Sharp R-380A User manual


R-380A

R-380A
1
SERVICE MANUAL
MICROWAVE OVEN
R-380A
GENERAL IMPORTANT INFORMATION
ThisManualhasbeenpreparedtoprovideSharpCorp.Service
engineers with Operation and Service Information.
It is recommended that service engineers carefully study the
entire text of this manual, so they will be qualified to render
satisfactory customer service.
CAUTION
MICROWAVE RADIATION
DO NOT BECOME EXPOSED TO RADIATION FROM
THE MICROWAVE GENERATOR OR OTHER PARTS
CONDUCTING MICROWAVE ENERGY.
Service engineers should not be exposed to the microwave
energy which may radiate from the magnetron or other
microwave generating devices if it is improperly used or
connected. All input and output microwave connections,
waveguides, flanges and gaskets must be secured. Never
operate the device without a microwave energy absorbing
load attached. Never look into an open waveguide or
antenna while the device is energized.
WARNING
Never operate the oven until the following points are ensured.
(A) The door is tightly closed.
(B) The door brackets and hinges are not defective.
(C) The door packing is not damaged.
(D) The door is not deformed or warped.
(E) There is not any other visible damage with the oven.
Servicing and repair work must be carried out only by trained
service engineers.
All the parts marked "*" on parts list are used at voltages more
than 250V.
Removal of the outer wrap gives access to potentials above
250V.
All the parts marked "∆" on parts list may cause undue micro-
wave exposure, by themselves, or when they are damaged,
loosened or removed.
SHARP CORPORATION
OSAKA, JAPAN
PRODUCT SPECIFICATIONS
APPEARANCE VIEW
OPERATING SEQUENCE
FUNCTION OF IMPORTANT
COMPONENTS
SERVICING AND
TROUBLESHOOTING CHART
TEST PROCEDURE
TOUCH CONTROL PANEL
ASSEMBLY
COMPONENT REPLACEMENT
AND ADJUSTMENT PROCEDURE
MICROWAVE MEASUREMENT
WIRING DIAGRAM
PARTS LIST

R-380A
2
ITEM DESCRIPTION
Power Requirements 230 - 240 Volts
50 Hertz
Single phase, 3 wire earthed
Power Consumption 1.5kW
Power Output 1000 watts nominal of RF microwave energy (IEC 705)
Operating fequency 2450 MHz
Case Dimensions Width 520 mm
Height 302 mm including foot
Depth 403 mm
Cooking Cavity Dimensions Width 348 mm
Height 212 mm
Depth 379 mm
Turntable diameter 335mm
Control Complement Touch Control System
Clock ( 1:00 - 12:59)
Timer (0 - 99 minutes 99 seconds)
Microwave Power for Variable Cooking
Repetition Rate;
HIGH............................................... Full power throughout the cooking time
MEDIUM HIGH .................................................. approx. 70% of Full Power
MEDIUM .............................................................approx. 50% of Full Power
MEDIUM LOW ....................................................approx. 30% of Full Power
LOW ................................................................... approx. 10% of Full Power
HELP pad
SENSOR INSTANT REHEAT pads
SENSOR COOK pad
SLOW COOK pad
EASY DEFROST pad
MEMORY pad
MORE, LESS pads
NUMBER pads
POWER LEVEL pad
CLOCK pad
TIMER pad
STOP/CLEAR pad
INSTANT COOK/START pad
Set Weight Approx. 17 kg
PRODUCT SPECIFICATIONS
GENERAL INFORMATION
WARNING
THIS APPLIANCE MUST BE EARTHED
IMPOTANT
THE WIRES IN THIS MAINS LEAD ARE COLOURED IN ACCORDANCE WITH THE FOLLOWING CODE:
GREEN-AND-YELLOW : EARTH
BLUE : NEUTRAL
BROWN : LIVE

R-380A
3
APPEARANCEVIEW
1. Ventilation openings
2. Oven lamp
3. Door hinges
4. Door safety latches
5. See through door
6. Door seals and sealing
surfaces
7. Coupling
8. Door open button
9. Touch control panel
10.Digital readout
11.Wave guide cover
12.Power supply cord
13.Rating label
14.Turntable tray
15.Turntable support
8
11 13
7
2
6
3
5
49
12
10
1
14
15
TOUCH CONTROL PANEL
Info Display
HELP
DINNER
PLATE
CASSEROLE
SOUP
PIZZA
VEGETABLES
MEAT
SLOW
COOK
POWER
LEVEL
STOP
CLEAR
INSTANT COOK
START
CLOCK TIMER
MEMORY
EASY
DEFROST
RICE/PASTA
DESSERTS
RICE PIE
Sensor Instant Reheat
Sensor Cook
LESS MORE
12345
6789O
COOK SENSOR KG DEF HELP
POWER LEVEL PAD
Press to select microwave power
setting. If not pressed, HIGH is au-
tomatically selected.
STOP/CLEAR PAD
Press to clear during programming.
Press once to stop operation of oven
during cooking; press twice to can-
cel cooking programme.
TIMER / CLOCK PAD
Press to set Timer.
INSTANT COOK/START PAD
Press once to cook for 1 minute on
HIGH or increase by 1 minute multi-
ples each time this pad is pressed
during cooking. Press to start the
oven after setting programmes.
Indicator
HELP PAD
Press to select auto start, informa-
tion guide on/off, child lock, dem-
onstration modes or info on pads.
Press to get cooking information.
SENSOR INSTANT REHEAT PADS
Press once to reheat 1 or 6 popular
menus.
SLOW COOK PADS
Press to cook slowly and for a long-
er time.
SENSOR COOK PADS
Press to select Sensor Cook menus.
EASY DEFROST PAD
Press to defrost frozen food by
entering quantity.
MORE( ), LESS ( ) PADS
Press to increase/ decrease the time
in one minute increments during
cooking or to after the cooking result
for the Sensor Instant Reheat, Sen-
sor Cook or Easy Defrost modes
NUMBER PADS
Press to enter cooking times, clock
time, weight or quantity of food.
MEMORY PAD
Press to enter a frequently used cook-
ing program. Press to recall the
memorized program.
CLOCK PAD
Press to set Clock.

