SonaSwitch
®
General
This operation and installation manual provides
general guidelines and suggestions to assist
you in using the SensComp, Inc. SonaSwitch®
MINI-S ultra-sonic sensor module in many
measurement applications.
General Installation Procedures
1. Always mount the SonaSwitch® MINI-S in a
suitable dry location. The SonaSwitch®
MINI-S is designed to be used in an indoor
or protected environment only. The
SonaSwitch® MINI-S E is suitable for
harsher environments and higher humidity
conditions. Excessive moisture on the
sensor will result in damage and improper
operation, and will void all warranties.
2. Mount the SonaSwitch® MINI-S as far off
the ground as practical.
3. Mount the SonaSwitch® MINI-S in a location
where environmental interference sources
are minimized (examples are EMI sources,
air nozzles, excessive air turbulence, etc.).
4. Mount the SonaSwitch® MINI-S in a 1.575
inch diameter hole, using RTV silicone or
edge clips to secure the sensor in place.
You can also use our enclosure PID#
619395, to house the SonaSwitch® MINI-S
5. As supplied, the SonaSwitch® MINI-S
should not need any adjustment as it has
been calibrated at the factory.
6. The two (2) NPN open collector digital out-
puts need to be “pulled up” (through a resis-
tance and/or impedance) to an external
positive power source of less than 40 VDC.
(Typically 4700 ohms when connected to an
external +5 VDC power source for testing or
for interfacing to TTL Logic level circuits).
The maximum output current is 600 mA.
The Range Set LEDs do not require pull-up
resistors, and can be used for setup
calibration before connecting the
SonaSwitch® MINI-S to external equipment.
System Wiring Information
Pin 1 – Power Supply – A +8 to +24 VDC
regulated power source supplying 30 mA of
current (2.0 Amperes during the 0.5 ms
transmit pulse).
Pin 2 – Power Supply Common (Ground) –
Common Return for DC power supply,
switched outputs, and clock signals.
Pin 3 – External Trigger – Accepts TTL com-
patible logic level clock signals. A low to
high (zero to +5 VDC) transition triggers
the SonaSwitch® MINI-S
Pin 4 – Trigger Enable – Allows the
SonaSwitch® MINI-S to accept an external
trigger signal. Enabled by connecting this
pin (pin 4) to common (pin 2).
Pin 5 – ECHO (PWM) Output – Delivers a TTL
compatible Pulse Width Modulated (PWM)
clock signal. This signal goes high at the
start of a cycle, and returns to a low state
when the returning echo is received.
Pin 6 – NPN Output 1 – This NPN open collector
output turns on and off when a target is
detected (on) or missing (off) as set by the
Range Set 1 push button.
Pin 7 – NPN Output 2 – This NPN open collector
output turns on and off when a target is
detected (on) or missing (off) as set by the
Range Set 2 push button.
Calibration Procedures
1. Apply DC power ( +8 to +24 VDC) to the
SonaSwitch® MINI-S (connector header
pins 1 and 2)
2. Allow five to ten minutes warm-up time for
the SonaSwitch® MINI-S to reach
operating temperature before calibrating
the unit.
3. If desired for testing, connect the two
NPN Open Collector Outputs to an
external positive power supply through
appropriate impedances. Since they are
open collector, they will always read zero
volts until connected to a pull-up load
(See General Installation Procedures –
Step 6).
4. NPN Output 1 Adjustment (pin 6)
Place the target at the desired
detection distance from the face of
the SonaSwitch® MINI-S.
Depress and hold the “Range Set 1”
push button switch. Wait for the
“Range Window” LED to flash three
times, followed by a “chirp” sound
from the sensor before releasing.
The NPN output 1 should now be set:
oLED 1 ON – NPN output is a
Logic Low (0 VDC) when target
is detected.
oLED 1 OFF – NPN output is a
SonaSwitch®
Logic High (+ power source) when
target is not detected.
5. NPN Output 2 Adjustment (pin 7)
Place the target at the desired
detection distance from the face of
the SonaSwitch® MINI-S
Depress and hold the “Range Set 2”
push button switch. Wait for the
“Range Window” LED to flash three
times, followed by a “chirp” sound
from the sensor before releasing.
The NPN output 2 should now be set:
oLED 2 ON – NPN output is a
Logic Low (0 VDC) when target
is detected.
oLED 2 OFF – NPN output is a
Logic High (+ power source)
when target is not detected.
6. Gain Adjustment
Note: The “Gain” adjust potentiometer
has been pre-set at the factory to
provide the best performance for the
range of your SonaSwitch® MINI-S. In
the event that it is changed, the steps
below will assist you in returning it to
the proper value.
To calibrate the “Gain” place the
target at the maximum desired
detection distance.
Rotate the “Gain” adjust
potentiometer fully counterclockwise
(CCW).
Slowly rotate “Gain” adjust
clockwise (CW) until detection
occurs.
Rotate “Gain” adjust clockwise (CW)
an additional 1/16 turn.
Note: Always calibrate the GAIN
control for minimum gain required
for reliable detection. Excessive
gain may result in false target
detection.
Range Window LED
The Range Window LED performs two indication
functions:
During Setup procedures, the LED will flash
as the set-up values are programmed into
the sensor.
During normal operation, the LED will
illuminate (ON) when a target is detected
between the two set points, and is off for
targets outside this region.
SonaSwitch® MINI-S
SonaSwitch® MINI-SE
Push Button Settable
Ultrasonic
Sensor
Installation and
Operation
Manual
SensComp, Inc.
36704 Commerce Road
Livonia, MI 48150
Phone: 734-953-4783
Fax: 734-953-4518
www.senscomp.com
Copyright © 2004 SensComp, Inc. 15July2016

