SEW-Eurodrive MOVIDRIVE MDR60A1320-503-01 User manual

*27789314_0722*
Drive Technology \ Drive Automation \ System Integration \ Services
Addendum to the Operating
Instructions
MOVIDRIVE® MDR60A1320-503-01 regenerative power
supply
Edition 07/2022 27789314/EN

SEW-EURODRIVE—Driving the world

Table of contents
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 3
Table of contents
1 General information.................................................................................................................. 4
1.1 About this documentation ...............................................................................................4
1.2 Structure of the safety notes ...........................................................................................4
1.3 Other applicable documentation .....................................................................................5
1.4 Rights to claim under limited warranty ............................................................................5
1.5 Product names and trademarks......................................................................................5
1.6 Copyright notice ..............................................................................................................5
2 Device structure ....................................................................................................................... 6
2.1 Characteristics ................................................................................................................6
2.2 Example nameplate and type designation ......................................................................6
3 Electrical installation................................................................................................................ 8
3.1 Installation in a CE typical drive system..........................................................................8
3.2 Electrical connection .......................................................................................................9
3.3 Control connections ......................................................................................................13
3.4 Terminal assignment control terminal strip X2..............................................................14
3.5 Terminal assignment inhibit input A1/A2.......................................................................15
4 Startup ..................................................................................................................................... 16
4.1 Initial operation..............................................................................................................16
4.2 Ready message ............................................................................................................17
5 Service..................................................................................................................................... 18
5.1 Reset.............................................................................................................................18
5.2 Operating displays ........................................................................................................19
5.3 Waste disposal..............................................................................................................21
6 Inspection/maintenance......................................................................................................... 22
6.1 Unit................................................................................................................................22
6.2 Check cooling air vents.................................................................................................22
7 Technical data......................................................................................................................... 23
7.1 Markings .......................................................................................................................23
7.2 General technical data ..................................................................................................24
7.3 Current carrying capacity ..............................................................................................25
7.4 Fuses and cable cross sections....................................................................................25
7.5 Dimension sheet ...........................................................................................................27
27789314/EN – 07/2022

1General information
About this documentation
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
4
1 General information
1.1 About this documentation
The documentation at hand is the original.
This documentation is an integral part of the product. The documentation is intended
for all employees who perform work on the product.
Make sure this documentation is accessible and legible. Ensure that persons respon-
sible for the systems and their operation as well as persons who work on the product
independently have read through the documentation carefully and understood it. If you
are unclear about any of the information in this documentation or if you require further
information, contact SEW‑EURODRIVE.
1.2 Structure of the safety notes
1.2.1 Meaning of signal words
The following table shows the grading and meaning of the signal words for safety
notes.
Signal word Meaning Consequences if disregarded
DANGER Imminent hazard Severe or fatal injuries
WARNING Possible dangerous situation Severe or fatal injuries
CAUTION Possible dangerous situation Minor injuries
NOTICE Possible damage to property Damage to the product or its envi-
ronment
INFORMATION Useful information or tip: Simplifies
handling of the product.
1.2.2 Structure of section-related safety notes
Section-related safety notes do not apply to a specific action but to several actions
pertaining to one subject. The hazard symbols used either indicate a general hazard
or a specific hazard.
This is the formal structure of a safety note for a specific section:
SIGNAL WORD
Type and source of hazard.
Possible consequence(s) if disregarded.
• Measure(s) to prevent the hazard.
27789314/EN – 07/2022

1
General information
Other applicable documentation
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 5
Meaning of the hazard symbols
The hazard symbols in the safety notes have the following meaning:
Hazard symbol Meaning
General hazard
Warning of dangerous electrical voltage
1.2.3 Structure of embedded safety notes
Embedded safety notes are directly integrated into the instructions just before the de-
scription of the dangerous action.
This is the formal structure of an embedded safety note:
SIGNAL WORD! Type and source of hazard. Possible consequence(s) if disre-
garded. Measure(s) to prevent the hazard.
1.3 Other applicable documentation
This documentation supplements the operating instructions of the associated product.
Use this document only in connection with the operating instructions.
Always use the latest edition of the documentation and the software.
The SEW‑EURODRIVE website (www.sew‑eurodrive.com) provides a wide selection
of documents for download in various languages. If required, you can also order print-
ed and bound copies of the documentation from SEW‑EURODRIVE.
1.4 Rights to claim under limited warranty
Read the information in this documentation. This is essential for fault-free operation
and fulfillment of any rights to claim under limited warranty. Read the documentation
before you start working with the product.
1.5 Product names and trademarks
The brands and product names in this documentation are trademarks or registered
trademarks of their respective titleholders.
1.6 Copyright notice
©2022SEW‑EURODRIVE. All rights reserved. Unauthorized reproduction, modifica-
tion, distribution or any other use of the whole or any part of this documentation is
strictly prohibited.
27789314/EN – 07/2022

