) T. MOT.
Closing Hammer = OFF Closing Hammer = ON
F) T.MOT.PED. 4 x Limit switch 4 x Safety Devices
G) T. PAUSA Alternate ON/OFF flashing light
H) RIT. ANTE Flashing beacon ON/OFF in alternation
A) 1-2 MOTORS
( Remote programming of radio control ):
The control unit allows the transmission code to be
programmed, without using the SEL button directly on the
control unit, but remotely.
The remote transmission code can be programmed as follows:
continuously sending a previously-memorised radio control
code for more than 10 seconds. At this point the control unit
switches to programming mode, as described above for the
CODE LED in the main menu.
The control unit is supplied by the manufacturer with the
remote transmission code programming function disabled. If
you wish to enable the function, proceed as follows: check that
Extended Menu 1 is enabled (RIT. ANTE LED and T. PAUSA
LED start flashing alternately, ANTE Led), with the SEL key
position on the flashing of 1-2 motors Led then press the SET
key, the 1-2 MOTORS Led will simultaneously switch on
permanently and the programming is completed. Repeat the
procedure to restore the previous configuration.

B) AUT / S-S (Photocells Test):
The control unit is supplied by the manufacturer with photocell
Test programming enabled (in accordance with Standard EN
12453). If you wish to disable the function proceed as follows:
check that Extended Menu 1 is enabled (T. PAUSA and RIT.
ANTE LEDs flashing alternatively), with the SEL key positioned
on the flashing of AUT/ S-S LED then press the SET key, the
AUT/S-S LED will simultaneously stays on steadily and
programming is completed. Accordingly, the photocell test will
not be carried out, therefore even if not connected (if unused,
DS1 and DS2 inputs must be jumped), the control unit is
enabled for operation. Repeat the procedure to restore the
previous configuration.
C) CODE ( Hydraulic Motors Maintenance Pressure ) :
The control unit is supplied by the manufacturer with the
hydraulic motors maintenance pressure function disabled. If
you wish to enable the function, proceed as follows: make sure
that you have enabled Extended Menu 1 (T. PAUSA LED and
RIT. ANTE LED start flashing alternately), with the SEL key
position on the flashing of CODE LED then press the SET key,
the CODE LED will simultaneously stay on steady and
programming is completed. Accordingly the control unit will
send a closing command every 2 hours to the motor for 2
seconds. Repeat the procedure to restore the previous
configuration.
D) INB. CMD. AP. LED ( Water Hammer ) :
The control unit is supplied by the manufacturer with Water
Hammer disabled. If you wish to enable the Water Hammer
function, proceed as follows: check that Extended Menu 1 is
enabled (RIT. ANTE LED and T. PAUSA LED start flashing
alternately), with the SEL key position on the flashing of
INB.CMD.AP LED then press the SET key, the INB.CMD.AP
LED will simultaneously switch on permanently and
programming is completed. If you wish to enable the Water
Hammer function to the power set through the "POWER"
Trimmer, repeat the operation described above, pressing the
SEL button twice instead of once (making the INB.CMD.AP.
LED flash rapidly). Repeat the operation to restore the initial
configuration.
Accordingly, we can facilitate the release of the gate and
therefore allow the proper execution of the opening phase. In
fact, the control unit, before starting the opening phase sends a
closing command for 2 seconds with power relative to the
choice selected.
E) T. MOT. ( Closing Hammer ) :
The control unit is supplied by the manufacturer with the
Closing Hammer Function disabled. If you wish to enable the
Closing Hammer function, proceed as follows: make sure that
you have enabled Extended Menu 1 (RIT. ANTE LED and T.
PAUSA LED start flashing alternately), with the SEL key
position on the flashing of T.MOT. LED then press the SET key,
the T.MOT. LED will simultaneously switch on permanently and
programming is completed. If you wish to enable the Closing
Hammer function to the power set through the "POWER"
Trimmer, repeat the operation described above, pressing the
SEL button twice instead of once (making the T.MOT. LED
flash rapidly). Repeat the operation to restore the initial
configuration.
Accordingly the control unit, if functioning with Deceleration
during closing, will reach (after having completed the
deceleration closing phase) a time of 1 second with power
relative to the choice selected in order to overcome the gate
installed.
F) T. MOT. PED. LED ( 4x Limit switch / 4x Safety device ) :
The control unit is supplied by the manufacturer with the 4 x
Motor 1 and 2 inputs Limit switch enabled. If you wish to enable
the Safety Devices inputs function, proceed as follows: make
sure that you have enabled Extended Menu 1 (RIT. ANTE LED
and T. PAUSA LED start flashing alternately), by using the SEL
key select the flashing T. MOT. PED. LED and press the SET
button: T. MOT. PED. LED stays steadily lit and programming is
complete.
