9. Specications
■ Display
● Digital display : Measured value / red LED 4 digits,
character height approx. 14.3 mm
Setting 1, 2 / green LED 4 digits,
character height approx. 8 mm
Other (higher limit, lower limit alarm, hysteresis 1, 2, dead
band (DB) / orange LED 2 digits, character height approx. 8
mm
● Status display : Output 1, 2 / green
For three-position type, green/red 2-color lamp, dead
band (DB) off
: higher limit, lower limit alarm / red
● Display accuracy : ± (0.25%FS + 1 digit)
Does not include cold junction temperature compensation
accuracy of thermocouple input
For details on accuracy, see “8. Measuring Range Codes.”
●
Range for maintaining
: 23°C±5°C (18 – 28°C)
display accuracy
● Display resolution : Differs according to measuring range (0.1, 1)
● Measured value : -10 – 110% of measuring range
display range However, Pt -200 – 600°C range is -240 – 680°C.
JPt -200 – 500°C range is -240 – 570°C.
● Display update cycle : 0.25 seconds
● Input scaling : 0 – 100.0 (linear input) standard
■ Setting
● Setting method : By operation of 4 or 8 front keys
● Setting range : Same as measuring range
■ Input
● Input type
● Thermocouple
: Selection by measuring range code (TC, Pt, mV, V, mA)
: B, R, S, K, E, J, T, N, PLⅡ,C(WRe5-26), (U, L (DIN43710)
Metal-chromel (AuFe-Cr)
: Min. input resistance 500kΩ
: Max. external resistance tolerance: 100Ω
: Burnout function: Standard equipment (up scale)
: Cold junction compensation accuracy (CJ error) ± 2°C
(within ambient temperature 5 – 45°C)
● R.T.D. : Pt100 / JPt100 3-wire type
: Amperage 0.25 mA
: Lead wire tolerable resistance
5Ω max. per wire (resistance for all wires must be equal)
● Voltage mV : -10 – 10, 0 – 10, 0 – 20, 0 – 50, 10 – 50, 0 – 100 mV DC
V : -1 – 1, 0 – 1, 0 – 2, 0 – 5, 1 – 5, 0 – 10 V DC
: Input resistance 500kΩ min.
● Current mA : 0 – 20, 4 – 20 mA DC
: Input resistance approx. 250Ω
● Sampling cycle : 0.25 seconds
● Isolation : No insulation between input and system; all others
insulated
■ Control
● Control mode : One-setting, two-position type control, two-setting,
two-position type control, three-position type control
●
Control output type/rating
:
Contact / 1c 240 V AC, 5A (resistive load), 2A (inductive
load)
: SSR drive voltage / 12V±1.5 V DC (max. load current
30 mA)
●
No. of control output points
: Output 1
: Output 2
● Hysteresis (DF) : Two-position type 0.1 – 9.9% FS
: Three-position type 0.2% FS xed
●
Action dead band (DB)
: 1 – 99% FS
(three-position type)
●
Control output characteristics
: RA (reverse characteristics) only
Relay output: Realized by NC terminal for cooling
● Isolation : Contact output insulated for all
: No insulation between SSR drive voltage and analog
output; all others insulated
■ Alarm output (optional)
●
Number of output points
: 2 (HL, LL)
● Type : HL higher limit alarm
LL Lower limit alarm
● Setting range : Higher limit alarm Without decimal point 0 – 99, no
With decimal point 0.0 – 99, no
(Note that decimal points cannot be
set for readings of 10 or higher.)
Lower limit alarm Without decimal point no, -99 – 0
With decimal point no, -99 – 0.0
(Note that decimal points cannot be
set for readings of -10 or lower.)
● Action : ON-OFF action
● Hysteresis : 0.2% FS xed
● Standby action : Standby action / no standby action
● Output type/rating : Contact 1a / 240 V AC, 2A (resistive load)
● Output updating cycle : 0.25 seconds
● Isolation : Insulated for all
● Selection conditions : Cannot be selected for two-setting, two-position type
■ Analog output (optional)
●
Number of output points
: 1
● Output type : Measured value
● Output range : Same as measuring range (xed)
Specication for lower limit value/higher limit value within
measuring range is possible (specify when ordering).
●
Output specications/rating
: Current 4 – 20 mA DC / max. load resistance 300Ω
Voltage 0 – 10 V DC / max. load current 2 mA
Voltage 0 – 10 mV DC, output resistance 10Ω
● Output accuracy : ±0.3%FS (for display value)
● Output resolution : Approx. 0.008% (1/13,000)
● Output updating cycle : 0.25 seconds
● Isolation : No insulation with control output P
■ General specifications
● Data storage : Non-volatile memory (EEPROM)
● Operating environment conditions
: Temperature -10–50°C
: Humidity 90%RH max. (no dew condensation)
: Elevation 2000 m above sea level or lower.
: Over voltage Category II
: Pollution degree 2 (IEC 60664)
● Storage temperature : -20 – 65°C
● Supply voltage : 100 – 240 V AC ± 10% 50/60 Hz
● Power consumption : Max. 14 VA for 100 – 240 V AC
●
Input/noise removal ratio
: Normal mode min. 50 dB (50/60 Hz)
: Common mode min. 130dB (50/60 Hz)
● Insulation resistance : Between input/output terminals and power terminal
● Dielectric strength : Between input/output terminals and power terminal
2300 V AC, 1 minute
Between power terminal and ground terminal
1500V AC, 1 minute
● Material of case : PPE resin (flame resistance UL94V-0)
● External dimensions : H96 x W96 x D120 mm (100 mm inside panel)
●
Protective structure
: Only front panel has dust-proof and dripproof
structure equivalent to IP66. (Panel thickness :1.2–3.2mm)
● Mounting : Push-in panel (one-touch mount)
● Panel thickness : 1.0 – 4.0 mm
● Panel cutout : H92 x W92 mm
● Weight : Approx. 340 g
500 V DC, 20 MΩ or above;
Between input/output terminals and ground terminal
500V DC, 20MΩ or above