  9. Server Technology CDUCW-16V-MX User manual

Server Technology CDUCW-16V-MX User manual

Model Available Input
Voltages Outlets
Available Input
Cord
Amperage Dimensions
(L x W x D)
© Server Technology, Inc. 01/26/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc.
Protected by one or more of the following patents: Patent # 7,043,543. Patent Pending. Printed in US.
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-16V (20-Amp)
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management
with power distribution and power and environmental monitoring.
Reboot a single or dual-power server with one command. Receive
SNMP-based alerts and email alerts when power or environmental
conditions exceed thresholds. Assign users specific access rights to
designated outlets or groups.
Only the Switched CDU products provide the flexibility needed for all
data centers and remote sites, including power requirements for
high-amp, high voltage; UL 60950-1 (branch circuit protection not
required for 20A rated devices); SSL & SSH security; and SNMP-based
input current monitoring.
The Switched CDU also supports Enterprise View PDU Manager.
This gives the engineer the ability to manage a large installation of
Networked CDUs from one location, view and access up to 1,000
Switched CDUs from a single web interface.
> Remote Power Management:
Power cycle individual power
outlets, or groups of power
outlets, to remotely reboot
servers and network devices,
anywhere in the world. Or,
power-off unused power
receptacles
> High Power Distribution: 120V,
208V, or 230V power; 20-Amp
power input feed option
> High Density: Single power
input feed; 16 outlets per
enclosure
> IP Access & Security: Web
interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS and RS-232 access
> Add an Expansion Module:
Daisy chain the Switched CDU
Expansion Module (CW/CX) for
power management of separate
power circuits from a single IP
address
> Environmental Monitoring:
Each Switched CDU supports two
temperature & humidity probes
and reports conditions thru the
Web interface
> Enterprise View: View and
access up to 1,000 Switched
CDUs from one Web interface**
> SNMP Traps: Provide automated
alerts for power and
environmental conditions
> Input Current Monitor:
Precisely measure the aggregate
current draw (in amps) on each
power circuit. On-site
verification of the input current
with the LED digital display.
Remote verification via browser
or serial screen.
> Power-up Sequencing: Prevent
an in-rush power overload
Input Current Monitoring
The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.
Temperature and Humidity
The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.
Additional Benefits:
CW-16V1-C20MX
CW-16V2-C20MX
100-120V
50/60Hz
208-240V
50/60Hz 20A
20A IEC 60320/C20
Power Inlet
IEC 60320/C20
Power Inlet
(16) NEMA 5-20R
(16) IEC 60320/C13
39.5” x 1.75” x 2.25”
39.5” x 1.75” x 2.25”
Additional Features and Specifications
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and
CAN/CSA 22.2 No. 60950-1-03
> European Union (TUVGS mark) to EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
EMTH-1-1 Temperature & Humidity Probe, 10’
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2 IEC 60320/C19 - Schuko 10’
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)
16/20A Blue (UK Commando) 10’
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’
> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’
> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’
> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’
> PT-ADP-C19 Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module
Model Numbers
> CX-16V1-C20MX
> CX-16V2-C20MX
> CX-16VE-C20MX
CW-16VE-C20MX 230V
50/60Hz 16A IEC 60320/C20
Power Inlet (16) IEC 60320/C13 39.5” x 1.75” x 2.25”
NORTH AMERICA / ASIA
Server Technology, Inc.
1040 Sandhill Drive
Reno, NV 89521
United States
1.775.284.2000 Tel
1.775.284.2065 Fax
[email protected]m
www.servertech.com
www.servertechblog.com
EMEA
Server Technology Intl
Sienna Court
The Broadway
Maidenhead
Berkshire
SL6 1NJ
United Kingdom
+44 (0) 1628 509053 Tel
+44 (0) 1628 509100 Fax
[email protected]m
Branch Circuit Protection (not required)
> Compliant to UL 60950-1
Model Available Input
Voltages Outlets
Available Input
Cord
Amperage Dimensions
(L x W x D)
© Server Technology, Inc. 01/26/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc.
Protected by one or more of the following patents: Patent # 7,043,543. Patent Pending. Printed in US.
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-16V (20-Amp)
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management
with power distribution and power and environmental monitoring.
Reboot a single or dual-power server with one command. Receive
SNMP-based alerts and email alerts when power or environmental
conditions exceed thresholds. Assign users specific access rights to
designated outlets or groups.
Only the Switched CDU products provide the flexibility needed for all
data centers and remote sites, including power requirements for
high-amp, high voltage; UL 60950-1 (branch circuit protection not
required for 20A rated devices); SSL & SSH security; and SNMP-based
input current monitoring.
The Switched CDU also supports Enterprise View PDU Manager.
This gives the engineer the ability to manage a large installation of
Networked CDUs from one location, view and access up to 1,000
Switched CDUs from a single web interface.
> Remote Power Management:
Power cycle individual power
outlets, or groups of power
outlets, to remotely reboot
servers and network devices,
anywhere in the world. Or,
power-off unused power
receptacles
> High Power Distribution: 120V,
208V, or 230V power; 20-Amp
power input feed option
> High Density: Single power
input feed; 16 outlets per
enclosure
> IP Access & Security: Web
interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS and RS-232 access
> Add an Expansion Module:
Daisy chain the Switched CDU
Expansion Module (CW/CX) for
power management of separate
power circuits from a single IP
address
> Environmental Monitoring:
Each Switched CDU supports two
temperature & humidity probes
and reports conditions thru the
Web interface
> Enterprise View: View and
access up to 1,000 Switched
CDUs from one Web interface**
> SNMP Traps: Provide automated
alerts for power and
environmental conditions
> Input Current Monitor:
Precisely measure the aggregate
current draw (in amps) on each
power circuit. On-site
verification of the input current
with the LED digital display.
Remote verification via browser
or serial screen.
> Power-up Sequencing: Prevent
an in-rush power overload
Input Current Monitoring
The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.
Temperature and Humidity
The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.
Additional Benefits:
CW-16V1-C20MX
CW-16V2-C20MX
100-120V
50/60Hz
208-240V
50/60Hz 20A
20A IEC 60320/C20
Power Inlet
IEC 60320/C20
Power Inlet
(16) NEMA 5-20R
(16) IEC 60320/C13
39.5” x 1.75” x 2.25”
39.5” x 1.75” x 2.25”
Additional Features and Specifications
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and
CAN/CSA 22.2 No. 60950-1-03
> European Union (TUVGS mark) to EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
EMTH-1-1 Temperature & Humidity Probe, 10’
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2 IEC 60320/C19 - Schuko 10’
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)
16/20A Blue (UK Commando) 10’
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’
> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’
> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’
> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’
> PT-ADP-C19 Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module
Model Numbers
> CX-16V1-C20MX
> CX-16V2-C20MX
> CX-16VE-C20MX
CW-16VE-C20MX 230V
50/60Hz 16A IEC 60320/C20
Power Inlet (16) IEC 60320/C13 39.5” x 1.75” x 2.25”
NORTH AMERICA / ASIA
Server Technology, Inc.
1040 Sandhill Drive
Reno, NV 89521
United States
1.775.284.2000 Tel
1.775.284.2065 Fax
[email protected]
www.servertech.com
www.servertechblog.com
EMEA
Server Technology Intl
Sienna Court
The Broadway
Maidenhead
Berkshire
SL6 1NJ
United Kingdom
+44 (0) 1628 509053 Tel
+44 (0) 1628 509100 Fax
[email protected]
Branch Circuit Protection (not required)
> Compliant to UL 60950-1