Repeat the operation to restore the initial configuration.
This way, the control unit changes operation of the 4 Limit
switch inputs in 4 Safety Devices inputs with the following
operation:
FC AP1 ( Safe opening ) :
If the device trips during closing, it is ignored. If it trips during
opening, it Stops + gate motion is reversed for 2 sec.
FC AP2 ( Safe opening ) :
If the device trips during closing, it is ignored. If it trips during
opening, it Stops + gate motion is reversed for 2 sec.
FC CH1 ( Safe closing ) :
If the device trips during opening and closing, it always Stops +
gate motion is reversed for 2 sec.
FC CH2 ( Safe opening and closing ) :
If the device trips during opening, it Stops + gate motion is
reversed for 2 sec. If it trips during closing, gate motion is
reversed.
Warning: Jumper if some of these inputs used as Safety
Devices are not used.
EXTENDED MENU 2
The control unit is supplied by the manufacturer with only the
option of directly selecting the functions listed in the main
menu.
To enable the functions listed in Extended Menu 2, proceed as
follows: open Extended Menu 1 (as instructed in the respective
section), then press and hold the SET key for 5 seconds, the T.
PAUSA LED and RIT. ANTE LED will flash simultaneously,
accordingly, you have 30 seconds to select the functions of
Extended Menu 2 using the SEL and SET buttons. After
another 30 seconds, the control unit returns to the main menu.
---------------------- EXTENDED MENU 2 -----------------
Reference LED LED Off LED On
A) 1-2 MOTORS Follow Me = OFF Follow Me = ON
B) AUT / S-S PreFlash. and Cort. L=OFF PreFlash. or Cort. L. =ON
C) CODE Pause Lamp. = OFF Pause Lamp. = ON
D) INB.CMD.AP SOFT START = OFF SOFT START = ON
E) T. MOT. El. Gate C
MD PED = OFF El. Gate CMD PED = ON
F) T.MOT.PED. PUL=PUL - PED=PED PUL=AP - PED=CH
G) T. PAUSA Flashing beacon ON/OFF simultaneous
H) RIT. ANTE Flashing beacon ON/OFF in simultaneous
A) 1-2 MOTORS ( Follow Me ) :
It is possible to set the "Follow Me" function on the control unit:
this function can only be programmed if a Pause Time has
already been programmed, and it is used to shorten the Pause
time to 5 sec after the photocell connected to DS1 disengages,
i.e. the gate closes 5 seconds after the user has passed
through. If you wish to enable the function, proceed as follows:
make sure that you have enabled Extended Menu 2 (T. PAUSA
LED and RIT. ANTE LED start flashing simultaneously), ANTE
CH Led), with the SEL key position on the flashing of 1-2
motors Led then press the SET key, the 1-2 MOTORS Led will
simultaneously switch on permanently and the programming is
completed. Repeat the procedure to restore the previous
configuration.

B) AUT / S-S ( Pre-flashing / Courtesy Light ) :
The control unit is supplied by the manufacturer with Pre-
flashing and Courtesy Light functions disabled. If you wish to
enable the Pre-flashing function, proceed as follows: make sure
that you have enabled Extended Menu 2 (T. PAUSA LED and
RIT. ANTE LED start flashing simultaneously), with the SEL key
positioned on the flashing of AUT/ S-S LED then press the SET
key, the AUT/S-S LED will simultaneously stays on steadily and
programming is completed. If you wish to enable the Courtesy
Light, repeat the operation described above, pressing the SEL
button twice instead of once (the AUT / S-S LED will flash
rapidly). Repeat the operation to restore the initial
configuration.
Pre-flashing** function The flashing beacon 230 Vac is
always activated 3 seconds before the automation starts any
type of motion.
Courtesy Light Function: The Flashing beacon 230 Vac
output will be activated for 3 minutes, each time that an
opening command is given.
C) CODE ( Flashing beacon function ) :
The control unit is supplied by the manufacturer with the
flashing beacon function during the Pause Time disabled. If you
wish to enable the function, proceed as follows: make sure that
you have enabled Extended Menu 2 (T. PAUSA LED and RIT.
ANTE LED start flashing simultaneously), with the SEL key
position on the flashing of CODE LED then press the SET key,
the CODE LED will simultaneously stay on steady and
programming is completed. Repeat the procedure to restore
the previous configuration.