R-380A
4
OPERATION SEQUENCE
OFF CONDITION
Closing the door activates all door interlock switches
(1st. latch switch, 2nd. latch switch and stop switch).
IMPORTANT
Whentheovendoorisclosed,themonitorswitchcontacts
(COM-NC) must be open.
Whenthemicrowaveovenispluggedinawalloutlet,rated
voltage is supplied to the point A3+A5 in the control unit.
Figure O-1 on page 28
1. The display shows SHARP , MICRO- , WAVE
and OVEN .
2. To set any programmes or set the clock, you must
first touch the STOP/CLEAR pad.
3. : appears in the display.
NOTE: When the oven door is opened, the oven lamp
comes on at this time.
MICROWAVE COOKING CONDITION
HIGH COOKING
Enter a desired cooking time with the touching NUMBER
pad and start the oven with touching START pad.
Function sequence
Figure O-2 on page 28
CONNECTED COMPONENTS RELAY
Oven lamp, Fan motor, Turntable motor RY1
Power transformer RY2
1. Ratedvoltage is supplied to theprimary winding of the
power transformer. The voltage is converted to about
3.3 volts A.C. output on the filament winding and high
voltage of approximately 2000 volts A.C. on the
secondary winding.
2. The filament winding voltage (3.3 volts) heats the
magnetronfilamentandthehighvoltage(2000volts)is
sent to the voltage doubling circuit, where it is doubled
to negative voltage of approximately 4000 volts D.C..
3. The 2450 MHz microwave energy produced in the
magnetron generates a wave length of 12.24 cm. This
energyischanneled throughthewaveguide (transport
channel)into theoven cavity, wherethe foodis placed
to be cooked.
4. Whenthecookingtimeisup,asignaltoneisheardand
the relays RY1+RY2 go back to their home position.
The circuits to the oven lamp, power transformer, fan
motor and turntable motor are cut off.
5. When the door is opened during a cook cycle, the
switches come to the following condition
CONDITION
DURING DOOR OPEN
SWITCH CONTACT COOKING
(NOCOOKING)
1st. latch switch COM-NO Closed Open
2nd. latch switch COM-NO Closed Open
Monitor switch COM-NC Open Closed
Stop switch COM-NO Closed Open
The circuits to the power transformer, fan motor and
turntable motor are cut off when the 1st. latch switch,
2nd.latch switch,andstop switchare madeopen.The
oven lamp remains on even if the oven door is opened
after the cooking cycle has been interrupted, because
therelayRY1 staysclosed.Shown inthedisplay isthe
remaining time.
6. MONITOR SWITCH CIRCUIT
The monitor switch is mechanically controlled by
oven door, and monitors the operation of the 1st and
2nd. latch switches.
6-1 When the oven door is opened during or after the
cycleofacookingprogram,the1st.latchswitch,2nd.
latchswitchand stopswitchmustopen theircontacts
first.
After that the contacts (COM-NC) of the monitor
switch can be closed.
6-2. When the oven door is closed, the contacts (COM-
NC) of the monitor switch must be opened. After that
thecontacts of the 1st. latchswitch, 2nd. latch switch
and stop switch are closed.
6-3. When the oven door is opened and the contacts of
the1st. latch switch, 2nd. latch switch remain closed.
The fuse M8A will blow, because the monitor switch
is closed and a short circuit is caused.
MEDIUM HIGH, MEDIUM, MEDIUM LOW, LOW
COOKING
When the microwave oven is preset for variable cooking
power, 230-240 volts A.C. power is supplied to the power
transformer intermittently within a 32-second time base
through the relay contact which is coupled with the cur-
rent-limitingrelay.Thefollowinglevelsofmicrowavepower
are given.
SETTING; 32 sec. ON
24 sec. ON
18 sec. ON
12 sec. ON
6 sec. ON
8 sec. OFF
14 sec. OFF
20 sec. OFF
26 sec. OFF
HIGH
MEDIUM HIGH
MEDIUM
MEDIUM LOW
LOW
Approx. 70%
Approx. 50%
Approx. 30%
Approx. 10%
NOTE: TheON/OFFtimeratiodoesnotexactlycorrespond
to the percentage of microwave power, because
approx. 2 seconds are needed for heating up the
magnetron filament.
SENSOR COOKING CONDITION
Using the SENSOR COOK or SENSOR INSTANT RE-
HEAT function, the foods are cooked or reheated without
figuring time, power level or quantity. When the oven
senses enough steam from the food, it relays the informa-
tiontoitsmicroprocessorwhichwillcalculatetheremaining
cooking time and power level needed for best results.
When the food is cooked, water vapor is developed. The
sensor “senses” the vapor and its resistance increases
gradually. When the resistance reaches the value set
according to the menu, supplementary cooking is started.
The time of supplementary cooking is determined by ex-
perimentwitheachfoodcategoryand inputtedintotheLSI.

R-380A
5
An example of how sensor works:
1. Potatoesatroomtemperature.
Vapor is emitted very slowly.
2. Heat potatoes. Moisture and
humidity is emitted rapidly.
Youcan smell the aroma asit
cooks.
3. Sensor detects moisture and
humidity and calculates
cooking time and variable
power.
Cooking Sequence.
1. Touch each SENSOR COOK or SENSOR INSTANT
REHEATfunctionpadtooperatingthesensorcooking.
NOTE: The oven should not be operated on SENSOR
COOK or SENSOR INSTANT REHEAT
immediately after plugging in the unit. Wait five
minutes before cooking on SENSOR COOK or
SENSOR INSTANT REHEAT.
2. The coil of shut-off relay (RY-1) is energized, the
turntable motor, oven lamp and cooling fan motor are
turned on, but the power transformer is not turned on.
3. After about 16 seconds, the cook relay (RY-2) is
energized. The power transformer is turned on,
microwaveenergyisproducedandfirststageisstarted.
The16 seconds isthe coolingtime required toremove
any vapor from the oven cavity and sensor.
NOTE: During this first stage, do not open the door or
touch STOP/CLEAR pad.
4. When the sensor detects the vapor emitted from the
food,thedisplayswitchesovertotheremainingcooking
time and the timer counts down to zero.
At this time, the door may be opened to stir food, turn
it or season, etc.
5. Whenthetimerreacheszero,anaudiblesignalsounds.
Theshut-offrelayandcookrelayarede-energizedand
the power transformer, oven lamp, etc. are turned off.
6. Opening the door or touching the STOP/CLEAR pad,
the time of day will reappear on the display and the
oven will revert to an OFF condition.
DOOR OPEN MECHANISM
The door is opened by pushing the open button on the
control panel, refer to the Figure D-1.
When the open button is pushed, the open button pushes
up the switch lever, and then the switch lever pushes up
thethelatchhead.Thelatchheadsaremovedupwardand
released from latch hook. Now the door will open.
Latch Hook
2nd. Latch
Switch
Monitor
Switch
Stop
Switch
Switch
Lever
Latch
Heads
Door
1st. Latch
Switch
Figure D-1. Door Open Mechanism
1ST.LATCHSWITCH,2ND. LATCHSWITCHAND
STOP SWITCH
1. Whentheovendoorisclosed,thecontacts(COM-NO)
must be closed.
2. When the oven door is opened, the contacts .(COM-
NO) must be opened.
MONITOR SWITCH
1. Whentheovendoorisclosed,thecontacts(COM-NC)
must be opened.
2. When the oven door is opened, the contacts (COM-
NC) must be closed.
3. Iftheovendoorisopenedandthecontacts(COM-NO)
ofthe1st.latchswitchand2nd.latchswitchfailtoopen,
the fuse M8A blows simultaneously with closing the
contacts (COM-NC) of the monitor switch.
CAUTION: BEFOREREPLACINGABLOWNFUSEM8A
TEST THE 1ST. LATCH SWITCH, 2ND.
LATCH SWITCH MONITOR SWITCH AND
MONITOR RESISTOR FOR PROPER OP-
ERATION.
MONITOR RESISTOR R 0.8Ω20W
ThemonitorresistorpreventsthefuseM8Aburstingwhen
the fuse M8A blows due to the operation of the monitor
switch.
ASYMMETRIC RECTIFIER
The asymmetric rectifier is a solid state device that pre-
vents current flow in both directions. And it prevents the
temperature rise of the power transformer by blowing the
fuse M8A when the high voltage rectifier is shorted.
D2 D1
ASYMMETRIC
RECTIFIER HIGH VOLTAGE
RECTIFIER
The rated peak reverse voltage of D1 of the asymmetric
rectifieris6KVTheratedpeakreversevoltageofD2ofthe
asymmetricrectifieris1.7KV.D1andD2ofthe asymmet-
ric rectifier or high voltage rectifier are shorted when the
each peak reverse voltage goes beyond the each rated
peak reverse voltage. (The process of blowing the fuse
M8A.)
FUNCTION OF IMPORTANT COMPONENTS
MICROWAVE
AH SENSOR
MICROWAVE

