
EN
Instructions for installation and use p. 11/38
3.5. Sensor operating modes
The sauna control unit can be operated with one or two sensors. A temperature
sensor (bench sensor, F2) or a humidity/temperature sensor (FTS2, PRO B3
only) can be used as the second sensor.
Single sensor mode (F1)
Single-sensor mode must be activated using the function selection switch (see
8.5. Activating/deactivating the single-sensor mode on page 25).
In single-sensor mode, the sauna control unit is operated with the heater sensor
with overheat cut-out (F1) only. This is included in the scope of delivery.
In single-sensor mode, the sauna control unit only displays the set temperature as
standard. The actual temperature is not displayed. If the sauna control unit is to
display the temperature above the heater (F1 sensor) as the actual temperature
in single-sensor mode, this must be activated during commissioning (see page
8.7. Displaying the heater temperature in single-sensor mode on page 26).
PRO B3 only: The maximum humidity level which can be set is based on the
temperature above the heater, and the humidity is timed. Only the set value for
the humidity level (in % of relative humidity) is displayed by the sauna control unit.
The actual humidity in the sauna cabin when the humidity is timed depends on
Two-sensor mode with bench sensor (F2)
Two-sensor mode is the factory setting.
In two-sensor mode with bench sensor, a second temperature sensor (bench
sensor) is installed above the rear sauna bench. The sauna control unit displays
the temperature measured by the bench sensor as the actual temperature.
PRO B3 only: In two-sensor mode with bench sensor, the humidity is timed.
Only the preset value for the humidity (in % relative humidity) is shown on the
display of the sauna control unit. The actual humidity in the sauna cabin when
the humidity is timed depends on the size of the cabin and the vaporizer output,