D) INB. CMD. AP. LED ( SOFT START ) :
The control unit is supplied by the manufacturer with the Soft
Start function disabled. If you wish to enable the function,
proceed as follows: make sure that you have enabled Extended
Menu 2 (T. PAUSA LED and RIT. ANTE LED start flashing
simultaneously), with the SEL key position on the flashing of
INB.CMD.AP LED then press the SET key, the INB.CMD.AP
LED will simultaneously switch on permanently and
programming is completed. Accordingly, every time the gate
starts motion the control unit will control motor start-up,
increasing the power gradually from minimum to maximum in
the first two seconds of operation. Repeat the procedure to
restore the previous configuration.
E) T. MOT. (Electric Lock activation CMD PED.) :
The control unit is supplied by the manufacturer with the
activation of the electric lock through the disabled Pedestrian
command. If you wish to enable the function, proceed as
follows: make sure that you have enabled Extended Menu 2 (T.
PAUSA LED and RIT. ANTE LED start flashing
simultaneously), with the SEL key position on the flashing of
T.MOT. LED then press the SET key, the T.MOT. LED will
simultaneously switch on permanently and programming is
completed. The activation of the electric lock function through
the Pedestrian command, is used when you have, for example,
a sliding gate with a door next to the Pedestrian passage.
Accordingly, the gate can be opened with the PUL commands
as well as from the Pedestrian door using the electric lock with
the PED. commands for 2 seconds. Repeat the procedure to
restore the previous configuration.
F) T. MOT. PED. LED ( PUL and PED command functions )
:
The control unit is factory supplied with PUL control input
operation for the connection of a cyclical primary control button
(NA) and a PED input for the connection of a cyclical
Pedestrian command button (NA). If you wish to select another
mode of function of the PUL and PED inputs, proceed as
follows: make sure that you have enabled Extended Menu 2 (T.
PAUSA LED and RIT. ANTE LED start flashing
simultaneously), by using the SEL key select the flashing T.
MOT. PED. LED and press the SET button: T. MOT. PED. LED
stays steadily lit and programming is complete.
Accordingly, the PUL input makes it possible to connect a
button (NA) for the Opening phase only, and the PED input for
connection to a button (NA) for the Closing phase only. Repeat
the procedure to restore the previous configuration.
EXTENDED MENU 3
The control unit is supplied by the manufacturer with only the
option of directly selecting the functions listed in the main
menu.
To enable power programming functions for deceleration
carried out by the control unit, proceed as follows: open
Extended Menu 2 (as instructed in the respective section), then
press and hold the SET key for 5 seconds, after which the T.
PAUSA LED and RIT. ANTE LED will start flashing alternately
and then simultaneous, in this way there will be 30 seconds to
select the desired deceleration using the SEL and SET keys,
then, after a further 30 seconds, the control unit returns to the
main menu.
---------------------- EXTENDED MENU 3 -----------------
Level Leds On
1 1-2 MOTORS
2 1-2 MOTORS - AUT / S-S
3 1-2 MOTORS - AUT / S-S - CODE
4 1-2 MOTORS - AUT / S-S – CODE - INB. CMD. AP.
5 1-2 MOTORS - AUT / S-S – CODE - INB. CMD. AP - T. MOT.
6 1-2 MOTORS - AUT / S-S - CODE - INB. CMD. AP - MOT. T. - PED. MOT. T.
Programming Motor Power during Deceleration
The control unit allows you to programme the motor power to
which the deceleration phase will be carried out.
It is possible to choose between 6 different levels of power:
every combination of lit Leds corresponds to a level according
to the table above; in other words, starting from the lowest led
(1-2 MOTORS LED) and moving upwards, each Led
corresponds to a higher power level. Using the SEL key it is
possible to scroll through the different power levels; for every
selected power level, the highest respective LED will flash (for
example, if level 4 is selected the 1-2 MOTORS AUT/S-S and
CODE LEDs light up steady, whereas the INB CMD. AP LED
flashes); press SET to confirm.
Level 3 is selected in the default configuration.
RESET :
To reset the default configuration of the control unit, press the
SEL and SET buttons simultaneously; all RED signal Leds will
switch on and then immediately off again.
DIAGNOSTICS :
Photocell Test :
The control unit is designed for the connection of safety
devices that comply with point 5.1.1.6 of standard EN 12453.
With every operation cycle, it performs a test of the operating
photocells connected. If there is no connection and/or non
operation, the control unit does not enable gate motion, and will
visually report the failed test by simultaneously flashing all of
the LED signal lights flash. Once the photocells are running
correctly again, the control unit is ready for normal operation.
This ensures monitoring against failures, in compliance with EN
954-1, Category 2.

Control input test:
On each low voltage control input, the control unit uses a LED
signal to make the status readily known.