R-380A
6
1. The high voltage rectifier is shorted by any causes
when microwave cooking.
2. The peak reverse voltage of D2 of the rectifier goes
beyond the rated peak reverse voltage 1.7 KV in the
voltage doubler circuit.
3. D2 of the rectifier is shorted.
4. Thelargeelectriccurrentsflowthroughthehighvoltage
winding of the power transformer.
5. Thelarge electriccurrents beyond8A flowthrough the
primary winding of the power transformer.
6. The fuse M8A blows by the large electric currents.
7. The power supply to all the electrical parts are cut off.
FUSE M8A
1. The fuse M8A blows when the contacts (COM-NO) of
the 1st. latch switch and 2nd. latch switch remain
closed with the oven door open and when the monitor
switch closes.
2. The fuse M8A also blows when asymmetric rectifier,
H.V. rectifier, H.V. wire harness, H.V.capacitor,
magnetronorsecondarywindingofpowertransformer
is shorted.
3. If the wire harness or electrical components are short-
circuited, this fuse M8A blows to prevent an electric
shock or fire hazard.
OVEN THERMAL CUT-OUT
Thethermal cut-out, located onthe top of theoven cavity,
is designed to prevent damage to the oven by fire. If the
foods load is overcooked, by either error in cook time or
defect in the control unit, the thermal cut-out will open.
Undernormaloperation,theoventhermalcut-outremains
closed.However,whenabnormallyhightemperaturesare
reached within the oven cavity, the oven thermal cut-out
will open at 125˚C, causing the oven to shut down. The
defective thermal cut-out must be replaced with new one.
MAGNETRON THERMAL CUT-OUT
The thermal cut-out located near the magnetron is de-
signed to prevent damage to the magnetron if an over
heated condition develops in the tube due to cooling fan
failure,obstructedairguide,dirtyorblockedairintake,etc.
Under normal operation, the thermal cut-out remains
closed.However,whenabnormallyhightemperaturesare
reached within the magnetron, the thermal cut-out will
open at 95˚C causing the oven to shut down, when the
magnetronhas cooledto75˚C, thethermal cut-outcloses
and cook cycle will resume.
TURNTABLE MOTOR
Theturntablemotordrivestheturntablerollerassemblyto
rotate the turntable.
FAN MOTOR
Thefanmotordrivesabladewhichdrawsexternalcoolair.
Thiscool air is directedthrough the airvanes surrounding
the magnetron and cools the magnetron. This air is
channeled through the oven cavity to remove steam and
vapors given off from the heating foods. It is then ex-
hausted through the exhausting air vents at the oven
cavity
NOISE FILTER
The noise filter prevents the radio frequency interference
that might flow back in the power circuit.

R-380A
7
SERVICING
WARNING TO SERVICE PERSONNEL
Microwaveovenscontaincircuitrycapableofproducingveryhighvoltageandcurrent,contactwithfollowingparts
of the high voltage circuit will result in electrocution. High voltage capacitor, Power transformer, Magnetron, High
voltage rectifier assembly, High voltage harness.
REMEMBER TO CHECK 4R
1) Reconnect all leads removed from components
during testing.
2) Replace the outer case (cabinet).
3) Reconnect the supply.
4) Run the oven. Check all functions.
Microwave ovens should not be run empty. To test for
the presence of microwave energy within a cavity,
place a cup of cold water on the oven turntable, close
the door and set the microwave timer for two (2)
minutes. Set the power level to HIGH and push the
START button. When the two minutes has elapsed
(timeratzero)carefullycheckthatthewaterisnowhot.
If the water remains cold carry out 3D checks and re-
examine the connections to the component being
tested.
REMEMBER TO CHECK 3D
1) Disconnect the supply.
2) Door opened, and wedged open.
3) Discharge high voltage capacitor.
WARNING: AGAINST THE CHARGE OF THE
HIGH-VOLTAGE CAPACITOR
Thehigh-voltagecapacitorremainschargedabout
60 seconds after the oven has been switched off.
Wait for 60 seconds and then short-circuit the
connectionofthehigh-voltagecapacitor(thatis,of
the connecting lead of the high-voltage rectifier)
against the chassis with the use of an insulated
screwdriver.
Sharprecommendthatwhereverpossiblefault-finding
is carried out with the supply disconnected. It may in,
some cases, be necessary to connect the supply after
the outer case has been removed, in this event carry
out 3D checks and then disconnect the leads to the
primary of the power transformer. Ensure that these
leads remain isolated from other components and the
ovenchassis.(Useinsulationtapeifnecessary.)When
the testing is completed carry out 3D checks and
reconnect the leads to the primary of the power trans-
former.
When all service work is completed, and the oven is fully assembled, the microwave power output should be
checked and microwave leakage test carried out
When troubleshooting the microwave oven, it is helpful to
follow the Sequence of Operation in performing the
checks.Manyofthepossiblecausesoftroublewillrequire
that a specific test be performed. These tests are given a
procedure letter which will be found in the "Test
Procedure"section.
IMPORTANT: If the oven becomes inoperative because
ofablownfuseM8Ainthe1st.latchswitch
-2nd.latch switch-monitor switch-moni-
tor resistor circuit, check the 1st. latch
switch, 2nd. latch switch, monitor switch
and monitor resistor before replacing the
fuse M8A.
TROUBLESHOOTING GUIDE

