  9. Server Technology CW-8H User manual

Server Technology CW-8H User manual

Model Available Input
Voltages Outlets
Available Input
Cord
Amperage Dimensions*
(L x W x D)
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-8H
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management with power
distribution and power and environmental monitoring. Reboot a single or
dual-power server with one command. Receive SNMP-based alerts and email alerts
when power or environmental conditions exceed thresholds. Assign users specific
access rights to designated outlets or groups.
Only the Switched CDU products provide the flexibility needed for all data centers
and remote sites, including power requirements for high-amp, high voltage; UL
60950-1 branch circuit protection; SSL & SSH security; and SNMP-based input current
monitoring.
> Remote Power Management:
Power cycle individual power
outlets, or groups of power
outlets, to remotely reboot
servers and network devices,
anywhere in the world. Or,
power-off unused power
receptacles
> High Power Distribution: 120V,
208V, or 230V power; 20 or
30-Amp power input feed
options
> High Density: Single power
input feed; 8 outlets per 1U
enclosure
> IP Access & Security: Web
interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS and RS-232 access
> Add an Expansion Module:
Daisy chain the Switched CDU
Expansion Module (CW/CX) for
power management of separate
power circuits from a single IP
address
> Environmental Monitoring:
Each Switched CDU supports two
temperature & humidity probes
and reports conditions thru the
Web interface
> SNMP Traps: Provide automated
alerts for power and
environmental conditions
> Input Current Monitor:
Precisely measure the aggregate
current draw (in amps) on each
power circuit. On-site
verification of the input current
with the LED digital display.
Remote verification via browser
or serial screen.
> Power-up Sequencing: Prevent
an in-rush power overload
Branch Circuit Protection
The Sentry CDU Family meets the new UL 60950-1
requirement for branch circuit protection.
Attention! The Sentry CDU products meet the above criteria by
providing overcurrent protection with UL-listed Bussman SC fuses for
each branch circuit. The CW-8H contains fuses within the enclosure.
Input Current Monitoring
The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.
Temperature and Humidity
The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.
Additional Benefits:
CW-8H1-C20
CW-8H2-C20
CW-8H1-L530
CW-8H2-L630
100-120V
50/60Hz
100-120V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz 30A
20A
30A
20A IEC 60320/C20
Power Inlet
NEMA L5-30P
Cordset
IEC 60320/C20
Power Inlet
NEMA L6-30P
Cordset
(8) NEMA 5-20R
(8) IEC 60320/C13
(8) NEMA 5-20R
(8) IEC 60320/C13
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
Additional Features and Specifications
Branch Circuit Protection
> Compliant to UL 60950-1
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and
CAN/CSA 22.2 No. 60950-1-03
> European Union (TUVGS mark) to EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3
> LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
EMTH-1-1 Temperature & Humidity Probe, 10’
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2 IEC 60320/C19 - Schuko 10’
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)
16/20A Blue (UK Commando) 10’
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’
> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’
> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’
> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’
> PT-ADP-C19 Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module
Model Numbers
> CX-8H1-C20
> CX-8H1-L530
> CX-8H2-C20
> CX-8H2-L630
> CX-8HE-C20
CW-8HE-C20* 230V
50/60Hz 16A IEC 60320/C20
Power Inlet (8) IEC 60320/C13 17.0” x 1.75” x 7.0”
*European Model
© Server Technology, Inc. 7/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.
Model Available Input
Voltages Outlets
Available Input
Cord
Amperage Dimensions*
(L x W x D)
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-8H
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management with power
distribution and power and environmental monitoring. Reboot a single or
dual-power server with one command. Receive SNMP-based alerts and email alerts
when power or environmental conditions exceed thresholds. Assign users specific
access rights to designated outlets or groups.
Only the Switched CDU products provide the flexibility needed for all data centers
and remote sites, including power requirements for high-amp, high voltage; UL
60950-1 branch circuit protection; SSL & SSH security; and SNMP-based input current
monitoring.
> Remote Power Management:
Power cycle individual power
outlets, or groups of power
outlets, to remotely reboot
servers and network devices,
anywhere in the world. Or,
power-off unused power
receptacles
> High Power Distribution: 120V,
208V, or 230V power; 20 or
30-Amp power input feed
options
> High Density: Single power
input feed; 8 outlets per 1U
enclosure
> IP Access & Security: Web
interface, SSL, SSH, Telnet, SNMP,
FTP, SNTP, Syslog, LDAP, LDAPS,
TACACS and RS-232 access
> Add an Expansion Module:
Daisy chain the Switched CDU
Expansion Module (CW/CX) for
power management of separate
power circuits from a single IP
address
> Environmental Monitoring:
Each Switched CDU supports two
temperature & humidity probes
and reports conditions thru the
Web interface
> SNMP Traps: Provide automated
alerts for power and
environmental conditions
> Input Current Monitor:
Precisely measure the aggregate
current draw (in amps) on each
power circuit. On-site
verification of the input current
with the LED digital display.
Remote verification via browser
or serial screen.
> Power-up Sequencing: Prevent
an in-rush power overload
Branch Circuit Protection
The Sentry CDU Family meets the new UL 60950-1
requirement for branch circuit protection.
Attention! The Sentry CDU products meet the above criteria by
providing overcurrent protection with UL-listed Bussman SC fuses for
each branch circuit. The CW-8H contains fuses within the enclosure.
Input Current Monitoring
The CDU’s exclusive True RMS current monitoring is critical
to preventing overloads in high-density computing
environments. LED digital displays on the CDU enclosure
report the input current of each phase or branch circuit.
Temperature and Humidity
The Switched CDU supports two external probes. Each of
these probes measure both temperature and humidity.
Receive SNMP-based alert notifications when conditions
exceed defined thresholds.
Additional Benefits:
CW-8H1-C20
CW-8H2-C20
CW-8H1-L530
CW-8H2-L630
100-120V
50/60Hz
100-120V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz 30A
20A
30A
20A IEC 60320/C20
Power Inlet
NEMA L5-30P
Cordset
IEC 60320/C20
Power Inlet
NEMA L6-30P
Cordset
(8) NEMA 5-20R
(8) IEC 60320/C13
(8) NEMA 5-20R
(8) IEC 60320/C13
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
Additional Features and Specifications
Branch Circuit Protection
> Compliant to UL 60950-1
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and
CAN/CSA 22.2 No. 60950-1-03
> European Union (TUVGS mark) to EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3
> LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
EMTH-1-1 Temperature & Humidity Probe, 10’
Power Cord Options
> PTCORD-1 IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2 IEC 60320/C19 - Schuko 10’
> PTCORD-3 IEC 60320/C19 - IEC 60309 (BS4343, CEE17)
16/20A Blue (UK Commando) 10’
> PTCORD-4 IEC 60320/C19 - BS1363 13A (UK) 10’
> PTCORD-5 IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’
> PTCORD-6 IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’
> PTCORD-7 IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’
> PT-ADP-C19 Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module
Model Numbers
> CX-8H1-C20
> CX-8H1-L530
> CX-8H2-C20
> CX-8H2-L630
> CX-8HE-C20
CW-8HE-C20* 230V
50/60Hz 16A IEC 60320/C20
Power Inlet (8) IEC 60320/C13 17.0” x 1.75” x 7.0”
*European Model
© Server Technology, Inc. 7/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.