Operating logic: when a LED is on it means the input is closed,
when a LED is off it means the input is open.
MANAGING PROGRAMMING LEDS:
After 5 minutes of inactivity in the programming procedure, the
control unit will automatically switch off the programming LEDs
to save energy. The LEDs will light up, depending on the
previously set programs, only when the SEL or SET keys are
pressed or when a motion command has been received.
OPTIONAL MODULES:
The control unit can be fitted with Optional Modules to enable
additional functions. Several functions will be available based
on the type of optional module installed. Refer to the optional
module instruction manual for their technical features.

Rev.3.2 dated 09-01-2018

OPTIONAL MODULE RTX 2278 ( BASIC)
It is possible to select four different operating frequencies, all
within the 868 MHz band.
The selected operating frequency must be set in the same
manner on either the memorised RTX2278 (Base) or the RTX
2252 (Sensor) devices.
Use Dip Switch SW1 on both the RTX 2278 and RTX 2252
devices to make the selection.
SW1 SW1 SW1 SW1
FREQUENCY A FREQUENCY B FREQUENCY C FREQUENCY D
Technical Data
- Power supply: 5Vdc
- Max. consumption: 25 mA
- Operating frequency: 868 MHz FSK band
- RTX 2252 Sensors that can be stored: 2
- Operating temperature: -10°C ÷ 55°C
- Dimensions: 59x39 mm.
TERMINAL BOARD CONNECTIONS:
CN1 :
1 : Aerial hot pole input.
2 : Aerial earth input.
DESCRIPTION OF OPERATION
The RTX 2278 (Base) device controls one, or at most, two RTX
2252 (Sensor) devices, through radio-frequency, for the
connection of sensitive edges. It is possible to view two menus
with the RTX 2278 (Base) Device:
MONITOR MENU
PROGRAMMING MENU
With the MONITOR MENU and an acoustic signal (Buzzer), the
Device reports the following information:
ALARM SIGNAL:
Led on + Acoustic signal.
This lets you know which one of the memorised RTX 2252
devices the alarm refers to. A short Beep sounds every time a
reference Led lights up.
---------------------- MONITOR MENU -----------------
Led Reference Led Off Led On
1) SENSOR 1 CODE No Alarm SENSOR 1 Alarm
2) SENSOR 2 CODE No Alarm SENSOR 2 Alarm
LOW BATTERY SIGNAL:
Led On (brief flashes) + Acoustic signal.
This lets you know which one of the memorised RTX 2252
devices has low batteries. In addition to the acoustic signal
whenever a reference Led lights up, two brief Beeps also sound
every minute.
---------------------- MONITOR MENU -----------------
Led Reference Led Off Flashing Led
1) SENSOR 1 CODE Battery OK Battery LOW
2) SENSOR 2 CODE Battery OK Battery LOW
In terms of the PROGRAMMING MENU, on the other hand,
please refer to the paragraph on "Programming Keys and
Signal Leds".
Check the Preselected Operating Frequency
Before programming the transmission code for RTX 2252
(Sensor) Transceivers combined with a RTX 2278 (Base)
Transceiver, it is necessary to select one of the four available
frequencies (see the "Operating Frequency Selection"
paragraph). It is then advisable to make sure that the
preselected band is free (not already in use by another device).
To carry out this check, do the following: using the SET key,
move to the PROGRAMMING MENU; the Base scans the
preselected frequency and if it is already occupied by the Base
the MONITOR LED and PROGR. MENU LEDs will flash
alternately. In this case proceed to select a different frequency
(on both the Base and Sensor). If, on the other hand, the
selected frequency is free, proceed with programming the
Sensors associated with each channel, as described below.
Programming Keys and Signal Leds
SEL key: this selects the type of function to be memorised, the
selection is indicated by a flashing LED. Repeatedly press the
key to select the desired function. The selection will remain
active for 15 seconds indicated by a flashing LED, after which
time the device will return to its original state.
SET Key:
- this is used to choose between the Monitor Menu and the
Programming Menu: if the SEL and SET keys are not used, the
Monitor Menu will be automatically selected after 1 minute of
inactivity.
- this programs the function selected using the SEL key.
Signal Led
Led on: option memorised.
Led off: option not memorised.
Flashing led: selected option.
---------------------- PROGRAMMING MENU -----------------
Led Reference Led Off Led On
1) SENSOR 1 CODE No Pgm. code SENSOR 1 Pgm.
2) SENSOR 2 CODE No Pgm. code SENSOR 2 Pgm .