R-380A
8
Home fuse blows when power
supplycordispluggedintowall
outlet.
FUSE M8A blows when power
supplycordispluggedintowall
outlet.
Display does not show any-
thing when power supply cord
is plugged into wall outlet.
Display doesnotoperateprop-
erly when STOP/CLEAR pad
is touched.
Oven lamp does not light at
door opened. (Display ap-
pears.)
Oven does not start when the
START pad is touched. (Dis-
play appears)
Oven lamp does not light (Dis-
play appears.)
Fan motor does not operate.
(Display appears.)
Turntablemotorassemblydoes
notoperate.(Displayappears.)
Oven or any electrical parts
does not stop when cooking
time is 0 or STOP/CLEAR pad
is touched.
Oven seems to be operating
butlittleornoheatis produced
inovenload.(Microwavepower
level is set at HIGH)
Oven does not seems to be
operating properly when ME-
DIUM HIGH, MEDIUM, ME-
DIUM LOW or LOW is set.
(Oven operates properly at
HIGH and then the STOP/
CLEARpadistouchedtheoven
stops.)
Oven goes into cook cycle but
shutsdownbeforeendofcook-
ing cycle.
Oven stops as soon as when
the START pad is touched.
AHsensordoesnotendduring
Sensor Cooking condition.
(Oven does not shut off after a
cup of water is boiling by sen-
sor cooking.
Oven stops at 16 sec. after
starting.
TEST PROCEDURE
CK = Check / RE = Replace
POSSIBLE CAUSE
AND
DEFECTIVE PARTS
CONDITION PROBLEM
ON
CONDITION
OFF
CONDITION
MAGNETRON
POWER TRANSFORMER
H.V. RECTIFIER ASSEMBLY
HIGH VOLTAGE CAPACITOR
1ST. LATCH SWITCH
2ND. LATCH SWITCH
STOP SWITCH
MONITOR SWITCH
MONITOR RESISTOR
THERMAL CUT-OUT 95˚C /125˚C
FAN MOTOR
TURNTABLE MOTOR
FUSE M8A
TOUCH CONTROL PANEL
KEY UNIT
RELAY (RY-1, RY-2)
FOIL PATERN ON P.W.B.
POWER SUPPLY CORD
SHORTED WIRE HARNESS
OPENED WIRE HARNESS
OVEN LAMP OR SOCKET
WALL OUTLET
MISADJUSTMENT SWITCH
HOME FUSE OR BREAKER
BLOCKED COOLING FAN
BLOCKED VENTILATION
NOISE FILTER
AH SENSOR
SENSOR
COOKING
CONDITION
ABC
D
EEEEGFHHIK LMN
RE CK CKRE CK CKCK CK CK
JO

R-380A
9
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
AMAGNETRON TEST
NEVER TOUCH ANY PART IN THE CIRCUIT WITH YOUR HAND OR AN INSULATED TOOL
WHILE THE OVEN IS IN OPERATION.
CARRY OUT 3D CHECK.
Isolatethe magnetron from highvoltage circuit byremoving all leadsconnected to filament terminal.
Totestforanopencircuitfilamentuseanohmmetertomakeacontinuitytestbetweenthemagnetron
filament terminals, the meter should show a reading of less than 1 ohm.
Totestforshortfilamenttoanodecondition,connectohmmeterbetweenoneofthefilamentterminals
and the case of the magnetron (ground). This test should be indicated an infinite resistance. If a low
or zero resistance reading is obtained then the magnetron should be replaced.
MICROWAVE OUTPUT POWER (1 Litre water load)
The following test procedure should be carried out with the microwave oven in a fully assembled
condition (outer case fitted). Microwave output power from the magnetron can be measured by way
of IEC 705, i.e. it can be measured by using water load how much it can be absorbed by the water
load.Tomeasurethemicrowaveoutputpowerinthemicrowaveoven,therelationofcalorieandwatt
is used. When P(W) heating works for t(second), approximately P x t/4.187 calorie is generated. On
theotherhand, ifthetemperature ofthewater withV(ml)rises∆T(°C)duringthis microwaveheating
period, the calorie of the water is V x ∆T.
The formula is as follows;
P x t / 4.187 = V x ∆T P (W) = 4.187 x V x ∆T / t
Our condition for water load is as follows:
Room temperature ......... around 20°C Power supply Voltage........... Rated voltage
Water load........ 1000 g Initial temperature ........ 10±2°C Heating time.......42 sec.
P = 100 x ∆T
Measuring condition:
1. Container
The water container must be a cylindrical borosilicate glass vessel having a maximum material
thickness of 3 mm and an outside diameter of approximately 190 mm.
2. Temperature of the oven and vessel
The oven and the empty vessel are at ambient temperature prior to the start the test.
3. Temperature of the water
The initial temperature of the water is (10±2)°C.
4. Select the initial and final water temperature so that the maximum difference between the final
water temperature and the ambient temperature is 5˚C.
5. Selectstirringdevicesandmeasuringinstrumentsinordertominimizeadditionorremovalofheat.
6. The graduation of the thermometer must be scaled by 0.1°C at minimum and accurate
thermometer.
7. The water load must be (1000±5) g.
8. “t”ismeasuredwhilethemicrowavegeneratorisoperatingatfullpower.Magnetronfilamentheat-
up time is not included.
NOTE: The operationtime ofthemicrowave ovenis “t+2” sec.2 sec.ismagnetron filamentheat-up time.
Measuring method:
1. Measure the initial temperature of the water before the water is added to the vessel.
(Example: The initial temperature T1 = 11°C)
2. Add the 1 litre water to the vessel.
3. Place the load on the centre of the shelf.
4. Operate the microwave oven at HIGH for the temperature of the water rises by a value ∆T of
(10 ±2)˚C.
5. Stir the water to equalize temperature throughout the vessel.
6. Measure the final water temperature. (Example: The final temperature T2 = 21°C)
7. Calculate the microwave power output P in watts from above formula.