2Device structure
Characteristics
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
6
2 Device structure
2.1 Characteristics
• Small, compact size
• Supply of drive controllers
• Braking power from drive controllers is fed back into power supply system
• Nominal power 160kW
• Continuous power 200kW
• Peak power 240kW (motor) / 210kW (regenerative) for 60s
• DC link connection of several drive controllers possible
• Power section with high efficiency and operational safety
• Automatic system synchronization
• Overload protection in regenerative operation
• Monitoring of line voltage, rotating field orientation and temperature
• Implementation of highly dynamic braking actions
• User-friendly startup because no programming or setting adjustment is required
2.2 Example nameplate and type designation
2.2.1 Nameplate
The following figure gives an example of a nameplate of the device. For the structure
of the type designation, refer to chapter "Type designation".
37583185163
27789314/EN – 07/2022

2
Device structure
Example nameplate and type designation
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 7
2.2.2 Type designation
Example: MDR60A1320-503-01
Product name MDR • MDR = MOVIDRIVE® regenerative power supply
Device type 60 • 60 = Type designation up to size 6
• 61 = Type designation for size 7
Version A• A = Version status up to size 6
• B = Version status for size 7
Recommended inverter 1320 • 1320 = 132kW
Connection voltage 5• 2=AC200–230V
• 5=AC380–500 V
Radio interference sup-
pression
0• 0 = No radio interference suppression
Number of phases 3 • 3 = 3-phase
Quadrants 0 • 4 = 4-quadrant operation
Designs
01 • 00 = Standard (phased out)
• 00/L = Coated PCBs
• 01 = Standard (as of July 2020)
27789314/EN – 07/2022

3Electrical installation
Installation in a CE typical drive system
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
8
3 Electrical installation
3.1 Installation in a CE typical drive system
3.1.1 General information
• The customer is responsible for maintaining the EU guidelines in the machine
operation.
– If you observe the following measures you can assume that there will be no
EMC problems caused by the regenerative power supply unit when operating
the machine and that the EU directive and the EMC law have been met.
– If you operate any devices in the vicinity of the supply and regenerative supply
unit that do not meet the CE requirements regarding interference immunity ac-
cording to EN 61000-6-2, these devices may be electromagnetically impaired
by the regenerative power supply units.
3.1.2 Structure
• Establish a connection over a large area on the grounded mounting plates for the
power supply and regenerative supply unit and radio interference suppression fil-
ter:
– Mounting plates with conductive surface (galvanized or stainless steel) make
for a permanent contact.
– Coated plates are not suitable for an EMC-compliant installation.
• If you use several mounting plates:
– Connect the mounting plates to each other over a large area (e.g. with copper
bands)
• Install the power cables and control cables separately.
• Route the cables as close as possible to the reference potential. Any free-floating
conductors act as antennas.
3.1.3 Filtering
• Use only those radio interference suppression filters assigned to the power supply
and regenerative supply units. Radio interference suppression filters reduce ex-
cessive high-frequency disturbances to a permitted level.
27789314/EN – 07/2022

