Chapter 2 - Default Operation
Chapter 2 - Default Operation
Sequence of Operation
1. Run/Stop command comes from Digital Input 1 (Forward) or Digital Input 2
(Reverse). When DI1 is ON, the motor starts and runs forward. When DI2 is ON, the
motor starts and runs in reverse. If both DIs are turned On, the first DI which turns
ON controls the motor. The second DI to turn ON has no effect until the first turns
OFF. Then the motor spins in the other direction.
2. Motor speed is controlled using Analog Input 1 (0 to 10 Vdc) and/or Analog Input 1
(4-20 mA) (AI1 + AI2).
3. Motor Operating activates Digital Output 1.
4. Faults activate Digital Output 2.
Parameter Changes
Part. No. Value ParameterFunction FunctionSelection Document Reference
(DPD01149)
P6.5.1 OK Reset Factory Defaults Sect. 2.2.6.1
Yes Startup Wizard Enter appropriate data Sect. 1.1
M1 Quick Setup Enter appropriate motor data Sect. 3.3
Default I/O Parameter settings
P3.5.1.1 DigIN SlotA.1 Ctrl Signal 1 A DI1 Default Function Sect. 3.5.7.1
P3.5.1.2 DigIN SlotA.2 Ctrl Signal 2 A DI2 Default Function Sect. 3.5.7.1
P3.5.1.7 DigIN SlotA.3 Ext Fault Close DI3 Default Function Sect. 3.5.7.1
P3.5.1.15 DigIN SlotA.4 Preset Freq Sel0 DI4 Default Function Sect. 3.5.7.1
P3.5.1.16 DigIN SlotA.5 Preset Freq Sel1 DI5 Default Function Sect. 3.5.7.1
P3.5.1.9 DigIN SlotA.6 Fault Reset Close DI6 Default Function Sect. 3.5.7.1
P3.5.2.1 AnIN SlotA.1 AI1 Signal Sel AI1 Default location Sect. 3.5.7.2
P3.5.2.3 0-10v/0-20 mA AI1 Signal Range AI1 Default Range (0-10V)* Sect. 3.5.7.2
P3.5.2.7 AnIN SlotA.2 AI2 Signal Sel AI2 Default location Sect. 3.5.7.2
P3.5.2.9 2-10v/4-20 mA AI2 Signal Range AI1 Default Range (4-20 mA)* Sect. 3.5.7.2
P3.5.3.2.1 Run RO1 Function DO1 Default Function Sect. 3.5.7.3
P3.5.3.2.4 Fault RO2 Function DO2 Default Function Sect. 3.5.7.3
P3.5.3.2.7 Ready RO3 Function DO3 Default Function Sect. 3.5.7.3
P3.5.4.1.1 O/P Freq AO1 Function AO1 Default Function Sect. 3.5.7.5
P3.5.4.1.3 0 mA/0V AO1 Min Signal AO1 Default Range (0-20 mA)* Sect. 3.5.7.5
* - Switch settings on controller board determine physical input or output type (Voltage or Current).