R-380A
10
Initial temperature............................................................................................. T1 = 11°C
Temperature after (42 + 2) = 44 sec................................................................. T2 = 21°C
Temperature difference Cold-Warm ............................................................... ∆T1 = 10°C
Measured output power
The equation is “P = 100 x ∆T”............................................ P = 100 x 10°C = 1000 Watts
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
JUDGMENT: The measured output power should be at least ±15 % of the rated output power.
CAUTION: 1°C CORRESPONDS TO 100 WATTS REPEAT MEASUREMENT IF THE POWER IS
INSUFFICIENT.
1000g
1000g
1000g
T1˚C T2˚C
Heat up for44 sec.
B POWER TRANSFORMER TEST
WARNING: Highvoltagesandlargecurrentsarepresentatthesecondarywindingandfilament
winding of the power transformer. It is very dangerous to work near this part when
the oven is on. NEVER make any voltage measurements of the high-voltage
circuits, including the magnetron filament.
CARRY OUT 3D CHECKS.
Disconnect the leads to the primary winding of the power transformer. Disconnect the filament and
secondary winding connections from the rest of the HV circuitry. Using an ohmmeter, set on a low
range, it is possible to check the continuity of all three windings. The following readings should be
obtained:
a. Primary winding ................... approx. 1.3 Ω
b. Secondary winding............... approx. 96 Ω
c. Filament winding .................. less than 1Ω
If the reading obtained are not stated as above, then the power transformer is probably faulty and
should be replaced.
CARRY OUT 4R CHECKS.
C HIGH VOLTAGE RECTIFIER ASSEMBLY TEST
HIGH VOLTAGE RECTIFIER TEST
CARRY OUT 3D CHECKS.
IsolatethehighvoltagerectifierassemblyfromtheHVcircuit.Thehighvoltagerectifier canbetested
using an ohmmeter set to its highest range. Connect the ohmmeter across the terminal B+C of the
high voltage rectifier and note the reading obtained. Reverse the meter leads and note this second
reading.Thenormalresistanceisinfiniteinonedirectionandmorethan100kΩintheotherdirection.
CARRY OUT 4R CHECKS.
ASYMMETRIC RECTIFIER TEST
CARRY OUT 3D CHECKS.
Isolate the high voltage rectifier assembly from the HV circuit. The asymmetric can be tested using
an ohmmeter set to its highest range across the terminals A+B of the asymmetric rectifier and note
AB
C
D2 D1
ASYMMETRIC
RECTIFIER
HIGH VOLTAGE RECTIFIER

R-380A
11
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
the reading obtained. Reverse the meter leads and note this second reading. If an open circuit is
indicated in both direction then the asymmetric rectifier is good. If an asymmetric rectifier is shorted
in either direction, then the asymmetric rectifier is probably faulty and must be replaced with high
voltage rectifier. When the asymmetric rectifier is defective, check whether magnetron, high voltage
rectifier, high voltage wire or filament winding of the power transformer is shorted.
CARRY OUT 4R CHECKS.
NOTE: FORMEASUREMENT OF THE RESISTANCEOF THE RECTIFIER, THEBATTERIES OF THE
MEASURING INSTRUMENT MUST HAVE A VOLTAGE AT LEAST 6 VOLTS, BECAUSE
OTHERWISE AN INFINITE RESISTANCE MIGHT BE SHOWN IN BOTH DIRECTIONS.
D HIGH VOLTAGE CAPACITOR TEST
CARRY OUT 3D CHECKS.
A. Isolate the high voltage capacitor from the circuit.
B. Continuity check must be carried out with measuring instrument which is set to the highest resistance
range.
C. A normal capacitor shows continuity for a short time (kick) and then a resistance of about 10MΩafter
it has been charged.
D. A short-circuited capacitor shows continuity all the time.
E. Anopencapacitorconstantlyshowsaresistanceabout10MΩbecauseofitsinternal10MΩresistance.
F. When the internal wire is opened in the high voltage capacitor shows an infinite resistance.
G. The resistance across all the terminals and the chassis must be infinite when the capacitor is normal.
If incorrect reading are obtained, the high voltage capacitor must be replaced.
CARRY OUT 4R CHECKS.
ESWITCH TEST
CARRY OUT 3D CHECKS.
Isolate the switch to be tested and using an ohmmeter check between the terminals as described in the
following table.
Table: Terminal Connection of Switch
Plunger Operation COM to NO COM to NC COM; Common terminal
Released Open circuit Short circuit NO; Normally open terminal
Depressed Short circuit Open circuit NC; Normally close terminal
If incorrect readings are obtained, make the necessary switch adjustment or replace the switch.
CARRY OUT 4R CHECKS.
CARRY OUT 3D CHECKS.
Disconnect the leads from the terminals of the temperature fuse or thermal cut-out. Then using an
ohmmeter, make a continuity test across the two terminals as described in the table below.
CARRY OUT 4R CHECKS.
Table: Temperature fuse and Thermal cut-out Test
Temperature of "ON" condition Temperature of "OFF" condition Indication ofohmmeter
Parts Name (closed circuit) (˚C) (open circuit) (˚C) (When room temperature
is approx. 20˚C)
Thermal cut-out 125˚C This is not resetable type. Above 125˚C Closed circuit.
Thermal cut-out 95˚C Below 75˚C Above 95˚C Closed circuit.
If incorrect readings are obtained, replace the temperature fuse or thermal cut-out.
Anopen circuitthermalcut-out 95˚C(MG) indicatesthatthe magnetronhas overheated,thismay be
duetoresistrictedventilation,coolingfanfailureorafaultconditionwithinthemagnetronorHVcircuit.
An open circuit thermal cut-out 125˚C (OVEN) indicates that the foods in the oven may catch fire,
FTEMPERATURE FUSE AND THERMAL CUT-OUT TEST