3
Electrical installation
Electrical connection
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 9
3.1.4 Shielding
• Metal cable glands ensure a connection of shield and housing over a large area.
• In case of contactors and terminals in shielded cables
– Connect the shields of all cables and connect these over a large area with the
mounting plate.
• In case of supply system cables between radio interference suppression filter and
drive controller in excess of 300mm:
– Shield supply system cable.
– Apply the shield of the supply system cable directly at the drive controller / on
the regenerative power supply unit and the radio interference suppression filter
and connect it over a large area to the mounting plate.
• SEW-EURODRIVE recommends making the cabling between the line filter and the
drive controller as short as possible and using shielded cables.
3.1.5 Grounding
• Ground all conductive metal components (power supply and regenerative supply
unit, drive controller, radio interference suppression filter) by using the appropriate
cables from a central grounding point (PE busbar).
• Comply with the minimum cross sections defined in the safety regulations:
– For EMC purposes, it is not the cable cross section but the surface of the cable
and the connection over a wide area that are important.
3.1.6 Further information
Regenerative power supply units are electrical operating resources for operation in in-
dustrial and commercial systems. These units are not subject to a specific identifica-
tion according to EMC Directive 2004/108/EC because according to EMC Directive
and EMC law, they are units intended for further installation by competent machine
and system manufacturers and cannot be operated on their own. The verification of
maintaining the protection targets required by the EMC Directive must be provided by
the installer/user of a machine/system.
When using the radio interference suppression filters provided by SEW-EURODRIVE
and adhering to the notes on EMC compliant installation, the appropriate requirements
for CE marking of the entire machine/system in which they are installed are met on the
basis of the EMC Directive 2004/108/EC.
The MOVIDRIVE® MDR60A... regenerative power supply units in combination with the
associated radio interference suppression filters are intended for operation in environ-
ments of class C2 limit.
Definition according to generic standard:
• EN 61000-6-4 for interference emission
• EN 61000-6-2 for interference immunity
3.2 Electrical connection
After you have removed the lateral knurled screws and the housing cover, the wiring
space of the MOVIDRIVE® MDR60A1320-503-01 is accessible. The incoming cables
are guided through the metal cable glands installed in the flange.
27789314/EN – 07/2022

3Electrical installation
Electrical connection
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
10
NOTICE
Make sure not to damage or tear off the cables leading to the display board
when removing the cover!
3.2.1 Power connection
Fusing:
• Consider the voltage drop in case of load when selecting the cable cross section.
• Protection of cables and regenerative power supply units on AC side (L1, L2, L3):
via commercial semiconductor fuses.
– Rated voltage of fuses must be configured according to the line voltage on site.
• Protection of the regenerative power supply on the DC voltage side at the termi-
nals + and -:
– The corresponding fuses are installed in the unit.
Connection:
• Make all connections as short and as low in inductance as possible.
• Use shielded cables to meet EMC directives (according to existing standards such
as VDE 0160 and EN 61800-5-1).
• Connect the supply cables to terminals L1, L2, and L3 of the regenerative power
supply unit. The connection must always be 3-phase.
• A certain phase sequence has to be observed for the power supply connections of
the power section (clockwise rotating field). The unit comes equipped with a phase
monitoring option. If the phase monitoring detects an incorrect phase sequence,
the unit will indicate the following fault message with its LEDs "Incorrect rotating
field" or "Phase failure" (→ chapter ""Operation and service""). In this case you
must replace 2 supply system phases of the power supply connection.
• Connect the cables for the DC link connection of the drive controller and the re-
generative power supply unit to the terminals + and -. Ensure correct polarity when
doing so!
• To absorb the torque, observe the specified torques and use a second wrench.
• Connect the protective earth conductor of the supply cable to one of the earthing
screws on the bottom of the unit.
NOTICE
Reversal or incorrect connection of the DC link cables from the + terminal or
the - terminal can destroy the drive controller and the regenerative power sup-
ply unit!
Wiring diagram
The following wiring diagram is a circuit recommendation. Special requirements for the
application, such as the integration of a PLC, may require changes to the connection
of contacts X2:1 to X2:12.
27789314/EN – 07/2022

3
Electrical installation
Electrical connection
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 11
1. ... 5. → Section "Notes on wiring diagram"
L1
L2
L3
PE
F11 F12 F13
NF...
L1 L2 L3
L1' L2' L3'
®®
456
3 8
7
+R
PE
X1: X4:
X2:
9
8
X3:
PE L1 L2 L3
PE W-R PE
max. 5 m
-UZ+UZ
VU
12
MOVIDRIVE
MDR60A1320-503-01
+
_
L1
L 2L3
7 8 9 10 11 12
X2:
X2: 2143
456
3 8
7
+R
PE
X1: X4:
X2:
9
8
X3:
PE L1 L2 L3
PE W-R PE
BW... l
-UZ+UZ
VU
12
®
1.
2.
4.
5.
MOVIDRIVE / MOVITRAC MOVIDRIVE / MOVITRAC
®®
A1 A2
SKS
1 2 3
3.
M
PE M
PE
Do not connect
Relay contacts Control electronics
ext.
OFF
ext. ON
RESET
Blocking
Energy
recovery
Affects line
contactor
Faulty DC link connection (cross-
polarity, ground fault) causes
irreparable damage to the
connected equipment!
The line connections of the
inverter must not be
connected!
37625465867
Notes on wiring diagram
1. Fusing according to these operating instructions.
2. Do not connect any additional consumers (besides the regenerative power supply)
behind the line contactor connected in the incoming cable.
3. Cable cross section according to applicable VDE regulations.
27789314/EN – 07/2022

