Geist HT Series User manual

Geist 1821 Yolande Ave., Lincoln, NE 68521
800.432.3219 | 402.474.3400 | F: 402.474.4369 | www.geistglobal.com
Instruction Manual
Rack Power Distribution Unit
HT Series

GM1097 Rev 2
2
Rev Date: 7/28/2014
Contents
Specifications ....................................................................................................................3
Overview 3
Environmental 3
Electrical 3
Receptacle Ratings 3
EMC Verification 3
Installation .......................................................................................................................4
Instructions 4
Guidelines 4
Mounting ...........................................................................................................................5
Service/Tech Support .....................................................................................................12
Service and Maintenance 12
More Technical Support 12
Table of Figures ..............................................................................................................13
Revision History ..............................................................................................................14

GM1097 Rev 2
3
Rev Date: 7/28/2014
Specifications
Overview
The HT Series products are Power Distribution Units (PDU) intended for connection to a 15 or 20
Amp AC Mains circuit
1
. The PDUs are designed to be powered by either a single phase or a three
phase AC input circuit. Three phase units can be configured for either a delta or wye input
connection.
Environmental
Temperature
Operating: 10°C (50°F) min 60°C (140°F) max
Storage: -25°C (-13°F) min 65°C (149°F) max
Humidity
Operating: 5% min 95% max (non-condensing)
Storage: 5% min 95% max (non-condensing)
Elevation
Operating: 0 m (0 ft) min 2000 m (6561 ft) max
Storage: 0 m (0 ft) min 15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
IEC-320 C13 125/250 Volt, 15 Amp (per Receptacle Bank)
IEC-320 C19 125/250 Volt, 20 Amp
EMC Verification
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Warning: Changes or modifications to this unit not expressly approved by the party responsible
for compliance could void the user’s authority to operate this equipment.
FCC and Canadian ICES-003 requirements for units with Ethernet Meter: The ferrite core shipped
with the unit must be placed around the Ethernet cable close to the PDU.
1
Global Versions of the HT Series are intended to be connected to a 16 Amp AC Mains Branch
Circuits

GM1097 Rev 2
4
Rev Date: 7/28/2014
Installation
Instructions
1. Using appropriate hardware, mount PDU to rack (see Mounting section for additional
instructions).
2. Plug PDU into de-energized 15 or 20 Amp branch circuit receptacle
2
.
3. Connect devices into PDU’s output receptacles. It is recommended that the devices are turned
off until all devices are connected to PDU
4. Turn on branch circuit to energize PDU.
5. Power on devices. Sequential power up is recommended to avoid high inrush current.
Guidelines
If the PDU is installed in a cabinet the ambient temperature of the rack should be no greater
than 60C.
Install the PDU such that the amount of airflow required for safe operation of equipment is
not compromised.
Mount the PDU so that a hazardous condition is not achieved due to uneven mechanical
loading.
Follow nameplate ratings when connecting equipment to the branch circuit. Take into
consideration the effect that overloading of the circuits might have on over-current protection
and supply wiring.
The PDU relies on the building installation for protection from over-current conditions. A
certified overcurrent protection device is required in the building installation. The overcurrent
protection device should be sized according to the PDU’s nameplate ratings and local/national
electrical codes.
Reliable earthing of rack-mount equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit. The PDU
must be connected to an earthed socket-outlet.
The PDU is intended for Restricted Access Locations only and only qualified service personnel
should install and access the PDU.
For pluggable equipment, install the PDU so that the input plug or appliance coupler may be
disconnected for service.
Sequential power-up of devices powered by the PDU is recommended to avoid high inrush
current.
Caution: Disconnect all power cords before servicing.
The PDU is intended for use with TN, TT, or IT power supply systems
2
Branch Circuit should be sized based on the PDU’s nameplate electrical rating. A 12 Amp rated
PDU is intended for use on a 15 Amp Branch Circuit, while a 16 Amp rated PDU is intended for use
on a 20 Amp Branch Circuit. For Global Units a 16 Amp rated PDU is intended for use on a 16 Amp
Branch Circuit.