R-380A
12
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
this may be due to over heating produced by improper setting of the cooking time or failure of the
control panel.
CARRY OUT 3D CHECKS.
Disconnect the leads from the monitor resist. Using an ohmmeter and set on a low range. Check
between the terminals of the monitor resistor.
The resistance of monitor resistor is approx. 0.8 ohms.
If incorrect readings are obtained, replace the monitor resistor.
CARRY OUT 4R CHECKS.
G MONITOR RESISTOR TEST
CARRY OUT 3D CHECKS.
Disconnect the leads from the motor.
Usinganohmmeter,checktheresistancebetweenthetwoterminalsasdescribedinthetablebelow.
Table: Resistance of Motor
Motors Resistance
Fan motor Approximately 390 Ω
Turntable motor Approximately 16.08 kΩ
If incorrect readings are obtained, replace the motor.
CARRY OUT 4R CHECKS
HMOTOR WINDING TEST
CARRY OUT 3D CHECKS.
1. If the fuse M8A is blown, there could be shorts or ground in electrical parts or wire harness.
Check them and replace the defective parts or repair the wire harness.
2. IfthefuseM8A isblownwhenthe doorisopened,checkthe 2nd.latchswitch,monitor switchand
monitor resistor.
If the fuse M8A is blown by incorrect door switching replace the defective switch(s) and the fuse
M8A.
3. If the fuse M8A is blown, there could be a short in the asymmetric rectifier or there could be a
ground in wire harness. A short in the asymmetric rectifier may have occured due to short or
ground in H.V. rectifier, magnetron, power transformer or H.V. wire. Check them and replace the
defective parts or repair the wire harness.
CARRY OUT 4R CHECKS.
CAUTION: ONLY REPLACE FUSE M8A WITH THE CORRECT VALUE REPLACEMENT
IBLOWN FUSE F M8A
JNOISE FILTER TEST
CARRY OUT 3D CHECKS.
Disconnect the leads from the terminals of the noise
filter. Using an ohmmeter, check between the termi-
nals as described in the following table.
MEASURING POINT INDICATION OF
OHMMETER
Between N and L Open circuit
Between terminal N and WHITE Short circuit
Between terminal L and RED Short circuit
N
LCx L
L
Cy
WHT
RED
L (min) Cx ±20% Cy ±20%
600µH 0.068µF 0.0022µF

R-380A
13
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
If incorrect readings are obtained, replace the noise filter unit.
CARRY OUT 4R CHECKS.
L KEY UNIT TEST
If the display fails to clear when the STOP/CLEAR pad is depressed, first verify the flat ribbon cable
ismakinggoodcontact,verifythatthedoorsensingswitch(stopswitch)operatesproperly;thatisthe
contacts are closed when the door is closed and open when the door is open.
If the door sensing switch (stop switch) is good, disconnect the flat ribbon that connects the key unit
tothe control unitand make surethe door sensingswitch is closed(either close thedoor or short the
doorsensingswitchconnector).Usethekeyunitmatrixindicatedonthecontrolpanelschematicand
place a jumper wire between the pins that correspond to the STOP/CLEAR pad making momentary
contact.Ifthecontrolunitrespondsbyclearingwithabeepthekeyunitisfaultyandmustbereplaced.
If the control unit does not respond, it is faulty and must be replaced.
If a specific pad does not respond, the above method may be used (after clearing the control unit) to
determine if the control unit or key pad is at fault.
K TOUCH CONTROL PANEL ASSEMBLY TEST
ThetouchcontrolpanelconsistsofcircuitsincludingsemiconductorssuchasLSI,ICs,etc.Therefore,
unlike conventional microwave ovens, proper maintenance cannot be performed with only a
voltmeterandohmmeter.Inthisservicemanual,thetouchcontrolpanelassemblyisdivided intotwo
units, Control Unit and Key Unit, and also the Control Unit is divided into two units, CPU Unit and
Power Unit, and troubleshooting by unit replacement is described according to the symptoms
indicated.
1. Key Unit. Note: Check key unit ribbon connection before replacement.
The following symptoms indicate a defective key unit. Replace the key unit.
a) When touching the pads, a certain pad produces no signal at all.
b) When touching a number pad, two figures or more are displayed.
c) When touching the pads, sometimes a pad produces no signal.
2. Control Unit.
Thefollowingsymptomsindicateadefectivecontrolunit.Beforereplacingthecontrolunit,perform
the Key unit test (Procedure L) to determine if control unit is faulty.
2-1 In connection with pads.
a) When touching the pads, a certain group of pads do not produce a signal.
b) When touching the pads, no pads produce a signal.
2-2 In connection with indicators.
a) At a certain digit, all or some segments do not light up.
b) At a certain digit, brightness is low.
c) Only one indicator does not light.
d) The corresponding segments of all digits do not light up; or they continue to light up.
e) Wrong figure appears.
f) A certain group of indicators do not light up.
g) The figure of all digits flicker.
2-3 Other possible troubles caused by defective control unit.
a) Buzzer does not sound or continues to sound.
b) Clock does not operate properly.
c) Cooking is not possible.
G 8
RICE
CLOCK
SOUP
MORE
TIMER
PIZZA
MEAT
HELP
POWER
LEVEL
STOP
CLEAR
DINNER
PLATE
SLOW
COOK
MEMORY
RICE /
PASTA
LESS
PIE
VEGETABLES
CASSEROLE
DESSERTS
EASY
DEFROST
G 7
2
7
34
9
5
08
1
6
G 6 G 5 G 4 G 3 G 2 G 1
G12 G11 G10
G 9
START
INSTANT
COOK

R-380A
14
CARRY OUT 3D CHECKS.
Remove the outer case and check voltage between Pin No 3 of the 2-pin connector (A) and the
commonterminaloftherelayRY2onthepowerunitwithanA.C.voltmeter.Themetershouldindicate
230 - 240 volts, if not check oven circuit.
RY1 and RY2 Relay Test
These relays are operated by D.C. voltage.
Check voltage at the relay coil with a D.C. voltmeter during the microwave cooking operation or
convection cooking operation.
DC. voltage indicated ............... Defective relay.
DC. voltage not indicated ......... Checkdiodewhichisconnectedtotherelaycoil.Ifdiodeisgood,
control unit is defective.
RELAY SYMBOL OPERATIONAL VOLTAGE CONNECTED COMPONENTS
RY1 APPROX. 24.5V D.C. Oven lamp / Turntable motor / Cooling fan motor
RY2 APPROX. 24.0V D.C. Power transformer
CARRY OUT 4R CHECKS.
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
M RELAY TEST
To protect the electronic circuits, this model is provided with a fine foil pattern added to the primary
onthePWB, thisfoilpattern actsasa fuse.Ifthe foilpatternisopen, followthetroubleshooting guide
given below for repair.
Problem: POWER ON, indicator does not light up.
CARRY OUT 3D CHECKS.
STEPS OCCURRENCE CAUSE OR CORRECTION
1 The rated AC voltage is not present between Check supply voltage and oven power cord.
Pin No. 3 of the 2-pin connector (A) and the
common terminal of the relay RY2.
2 The rated AC voltage is present to primary Low voltage transformer or secondary circuit defective.
side of low voltage transformer. Check and repair.
3 Only pattern at "a" is broken. *Insert jumper wire J1 and solder.
4 Pattern at "a" and "b" are broken. *Insert the coil RCILF2003YAZZ between "c" and "d".
NOTE: *At the time of making these repairs,
makea visualinspectionof thevaristor.
Checkforburned damageandexamine
the transformer with a tester for the
presence of layer short-circuit (check
the primary coil resistance). If any ab-
normal condition is detected, replace
the defective parts.
CARRY OUT 4R CHECKS.
N PROCEDURES TO BE TAKEN WHEN THE FOIL PATTERN ON THE PRINTED WIRING BOARD
(PWB) IS OPEN
RY2
a
b
cd
HVT
AC
(COM)
VH
XH
3
3
CN - A
(J1)
Checking the initial sensor cooking condition
(1) The oven should be plugged in at least two minutes before sensor cooking.
(2) Room temperature should not exceed 35˚C.
(3)Theunit shouldnotbeinstalled inanyarea whereheatandsteam aregenerated.The unitshould
not be installed, for example, next to a conventional surface unit. Refer to the "INSTALLATION
Instructions" .
(4) Exhaust vents are provided on the back of the unit for proper cooling and air flow in the cavity. To
OAH SENSOR TEST

