Compact Operating Instructions – MOVITRANS® Stationary Components 9
2
Startup/operation
Safety Notes
2.11 Startup/operation
Observe the following notes for starting up and operating the MOVITRANS®units:
• Only qualified electricians with the relevant accident prevention training are allowed
to perform installation, startup and service work on the unit. They must also comply
with the regulations in force (e.g. EN 60204, VBG 4, DIN-VDE 0100/0113/0160).
• Never install damaged units and put them into operation.
• Do not deactivate monitoring and protection devices even for a test run.
• Take appropriate measures (for example, connect binary input DI00 "/CONTROL-
LER INHIBIT" to DGND on the TPS stationary converter) to ensure that the system
does not start up unintentionally when power is switched on.
• During operation, the MOVITRANS®units can have live, bare and movable or rotat-
ing parts as well as hot surfaces, depending on their enclosure.
• When the unit is switched on, dangerous voltages are present at the output terminals
and at any connected cables, terminals and MOVITRANS®units. Dangerous volt-
ages can be present even when the TPS stationary converter supply is disabled and
the system is at a standstill.
• The fact that the operation LED V1 and other display elements are no longer illumi-
nated on the TPS stationary converter does not indicate that the device and con-
nected MOVITRANS®units have been disconnected from the power supply and do
not carry any voltage.
• Safety functions within the unit may cause system standstill. Removing the cause of
the problem or performing a reset can result in an automatic restart of the plant. If
safety reasons prohibit this action, disconnect the TPS10A stationary converter from
the power supply before correcting the fault.
• Before removing the protective cover, disconnect the units from the supply system.
Dangerous voltages may still be present in the units and the connected
MOVITRANS®devices for up to 10 minutes after disconnection.
• With the protective cover removed, the MOVITRANS®units have enclosure IP00.
Dangerous voltages are present at all components. All units must be closed during
operation.
• Please wear appropriate protective clothing during assembly, especially when sol-
dering the TLS line cables.
• Take appropriate security measures to prevent burns by the soldering iron or by hot
solder. Take appropriate measures to prevent hot solder from leaking.