3Electrical installation
Electrical connection
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
12
4. It is possible to connect one or more drive controllers at this site, even with differ-
ent power ratings. Keep the DC connection cables as short as possible even when
connecting several drive controllers! Route the cables as closely as possible.
5. The option of an external ON or RESET takes place via terminal pairs X2:11 and
X2:12 (chapter "Terminal assignment control terminal strip X2"(→212)):
• X2:11 and X2:12: Positive impulse (DC 12 to 24 V); can be implemented
through PLC control (terminal 11 +, terminal 12 -).
3.2.2 Control cables
• Connect the control cables to the control terminal strip X2 (→section "Terminal as-
signment control terminal strip X2").
• Do not route the control cables parallel to motor cables, which emit interference.
• Apply the shielding of the control cables over a wide area of the metal cable
glands on the flange.
3.2.3 Control connections
Use the terminal control strip X2 to connect via relay certain messages such as ready
for operation or a collective fault outside the unit. You can also perform an external
RESET or switching function via the control terminal strip X2 and link it with the fre-
quency inverter.
3.2.4 Terminal assignment control terminal strip X2
121110987654321
+-
[1] [2]
[3] [4] [5]
37346745739
[1] X2:1 to X2:4 relay collective fault
[2] X2:5, X2:6 Internal assignment for temperature monitoring. Do not connect any
cables!
[3] X2:7, X2:8 External OFF
[4] X2:9, X2:10 not assigned
[5] X2:11, X2:12 = ON / RESET
NOTICE
Do not connect any external voltage to terminals X2:5 and X2:10 because otherwise
the unit may be damaged!
27789314/EN – 07/2022

3
Electrical installation
Control connections
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 13
Terminal Function Description
X2:1 NC contact Isolated relay contacts1) and there is
no collective fault, the relay picks up.2)
Collective fault signal switching capacity of the
relay contacts:
• 30V DC3A
• 230V AC5A
X2:2 NC contact
X2:3 NO contact
X2:4 NO contact
X2:5 Internal assignment for temperature
monitoring
X2:6
X2:7 OFF pushbutton To switch off the regenerative power supply
X2:8
X2:9 Not assigned
X2:10
X2:11 (+24V) External voltage input To switch on the regenerative power supply or
confirm faults
X2:12 (0V)
1) When the supply voltage is present, the precharging of the DC link capacitors is complete,
2) The relay drops out in the event of an OFF command via terminals X2:7 and X2:8 and in the event of a fault message.
3.2.5 Terminal assignment inhibit input A1/A2
Terminal Function Description
A1 Inhibit input 24 V Control voltage to inhibit the regenerative
power supply path (not isolated)
A2 DGND
Higher-level
controller
Binary output
MOVIDRIVE
MDR60A1320-503-01
®
DGND
A1
A2
9007203321273099
3.3 Control connections
Use the terminal control strip X2 to connect via relay certain messages such as ready
for operation or a collective fault outside the unit. You can also perform an external
RESET or switching function via the control terminal strip X2 and link it with the fre-
quency inverter.
27789314/EN – 07/2022