R-380A
15
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
permitadequateventilation,besuretoinstallsoasnottoblockthesevents.Thereshouldbesome
space for air circulation.
(5) Be sure the exterior of the cooking container and the interior of the oven are dry. Wipe off any
moisture with a dry cloth or paper towel.
(6) The Sensor works with food at normal storage temperature. For example, chicken pieces would
be at refrigerator temperature and canned soup at room temperature.
(7) Avoid using aerosol sprays or cleaning solvents near the oven while using Sensor settings. The
sensor will detect the vapour given of by the spray and turn off before food is properly cooked.
(8) If the sensor has not detected the vapour of the food, ERROR will appear and the oven will shut
off.
Water load cooking test
Makesuretheovenhasbeenpluggedinatleastfiveminutesbeforecheckingsensorcookoperation.
The cabinet should be installed and screws tightened.
(1) Fill approximately 200 milliliters (7.2 oz) of tap water in a 1000 milliliter measuring cup.
(2) Place the container on the center of tray in the oven cavity.
(3) Close the door.
(4) Touch SOUP pad of SENSOR INSTANT REHEAT once. Now, the oven is in the sensor cooking
condition and "SOUP", "SENSOR" and "REHEAT" will appear in the display.
(5) The oven will operate for the first 16 seconds, without generating microwave energy.
NOTE: ERROR will appear if the door is opened or STOP/CLEAR pad is touched during first stage
of sensor cooking.
(6) After approximately 16 seconds, microwave energy is produced, and the display should start to
countdown theremaining cookingtime, andoven shouldturn offafter wateris boiling(bubbling).
If the oven does not turn off, replace the AH sensor or check the control unit, refer to explanation
below.
TESTING METHOD FOR AH SENSOR AND/OR CONTROL UNIT
To determine if the sensor is defective, the simplest method is to replace it with a new replacement
sensor.
(1) Disconnect oven from power supply and remove outer case.
(2) Discharge the high voltage capacitor.
(3) Remove the AH sensor.
(4) Install the new AH sensor.
(5) Re-install the outer case.
(6)Reconnecttheoventothepowersupplyandcheckthesensorcookoperationproceedasfollows:
6-1. Fill approximately 200 milliliters (7.2 oz) of tap water in a 1000 milliliter measuring cup.
6-2. Place the container on the center of tray in the oven cavity.
6-3. Close the door.
6-4. Touch SOUP pad once.
6-5. The control panel is in automatic Sensor operation.
6-6. The display will start to count down the remaining cooking time, and the oven will turn off
automatically after the water is boiling (babbling).
If new sensor dose not operate properly, the problem is with the control unit.
CHECKING CONTROL UNIT
(1) Disconnect oven from power supply and remove outer case.
(2) Discharge the high voltage capacitor.
(3) Disconnect the wire leads from the cook relay.
(4) Disconnect the sensor connector that is mounted to lower portion of control panel.
(5) Then connect the dummy resistor circuit (see fig.) to the sensor connector of control panel.
(6)Reconnecttheoventothepowersupplyandcheckthesensorcookoperation,proceedasfollows:
6-1. Touch SOUP pad once.
6-2. The control panel is in the sensor cooking operation.
6-3. After approximately 20 seconds, push plunger of select switch. This condition is same as
judgement by AH sensor.
6-4.Afterapproximately3seconds,thedisplayshows"XX.XX"whichistheremainingcooking
time, and the display count down.

R-380A
16
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
If the above is not the case, the control unit is probably defective.
If the above is proper, the AH sensor is probably defective.
R1,R2 : 22Ω±1% 1/2W
R3 : 4.3kΩ±5% 1/4W
R4 : 1MΩ±5% 1/4W
Plunger
NC
NO
COM
COM NO
NC
R3 R4
R1
R2
1
2
3
F-1
F-2
F-3
To connector (F)
on Control Unit.
CONNECTOR
Sensor Dummy Resistor Circuit
TOUCH CONTROL PANEL ASSEMBLY
OUTLINE OF TOUCH CONTROL PANEL
The touch control section consists of the following units.
(1) Key Unit
(2) Control Unit (The Control Unit consists of Power Unit
and CPU Unit).
The principal functions of these units and the signals
communicated among them are explained below.
Key Unit
Thekeyunitiscomposedofamatrix,signalsgeneratedin
the LSI are sent to the key unit through P20 - P27.
Whena keypadis touched,a signaliscompleted through
thekeyunitandpassedbacktothe LSIthroughP74-P77
to perform the function that was requested.
Control Unit
Control unit consists of LSI, ACL circuit, indicator circuit,
powersource circuit,relay circuit, buzzercircuit, synchro-
nizing signal circuit, absolute humidity sensor circuit and
back light circuit.
1) ACL
This circuit generates a signal which resets the LSI to
the initial state when power is supplied.
2) Indicator Circuit
This circuit consists of 25 segments and 4 common
electrodes using a Liquid Crystal Display.
3) Power Source Circuit
Thiscircuitgeneratesvoltagesnecessaryinthecontrol
unit from the AC line voltage.
In addition, the synchronizing signal is available in
order to compose a basic standard time in the clock
circuit.
Symbol Voltage Application
VC -5.3V LSI(IC1)
4) Relay Circuit
A circuit to drive the magnetron, fan motor, turntable
motor and light the oven lamp.
5) Buzzer Circuit
ThebuzzerisresponsivetosignalsfromtheLSItoemit
audible sounds (key touch sound and completion
sound).
6) Synchronizing Signal Circuit
The power source synchronizing signal is available in
order to compose a basic standard time in the clock
circuit. It accompanies a very small error because it
works on commercial frequency.
7) Door Sensing Switch
A switch to "tell" the LSI if the door is open or closed.
8) Back Light Circuit
A circuit to drive the back light (Light emitting diodes
LD1 - LD5).
9) Absolute Humidity Sensor Circuit
This circuit detects moisture of the cooking food to
allow its automatic cooking.