GM1097 Rev 2
5
Rev Date: 7/28/2014
Mounting
Full Length Bracket
Using the full length bracket, mount PDU to rack as shown
Mini "L" Brackets (SLB-4)
Using the mini “L” brackets, attach PDU to rack as shown

GM1097 Rev 2
6
Rev Date: 7/28/2014
Vertical Extension Brackets (VCB-1)
Using the vertical extension brackets, attach PDU to rack as shown
Toolless Mounting Hardware (11621)
Secure toolless mounting buttons to PDU as shown. Use toolless buttons with key-holed slots built
into cabinet or with optional Geist key-holed brackets.

GM1097 Rev 2
7
Rev Date: 7/28/2014
Toolless Full Length Bracket (TLFL)
Using full length toolless bracket and toolless mounting buttons, attach PDU to rack as shown
Single Side Mount 2 Unit Brackets (TSMX2)
Using single side mount 2 unit brackets and toolless mounting buttons, attach PDU to rack as
shown

GM1097 Rev 2
8
Rev Date: 7/28/2014
Offset/Side Mount Brackets (EZB-1)
Using the offset/side mount brackets, attach PDU to rack as shown.
7" Extension Brackets (XB-7)
Using the 7” extension brackets, attach PDU to rack as shown

GM1097 Rev 2
9
Rev Date: 7/28/2014
Flush Mount Brackets (FM)
Using flush mount brackets, attach PDU to rack as shown
Adjustable Mount Brackets (AM)
Using adjustable mount brackets, attach PDU to rack as shown

GM1097 Rev 2
10
Rev Date: 7/28/2014
Panel Mount Brackets (PM)
Using panel mount brackets, attach PDU to rack as shown
23" Conversion Mounting Brackets (23-RM)
Using conversion mounting brackets, attach 19” PDU to 23” rack as shown

GM1097 Rev 2
11
Rev Date: 7/28/2014
Cable Mount Bracket (CMB-1)
Attach cable mount bracket to PDU as shown; use tie-wraps to secure cords to bracket
19" Horizontal/Panel Mount Brackets (7938)
Using the 19” horizontal/panel mount brackets, attach PDU to rack as shown

GM1097 Rev 2
12
Rev Date: 7/28/2014
Service/Tech Support
Service and Maintenance
No service or maintenance is required. Do not attempt to open the PDU or you may void the
warranty. No serviceable parts inside. It is recommended that power be removed from the unit
before installing or removing any equipment.
More Technical Support
http://www.geistglobal.com
(800) 432-3219
Email: support@geistglobal.com
Or contact your distributor.

GM1097 Rev 2
13
Rev Date: 7/28/2014
Table of Figures
Full Length Bracket...................................................................................................................................................................5
Mini "L" Brackets (SLB-4) ......................................................................................................................................................5
Vertical Extension Brackets (VCB-1)......................................................................................................................................6
Toolless Mounting Hardware (11621)......................................................................................................................................6
Toolless Full Length Bracket (TLFL)......................................................................................................................................7
Single Side Mount 2 Unit Brackets (TSMX2) .........................................................................................................................7
Offset/Side Mount Brackets (EZB-1).......................................................................................................................................8
7" Extension Brackets (XB-7)...................................................................................................................................................8
Flush Mount Brackets (FM) .....................................................................................................................................................9
Adjustable Mount Brackets (AM)............................................................................................................................................9
Panel Mount Brackets (PM) ...................................................................................................................................................10
23" Conversion Mounting Brackets (23-RM).......................................................................................................................10
Cable Mount Bracket (CMB-1)..............................................................................................................................................11
19" Horizontal/Panel Mount Brackets (7938).......................................................................................................................11

GM1097 Rev 2
14
Rev Date: 7/28/2014
Revision History
Revision
Date
Notes
Approved By
1.0
5/20/2010
Original Published Version
BP
1.1
6/22/2012
Change Logo and Web Address
SR
2.0
7/28/2014
Changed company’s name
QN
Table of contents
Other Geist Power Distribution Unit manuals
Popular Power Distribution Unit manuals by other brands

Ilsco
Ilsco SSI SpecPRO SRM Series manual

ICT
ICT ICT200DF-12IRC instruction manual

hager
hager orion plus Mounting instructions

Essential Audio Tools
Essential Audio Tools Mains Multiplier 6+ user manual

Sonnen
Sonnen sonnenProtect 1300 operating instructions

Pepperl+Fuchs
Pepperl+Fuchs GUB Series Brief instructions