This manual suits for next models

1

Other SensComp Accessories manuals

SensComp SonaSwitch MINI-A User manual

SensComp

SensComp SonaSwitch MINI-A User manual

SensComp SonaSwitch 1650S Series Specification sheet

SensComp

SensComp SonaSwitch 1650S Series Specification sheet

SensComp 600 Series User manual

SensComp

SensComp 600 Series User manual

SensComp MINI-S User manual

SensComp

SensComp MINI-S User manual

SensComp Cricket-S User manual

SensComp

SensComp Cricket-S User manual

SensComp Cricket-A User manual

SensComp

SensComp Cricket-A User manual

Popular Accessories manuals by other brands

Pil Sensoren P41-200-I-CM12 quick start guide

Pil Sensoren

Pil Sensoren P41-200-I-CM12 quick start guide

netvox R718PA22 user manual

netvox

netvox R718PA22 user manual

Anton Paar ADU 5 Product information

Anton Paar

Anton Paar ADU 5 Product information

Viking LSD-2 product manual

Viking

Viking LSD-2 product manual

Bogen LMR1S user guide

Bogen

Bogen LMR1S user guide

DAMM BS422 Installation and setup

DAMM

DAMM BS422 Installation and setup

Serioux SRX-560P instruction manual

Serioux

Serioux SRX-560P instruction manual

Blyss 21217KF Safety guide

Blyss

Blyss 21217KF Safety guide

Razor Jetts Mini instruction manual

Razor

Razor Jetts Mini instruction manual

Mirabella International 43061068 quick start guide

Mirabella International

Mirabella International 43061068 quick start guide

LSI LASTEM DNA310.1 user manual

LSI LASTEM

LSI LASTEM DNA310.1 user manual

Zinc ZN25152 User instructions

Zinc

Zinc ZN25152 User instructions

Graef CC120 operating instructions

Graef

Graef CC120 operating instructions

Mesalabs Smart-Well 1710 Operation manual

Mesalabs

Mesalabs Smart-Well 1710 Operation manual

Wenglor LN Series operating instructions

Wenglor

Wenglor LN Series operating instructions

PEWA Steinel SN-617011 operating instructions

PEWA

PEWA Steinel SN-617011 operating instructions

Continuum Cobra S owner's manual

Continuum

Continuum Cobra S owner's manual

Satel AGD-200 quick start guide

Satel

Satel AGD-200 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.