
Ratio Conditions and Actions
Evaluating any necessary actions can be completed once the ratios for the
connector are calculated. The following table shows the suggested action based on
maintaining the present load rating of the asset.
Resistance Ratio Condition of fitting Action
0.3 to 1.0 Normal Connection: Serviceable
New connections are expected to be in
the 0.3 to 0.8 range
None
1.01 to 1.2 Serviceable; Poor
Shows deterioration; Overloads &
faults may deteriorate the connection
Re-inspect in one
year, or after next
fault
1.21 to 1.5 Serviceable; Poor
Shows deterioration; Overloads &
faults may deteriorate the connection
Re-inspect in six
months, or after
next fault
1.51 to 2.0 Serviceable; Very poor
High loads, overloads, or faults may
deteriorate the connection
Schedule asset
replacement in less
than three months
2.01 to 3.0 Bad; deterioration rate is
increasing
High loads, overloads, or faults may
fail the connection. High tensions from
cold weather or wind may initiate
failure under normal loading
Schedule asset
replacement very
soon
>3.0 Failing
Normal loads, overloads, or faults may
fail the connection; High tensions from
cold weather or wind are likely to
initiate failure under normal loading
Replace as soon as
possible
*Actions required based on resistance ratios (Rfitting / Rconductor)
*These ratio conditions and actions are developed from field measurements, manufacturer
data, lab tests, failure analysis and understanding of deterioration mechanisms. This
guideline may be modified as field and test data accumulates.
Calculating the Resistance of Power Tap
Connectors:
The Ohmstik will take resistance on other Full and Limited tension connectors.
It is always best practice to take all three readings of the series and evaluate the
condition with the above table. However, due to the build and size, it may not be
possible to take all three readings in series. If evaluating based on a benchmark
measurements, or comparison to a known good fitting, a reading across the
connector can be made.
Factors effecting the reading may include line tension and wire condition (heavily
birdcaged or other).
Page 9