This manual suits for next models

5

Other Server Technology Power Distribution Unit manuals

Server Technology Switched Rack PDU User manual

Server Technology

Server Technology Switched Rack PDU User manual

Server Technology switched pro2 User manual

Server Technology

Server Technology switched pro2 User manual

Server Technology Sentry CB-12H Series User manual

Server Technology

Server Technology Sentry CB-12H Series User manual

Server Technology CDUCW-24V4 User manual

Server Technology

Server Technology CDUCW-24V4 User manual

Server Technology CDUCW-16V-MX User manual

Server Technology

Server Technology CDUCW-16V-MX User manual

Server Technology 4805-XLS-16B User manual

Server Technology

Server Technology 4805-XLS-16B User manual

Server Technology switched pro2 User manual

Server Technology

Server Technology switched pro2 User manual

Server Technology CW-16V User manual

Server Technology

Server Technology CW-16V User manual

Server Technology Sentry PT22 Installation guide

Server Technology

Server Technology Sentry PT22 Installation guide

Popular Power Distribution Unit manuals by other brands

Ilsco SSI SpecPro SSM 48 Series Installation instruction

Ilsco

Ilsco SSI SpecPro SSM 48 Series Installation instruction

Minuteman RPM 1609 Specifications

Minuteman

Minuteman RPM 1609 Specifications

SMAR IS400P installation manual

SMAR

SMAR IS400P installation manual

ABB REB650 Applications manual

ABB

ABB REB650 Applications manual

Siemens Siprotec 5 7SS85 Techical data

Siemens

Siemens Siprotec 5 7SS85 Techical data

S&C Trans-Rupter II SE Installation

S&C

S&C Trans-Rupter II SE Installation

SELF SLPU-2P1U1C1S-WL-BK manual

SELF

SELF SLPU-2P1U1C1S-WL-BK manual

Avocent Cyclades PM10-15A Specification sheet

Avocent

Avocent Cyclades PM10-15A Specification sheet

LifeSafety Power NETPOWER NPM115 installation manual

LifeSafety Power

LifeSafety Power NETPOWER NPM115 installation manual

Geist VRTD Series instruction manual

Geist

Geist VRTD Series instruction manual

CEP 8706GU Installation and operating instructions

CEP

CEP 8706GU Installation and operating instructions

Hussmann Proto-Aire EZ Installation and operation manual

Hussmann

Hussmann Proto-Aire EZ Installation and operation manual

Schaudt CV 304 instruction manual

Schaudt

Schaudt CV 304 instruction manual

ATEN ALTUSEN PE6108 user manual

ATEN

ATEN ALTUSEN PE6108 user manual

aldes InspirAIR Home Series Installation and maintenance guide

aldes

aldes InspirAIR Home Series Installation and maintenance guide

ABB Relion 615 series manual

ABB

ABB Relion 615 series manual

Raritan PX3TS Quick setup guide

Raritan

Raritan PX3TS Quick setup guide

MTT MS3707H user manual

MTT

MTT MS3707H user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.