SENSOR 1 CODE ( Programming for transceiver RTX
2252 Sensor no. 1)
Programming for the transmission code of Transceiver RTX
2252 (Sensor) no. 1 combined with a RTX 2278 (Base)
Transceiver must be carried out as follows: press the SEL key,
the SENSOR 1 CODE LED will start flashing; in this phase the
Base communicates in broadcast mode with all installed
sensors, looking for one that can be memorised: press the SET
key for the Sensor you wish to memorise to send the
memorisation confirmation code ( the TX LED of the Sensor will
flash quickly 5 times); the SENSOR 1 CODE LED will stay on
steady and programming is finished. The Base device exits
programming if no confirmation code is received within 15
seconds.
Deletion: The memorised code can be deleted as follows:
press the SEL key, the SENSOR 1 CODE LED will start
flashing. Press the SET key, the SENSOR 1 CODE LED will
switch off, and the procedure is finished.

SENSOR 2 CODE ( Programming for transceiver RTX
2252 Sensor no. 2)
To programme the transmission code for RTX 2252 (Sensor)
Transceiver no. 2 combined with an RTX 2278 (Base)
Transceiver, proceed as described in point "2) SENSOR 1
CODE".
RESET
If the device must be reset to factory configuration, keep the
SEL and SET keys simultaneously pressed down for more than
2 seconds so that all signal LEDs briefly switch on at the same
time accompanied by three quick Buzzer Beeps.
RTX 2252 (Sensor)
Technical Data
- Battery power supply: 1.5Vdc Alkaline (LR20 Type
D)
- Operating frequency: 868 MHz FSK band
- System capacity in open field: 10÷20 m max.
- Operating temperature: -10÷55°C
- Dimensions: 120x80x50mm.
- Container: ABS UL94V-0 ( IP56 )
CN1 Terminal Board Connections
CN1:
1 : Safety Device Input (NC) or 8K2
2 : Safety Device Input (NC) or 8K2.
3 : Inhibitor Input (NC).
4 : Inhibitor Input (NC).
Description of Operation
The RTX 2252 (Sensor) device allows NC (normally closed
contact) standard type or 8K2 resistance type sensitive edges
to be connected, normally installed on the mobile part of the
gate.
It only works in combination with the control Base. The device
is battery-operated so as to exclude any type of cable
connection.
Once it is memorised (see "RTX 2278 - Programming Keys and
Signal Leds" paragraph) it can send the following information to
the RTX 2278 (Base) device:
- Survival signal:
this is used to periodically check the correct radio connection
between the devices.
- Alarm signal:
this is used to inform the base that the safety device is
operating.
- Low battery signal:
this is used to inform the system of the battery level.
ATTENTION! If the RTX 2252 Device (Sensor) is dismantled
from an installation, it is advisable to take the batteries out so
that the Sensor no longer continues unnecessary transmission.
NC or 8K2 Operating Mode Selection
The RTX 2252 Device allows NC (normally closed contact)
standard type or 8K2 resistance type sensitive edges to be
connected. Use Dip Switch SW2 No. 1 to make the selection:
DIP 1 = OFF NC input operation (default).
DIP 1 = ON 8K2 input operation.
SW2 SW2
NC 8K2
Transmission Mode Selection
With the RTX 2252 (Sensor) Transceiver device it is possible to
select two different operating modes, "Normal" or "Low Power".
The difference in operation consists in the Sensor transmitting
power. In "Low Power" operating mode the transmitting power
of the Sensor is considerably lower; in terms of energy savings,
which translates into longer battery life, it is necessary,
however, to take into account the subsequent reduction in radio
capacity for installation.
Use Dip Switch SW2 No. 2 to make the selection:
DIP 2 = OFF : "Low Power" operating mode disabled (default).
DIP 2 = ON : "Low Power" operating mode enabled.
SW2 SW2
LP=OFF LP=ON
Inhibitor Input Operating Mode
With the RTX 2252 (Sensor) Device it is possible to connect an
(NC) contact to temporarily inhibit the sensitive edge installed
on it.
ATTENTION! When not in use, the inhibitor input must always
be jumpered.
Low Battery Signal
Discharged battery levels are reported by the TX LED flashing
quickly on the RTX 2252 (Sensor) Device. The same
information is also sent to RTX 2278 (Base) device, that reports
the event with visual and acoustic warnings.
ATTENTION! We recommend replacing the device batteries as
soon as the TX LED starts flashing.
ATTENTION
- For best performance, change the 1.5V alkaline batteries
annually.
- To change the batteries, open the Sensor container with a
screwdriver.
- Dispose of the used batteries in appropriate waste containers.
This manual suits for next models
9
Table of contents
Other Seav Control Panel manuals