3Electrical installation
Terminal assignment control terminal strip X2
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
14
3.4 Terminal assignment control terminal strip X2
121110987654321
+-
[1] [2]
[3] [4] [5]
37346745739
[1] X2:1 to X2:4 relay collective fault
[2] X2:5, X2:6 Internal assignment for temperature monitoring. Do not connect any
cables!
[3] X2:7, X2:8 External OFF
[4] X2:9, X2:10 not assigned
[5] X2:11, X2:12 = ON / RESET
NOTICE
Do not connect any external voltage to terminals X2:5 and X2:10 because otherwise
the unit may be damaged!
Terminal Function Description
X2:1 NC contact Isolated relay contacts1) and there is
no collective fault, the relay picks up.2)
Collective fault signal switching capacity of the
relay contacts:
• 30V DC3A
• 230V AC5A
X2:2 NC contact
X2:3 NO contact
X2:4 NO contact
X2:5 Internal assignment for temperature
monitoring
X2:6
X2:7 OFF pushbutton To switch off the regenerative power supply
X2:8
X2:9 Not assigned
X2:10
X2:11 (+24V) External voltage input To switch on the regenerative power supply or
confirm faults
X2:12 (0V)
1) When the supply voltage is present, the precharging of the DC link capacitors is complete,
2) The relay drops out in the event of an OFF command via terminals X2:7 and X2:8 and in the event of a fault message.
27789314/EN – 07/2022

3
Electrical installation
Terminal assignment inhibit input A1/A2
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 15
3.5 Terminal assignment inhibit input A1/A2
Terminal Function Description
A1 Inhibit input 24 V Control voltage to inhibit the regenerative
power supply path (not isolated)
A2 DGND
Higher-level
controller
Binary output
MOVIDRIVE
MDR60A1320-503-01
®
DGND
A1
A2
9007203321273099
27789314/EN – 07/2022

4Startup
Initial operation
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
16
4 Startup
4.1 Initial operation
NOTICE
• Check the wiring for completeness, false polarity, short circuits and ground fault
prior to taking the unit into operation.
• Incorrect connection could result in problems with the drive controller.
1. Switch on the supply system. The unit is ready for operation after about 1s.
2. Check to make sure that the regenerative power supply unit is ready for operation:
• The unit is ready for operation if only the green LED of the regenerative power
supply unit is lit up.
• A problem exists if other LEDs besides the green LED are lit up. Remedy any
faults before you proceed with startup. Observe chapter ""Operation and ser-
vice"".
3. Check to see if the drive controller is ready for operation in accordance with the
corresponding operating instructions.
27789314/EN – 07/2022

4
Startup
Ready message
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 17
4.2 Ready message
The following figure shows how the ready signal (ready) from the regenerative power
supply unit must be connected to the "Power supply system on" binary input of the
MOVIDRIVE® inverter. With MOVITRAC®, the evaluation is carried out via a binary in-
put ("External fault") and the fault response must be parameterized.
The following figure shows an example of a MOVIDRIVE®-MDX60/61B.. and a
MOVITRAC® inverter.
X13:
X2:
X12:
DIØØ
DIØ1
DIØ2
DIØ3
DIØ4
DIØ5
DCOM
VO24
DGND
ST11
ST12
DIØØ
DIØ1
DIØ2
DIØ3
DIØ4
DIØ5TF
VOTF
24VIO
GND
1
2
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
7
8
9
X13:DIØØ...DIØ5
n12/n22
RS-485 -
RS-485+
MOVIDRIVE®MOVITRAC®
121110987654321
MOVIDRIVE®MDR60A1320-503-01
n11/n21
n13 = n11 + n12 {
Regenerative power supply unit
Inverter Inverter
/Controller inhibit
CCW/stop
CW/stop
Power ON
Enable/stop
Reference
Fault reset
DC+24V output
Reference potential for binary
signals
CW/stop
CCW/stop
Enable/stop
Reference potential for binary
signals
/External fault
Supply voltage for TF/TH
(disconnectable with P808)
+24 V input/output
37627939339
27789314/EN – 07/2022

5Service
Reset
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
18
5 Service
5.1 Reset
5.1.1 Regenerative power supply
Any time the MOVIDRIVE® MDR60A1320-503-01 regenerative power supply unit is
switched off, an automatic reset occurs. You can trigger a manual reset by using the
reset pushbutton on the front panel (chapter "Operation displays") of the
MDR60A1320-503-01.
DGND
X12/X13:
DGND 9
X2:
121110987654321
MOVIDRIVE®MDR60A1320-503-01
DI..
DI..
DI..
DI..
DI..
DI..
Regenerative power supply
unit
Inverter*
/Controller inhibit
CW/stop
CCW/stop
Enable/stop
Power ON
Reset
Reference potential for binary
signals
Higher-level
controller
Binary
outputs
Ref. binary
outputs
37612727819
*Parameterize a digital input with "Reset".
27789314/EN – 07/2022