R-380A
17
DESCRIPTION OF LSI
LSI(IZA778DR):
The I/O signal of the LSI(IZA778DR) is detailed in the following table.
Pin No. Signal I/O Description
A
B
0.12 sec.
2.4 sec.
H : GND
L : -5V
H : GND
L : -5V
1 C1 IN Terminal not used.
2 VL1 IN Power source voltage input terminal.
Standard voltage for LCD.
3-6 AN7-AN4 IN Terminal to change cooking constant according to the Model.
ByusingtheA/DconvertercontainedintheLSI,DCvoltageinaccordancewiththe
Model in operation is applied to set up its cooking constant.
7 AN3 OUT Terminal not used.
8 AIN2 IN Toinputsignalwhichcommunicatesthedooropen/closeinformationtoLSI.
Door closed; "H" level signal (0V).
Door opened; "L" level signal (-5V).
9 AN1 IN AH sensor input.
This input is an analog input terminal from the AH sensor circuit, and connected
the A/D converter built into the LSI.
10 AN0 IN Usedforinitialbalancingofthebridgecircuit(absolutehumiditysensor).Thisinput
is an analog input terminal from the AH sensor circuit, and connected to the A/D
converter built into the LSI.
11-13 P57-P55 OUT Terminal not used.
14 P54 OUT Signal to sound buzzer (2.0kHz).
A: key touch sound.
B: Completion sound.
15-18 P53-P50 OUT Terminal not used.
19-23 P47-P43 OUT Used for initial balancing of the bridge circuit (absolute humidity sensor).
24 INT0 IN Signal synchronized with commercial power source frequency.
Thisisthebasictimingfortimeprocess-
ing of LSI.
25-26 P41-P40 OUT Terminal not used.
27 P77 IN Signal coming from touch key.
When either G12 line on key matrix is touched, a corresponding signal out of P20
-P27 willbe input intoP77. Whenno key istouched, thesignal isheld at "H"level.
28 P76 IN Signal similar to R77.
WheneitherG11lineonkeymatrixistouched,acorrespondingsignalwillbeinputintoR76.
29 P75 IN Signal similar to R77.
WheneitherG10lineonkeymatrixistouched,acorrespondingsignalwillbeinputintoR75.
30 P74 IN Signal similar to R77.
WheneitherG9lineonkeymatrixistouched,acorrespondingsignalwillbeinputintoR74.
31 P73 OUT Oven lamp, fan motor and turntable motor driving signal.
Toturn onandoff theshut-off relay(RY1).
Thesquare waveform voltageis delivered
to the relay RY1 driving circuit and RY2
control circuit.
32 P72 OUT Magnetron high-voltage circuit driving signal.
To turn on and off the cook relay
(RY2). The signals holds "L" level
during microwave cooking and "H"
levelwhilenotcooking.Inothercook-
ing modes (variable cooking) the sig-
nal turns to "H" level and "L" level in
repetitionaccordingtothepowerlevel.
33 P71 OUT Terminal not used.
34 P70 IN Connected to VC.
35 RESET IN Auto clear terminal.
Signal is input to reset the LSI to the initial state when power is supplied.
Temporarily set to "L" level the moment power is supplied, at this time the LSI is
reset. Thereafter set at "H" level.
20.0 msec.
H : GND
L : -5V
20.0 msec.
During cooking
H : GND
L : -5V
P-HI
H : GND
L : -5V
H : GND
L : -5V
P-70
ON
ON
OFF
OFF OFF
24 sec.
8 sec.

R-380A
18
36-37 P81-P80 OUT Terminal not used.
38 XIN IN Internal clock oscillation frequency input setting.
The internal clock frequency is set by inserting the ceramic filter oscillation circuit
with respect to XIN terminal.
39 XOUT OUT Internal clock oscillation frequency control output.
Output to control oscillation input of XOUT.
40 VSS IN Power source voltage: -5.1V.
VC voltage of power source circuit input.
41 P27 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G8 line keys on key matrix is touched.
42 P26 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G7 line keys on key matrix is touched.
43 P25 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G6 line keys on key matrix is touched.
44 P24 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G5 line keys on key matrix is touched.
45 P23 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G4 line keys on key matrix is touched.
46 P22 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G3 line keys on key matrix is touched.
47 P21 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G2 line keys on key matrix is touched.
48 P20 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to P74 - P77 terminal
while one of G1 line keys on key matrix is touched.
49-50 P17-P16 OUT Terminal not used.
51-62 SEG39-SEG28 IN Terminal not used.
63-66 SEG27-SEG24 OUT Segment data signals.
Connected to LCD.
The relation between signals are as follows:
LSI Signal (Pin No.) LCD (Pin No.) LSI Signal (Pin No.) LCD (Pin No.)
SEG 27 (63)............................. S0 SEG 12 (78) ............................. S5
SEG 26 (64)............................. S1 SEG 11 (79) ............................. S6
SEG 25 (65)............................. S2 SEG 10 (80) ............................. S7
SEG 24 (66)............................. S3 SEG 9 (81)............................... S8
SEG 22 (68)............................. S4 SEG 8 (82)............................... S9
SEG 21 (69)........................... S26 SEG 6 (84)............................. S10
SEG 20 (70)........................... S25 SEG 5 (85)............................. S11
SEG 19 (71)........................... S24 SEG 4 (86)............................. S12
SEG 18 (72)........................... S23 SEG 3 (87)............................. S13
SEG 17 (73)........................... S22 SEG 2 (88)............................. S14
SEG 16 (74)........................... S21 SEG 1 (89)............................. S15
SEG 14 (76)........................... S20 SEG 0 (90)............................. S16
SEG 13 (77)........................... S19
67 SEG23 OUT Terminal not used.
68-74 SEG22-SEG16 OUT Segment data signal.
Signal similar to SEG27.
75 SEG15 OUT Terminal not used.
76-82 SEG14-SEG8 OUT Segment data signal.
Signal similar to SEG27.
83 SEG7 OUT Terminal not used.
84-90 SEG6-SEG0 OUT Segment data signal.
Signal similar to SEG27.
91 VCC IN Connected to GND.
92 VREF IN Connected to GND.
Pin No. Signal I/O Description
Table of contents
Other Sharp Microwave Oven manuals

Sharp
Sharp R652BK User manual

Sharp
Sharp R-209 Instruction Manual

Sharp
Sharp R-753GX(BS) User manual

Sharp
Sharp SM327FHW User manual

Sharp
Sharp Carousel R-1874 User manual

Sharp
Sharp SMO1461GS User manual

Sharp
Sharp R-420CK User manual

Sharp
Sharp R-370EK User manual

Sharp
Sharp R-408EW User manual

Sharp
Sharp R-2110JK User manual