This manual suits for next models

3

Other Server Technology Power Distribution Unit manuals

Server Technology CDUCW-24V4 User manual

Server Technology

Server Technology CDUCW-24V4 User manual

Server Technology 4805-XLS-16B User manual

Server Technology

Server Technology 4805-XLS-16B User manual

Server Technology switched pro2 User manual

Server Technology

Server Technology switched pro2 User manual

Server Technology Sentry CB-12H Series User manual

Server Technology

Server Technology Sentry CB-12H Series User manual

Server Technology Switched Rack PDU User manual

Server Technology

Server Technology Switched Rack PDU User manual

Server Technology switched pro2 User manual

Server Technology

Server Technology switched pro2 User manual

Server Technology CW-8H User manual

Server Technology

Server Technology CW-8H User manual

Server Technology Sentry PT22 Installation guide

Server Technology

Server Technology Sentry PT22 Installation guide

Server Technology CW-16V User manual

Server Technology

Server Technology CW-16V User manual

Popular Power Distribution Unit manuals by other brands

Keysight Technologies 85039B LO User's and service guide

Keysight Technologies

Keysight Technologies 85039B LO User's and service guide

GE L90 instruction manual

GE

GE L90 instruction manual

Häfele LOOX5 P-01478623 quick start guide

Häfele

Häfele LOOX5 P-01478623 quick start guide

CEP 6502GU Installation and operating instructions

CEP

CEP 6502GU Installation and operating instructions

LEGRAND RARITAN PXE Quick setup guide

LEGRAND

LEGRAND RARITAN PXE Quick setup guide

turck IM33-FSD-EX/L quick start guide

turck

turck IM33-FSD-EX/L quick start guide

Spectrum Brands 72A-190BQREM Series Installation and operation manual

Spectrum Brands

Spectrum Brands 72A-190BQREM Series Installation and operation manual

Art PB 4X4 Specification sheet

Art

Art PB 4X4 Specification sheet

CYP CSR-8PSU-5V Operation manual

CYP

CYP CSR-8PSU-5V Operation manual

ABB 83325/2-500 manual

ABB

ABB 83325/2-500 manual

Middle Atlantic Products PD-DC-125R instruction sheet

Middle Atlantic Products

Middle Atlantic Products PD-DC-125R instruction sheet

Penn Elcom PDU16-6UK user guide

Penn Elcom

Penn Elcom PDU16-6UK user guide

Eaton xComfort CBEU-02/01 Assembly instructions

Eaton

Eaton xComfort CBEU-02/01 Assembly instructions

Intellitec POWER LINE 2004 EMS Installation and service manual

Intellitec

Intellitec POWER LINE 2004 EMS Installation and service manual

Intellinet 164603 Quick instruction guide

Intellinet

Intellinet 164603 Quick instruction guide

Siemens SIPROTEC 7ST6 manual

Siemens

Siemens SIPROTEC 7ST6 manual

Toshiba REMOTE-D Brochure & specs

Toshiba

Toshiba REMOTE-D Brochure & specs

Vimar ELVOX 46264.002 quick start guide

Vimar

Vimar ELVOX 46264.002 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.