5
Service
Operating displays
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply 19
5.2 Operating displays
The 5 LEDs in the cover of the regenerative power supply unit show the respective op-
erating state. Observe chapter ""LED signals"" (→ 2 20). The same LEDs are also
located on the internal control board for easier checking during maintenance. There is,
however, a separate orange LED on the board; its function is assigned to the two-
color (green/orange) LED in the cover.
off/collective error
phase failure
overcurrent/UcE
operation
overtemperature
reset
GN
RD
RD
YE
OG
1877453195
If a fault message is generated during the braking process, leading to the disconnec-
tion of the regenerative power supply unit, the regenerative power supply unit may not
be confirmed until the braking process is complete and the DC link voltage has
dropped to the default value.
We recommend that you block the pulse enable of the drive controller via the central-
ized alarm signal relay to prevent any problems that arise.
27789314/EN – 07/2022

5Service
Operating displays
Addendum to the Operating Instructions – MOVIDRIVE® MDR60A1320-503-01 regenerative power supply
20
5.2.1 UCE disconnection
The regenerative power supply unit switches off via the UCE protective device if the
maximum current specified for the respective unit is exceeded. The operating principle
of this protective device does, however, cause an overload of the IGBTs for less than
a millisecond far in excess of its specifications for normal operation. This is not usually
a problem for the unit. If this overcurrent disconnection occurs often or regularly, the
result will be an accelerated aging of the power semiconductors and ultimately prema-
ture failure of the component.
Frequent UCE disconnections due to overcurrents can be triggered by:
• Overload
• Undervoltage in the supply system
• Defective or oscillating controller, such as in the drive controller
• An oscillating reference value of the controller
• Incorrect dimensioning of the system
5.2.2 LED signals
Fault
code
LED displays Meaning Relay
status
Opera-
tion
(Green)
Phase
failure
(Red)
Over-
cur-
rent /
UCE
(Red)
Overtem-
perature
(Orange)
Collective
fault
(Yellow)
During initial startup During operation
1 X - - - - The unit is ready for opera-
tion (after about 1s)
Unit in operation In rest posi-
tion
2 X - - - - Unit ready for operation but no regenerative power supply
→check DC fuses
3 X - - X X - Overtemperature of the heat
sink.
→Fault message cannot be
confirmed while temperature
is still too high.
Dropped out
4 X - - - X - Just like fault code 3.
→Heat sink temperature has
dropped and fault can be con-
firmed.
5 X - - - X Unit has been turned off (external OFF).
→Enable signal required
6 X - - - X Triggering the overvoltage monitoring.
Enable signal is required if the line voltage has dropped to
nominal value
7 X X - - X Incorrect rotating field or
phase
Phase failure has been de-
tected
→Confirmation necessary.
8 X - X - X - Overcurrent (three-phase
side) has been detected.
→Confirmation necessary.
9 X X X - X Fault codes 7 and 8 Overcurrent has been detect-
ed with simultaneous phase
failure detection due to com-
mutation notch.
10 X X X X X Several faults occurring at the same time.
11 - - - - - Unit not operating, at least 2 phases without voltage.
13 X X - - - - Massive commutation notch
has been detected, no dis-
connection because jumpers
3 and 7 are open.
→Operation can be re-
sumed, recommendation for
improved supply system.
27789314/EN – 07/2022
Table of contents
Other SEW-Eurodrive Power Supply manuals

SEW-Eurodrive
SEW-Eurodrive MOVITRANS TES31A User manual

SEW-Eurodrive
SEW-Eurodrive MOVITRANS THM20C User manual

SEW-Eurodrive
SEW-Eurodrive MOVITRANS THM10C Series User manual

SEW-Eurodrive
SEW-Eurodrive MOVIDRIVE MDC90A-0120-50X-X-000 User manual

SEW-Eurodrive
SEW-Eurodrive MOVITRANS Administrator guide

SEW-Eurodrive
SEW-Eurodrive MOVIDRIVE MDR60A User guide
Popular Power Supply manuals by other brands

Camtec
Camtec DCUPS2U4AH technical information

Wealtec
Wealtec ELITE 200 Service & operation & instruction manual

Puls
Puls PIANO Series manual

OCZ
OCZ OCZ400SXS2 - MECHANICAL DRAWING manual

alfatronix
alfatronix AD Series Operating & assembly instructions

Cooler Master
Cooler Master Silent Pro M700 RS-700-AMBA-D3 user manual