manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens Desigo TRA QMX3.P36F User manual

Siemens Desigo TRA QMX3.P36F User manual

This manual suits for next models

1

Other Siemens Controllers manuals

Siemens SIMATIC FM 452 User manual

Siemens

Siemens SIMATIC FM 452 User manual

Siemens GDB 9E Series User manual

Siemens

Siemens GDB 9E Series User manual

Siemens Simatic S7 Series User guide

Siemens

Siemens Simatic S7 Series User guide

Siemens POS8.4420/109 User manual

Siemens

Siemens POS8.4420/109 User manual

Siemens RWF50.3 User manual

Siemens

Siemens RWF50.3 User manual

Siemens SIMATIC PN/BACnet LINK User manual

Siemens

Siemens SIMATIC PN/BACnet LINK User manual

Siemens SINUMERIK 802D sl User manual

Siemens

Siemens SINUMERIK 802D sl User manual

Siemens GBB 1 Series User manual

Siemens

Siemens GBB 1 Series User manual

Siemens GNA 1E Series User manual

Siemens

Siemens GNA 1E Series User manual

Siemens SQM50 series User manual

Siemens

Siemens SQM50 series User manual

Siemens ecofast 3RK1702-2GB18-0AA1 User manual

Siemens

Siemens ecofast 3RK1702-2GB18-0AA1 User manual

Siemens SINUMERIK 802D sl Parts list manual

Siemens

Siemens SINUMERIK 802D sl Parts list manual

Siemens SLX-ASC-PFCU User manual

Siemens

Siemens SLX-ASC-PFCU User manual

Siemens SIMATIC S5-100U User guide

Siemens

Siemens SIMATIC S5-100U User guide

Siemens SINUMERIK 840D sl Quick start guide

Siemens

Siemens SINUMERIK 840D sl Quick start guide

Siemens AVS75.39 Series User manual

Siemens

Siemens AVS75.39 Series User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens S7-1200 TELECONTROL User manual

Siemens

Siemens S7-1200 TELECONTROL User manual

Siemens 3RW51 Series User manual

Siemens

Siemens 3RW51 Series User manual

Siemens GGA Series User manual

Siemens

Siemens GGA Series User manual

Siemens Simatic S7-300 User manual

Siemens

Siemens Simatic S7-300 User manual

Siemens 3WX3666-7JA00 User manual

Siemens

Siemens 3WX3666-7JA00 User manual

Siemens SIMATIC S7-1200 CP 1243-8 IRC User guide

Siemens

Siemens SIMATIC S7-1200 CP 1243-8 IRC User guide

Siemens RVP540 Operator's manual

Siemens

Siemens RVP540 Operator's manual

Popular Controllers manuals by other brands

Digiplex DGP-848 Programming guide

Digiplex

Digiplex DGP-848 Programming guide

YASKAWA SGM series user manual

YASKAWA

YASKAWA SGM series user manual

Sinope Calypso RM3500ZB installation guide

Sinope

Sinope Calypso RM3500ZB installation guide

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

Isimet

Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS sv-ip5a user manual

LSIS

LSIS sv-ip5a user manual

Airflow Uno hab Installation and operating instructions

Airflow

Airflow Uno hab Installation and operating instructions

ABB ACS580-01 drives Hardware manual

ABB

ABB ACS580-01 drives Hardware manual

Panasonic GM1 Series Reference manual

Panasonic

Panasonic GM1 Series Reference manual

Emerson SW93 owner's manual

Emerson

Emerson SW93 owner's manual

AutoAqua Smart ATO micro SATO-120P manual

AutoAqua

AutoAqua Smart ATO micro SATO-120P manual

Panasonic FP? Positioning Unit RTEX Technical manual

Panasonic

Panasonic FP? Positioning Unit RTEX Technical manual

Alpha IP MIOB 21001 manual

Alpha IP

Alpha IP MIOB 21001 manual

Surecom SR-629 user manual

Surecom

Surecom SR-629 user manual

Regulus SRS1 T Installation and operation manual

Regulus

Regulus SRS1 T Installation and operation manual

3M MicroTouch EX113 reference guide

3M

3M MicroTouch EX113 reference guide

KUHN TKS user manual

KUHN

KUHN TKS user manual

S&C PMH Instructions for operation

S&C

S&C PMH Instructions for operation

Regin CORRIGO L10 manual

Regin

Regin CORRIGO L10 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

s
1601
1601p01en
1601p01en
Desigo™ TRA
Freely configurable
flush
-mounted room
operator unit for KNX
PL-Link
QMX3.P36F
QMX3.P36G
•Freely configurable user interface (keys and visual items) as part of Total
Room Automation
•Energy efficiency function ("Green Leaf ")
•Room temperature measurement
•Display of room temperature, control mode, scenes etc. (LCD)
•Backlit display, white or blue selection
•KNX PL-Link interface to the room automation station with plug & play
functionality
•Can be combined with different standard and design bezels
CM2N1601en_04
2016-03-24
Building Technologies
Use
The QMX3.P36... room operator unit is used as part of Desigo room automation to
measure the room temperature as well as to operate the room functions. The room
automation station determines the functions of both LCD display and keys.
The room operator unit can be used together with the Desigo TRA room
automation stations.
Type summary, ordering
The following items are supplied in the package:
Item
QMX3.P36F
QMX3.P36G
Operator unit
X
X
Bezel, titanium white Siemens DELTA-line Similar to Delta azio
120 x 80 mm
Base plate
CEE/VDE (type A)
3 modules landscape
In plastic bag for handover
to electrical installer
KNX PL-Link plug
X
X
Compatibility
•The QMX3.P36... room operator unit can be used with the Desigo TRA room
automation stations.
•Supported bezel programs
Siemens DELTA: DELTA line, DELTA miro and DELTA vita.
(For the DELTA style and DELTA profil series an adapter frame for
55mm x 55mm inserts is required)
Berker:(B.1, B.7
Gira:Standard 55, E2, Event, Esprit
Jung: A500, AS500, stainless steel; LS990, aluminum
Merten: System M
Feller:EDIZIOdue, PRESTIGE
(Adapter frame for 55mm x 55mm devices is required)
•Bezels from various other manufacturers can also be used (suitability must be
clarified in advance).
Product number
Stock number
Designation
Room
operator
unit
s
QMX3.P36F
S55624-H100
Freely configurable flush-mounted room operator unit for
KNX PL-Link
with
square
white bezel CEE/VDE (type A)
QMX3.P36G
S55624-H101
Freely configurable flush-mounted room operator unit for
KNX PL-Link
with
landscape
white bezel (3 modules landscape )
2 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
Mechanical design
•The unit is designed for mounting in a conduit box (A)
– Square CEE/VDE (type A)
– Rectangular 3 modules landscape
(suitability to be clarified in advance).
•The base plate (B) (rectangular or landscape) contains:
– A hook to attach a securing strap to protect against tampering
(the strap is not provided)
– an earthing plate (quick slide connector) to connect an earthing cable
•One Bezel (C) is supplied:
– Siemens DELTA line (square, with the QMX3.P36F)
– Siemens similar to DELTA azio 120 x 180
(rectangular, with the QMX3.P36G)
Bezels from various other manufacturers can also be used
(suitability to be clarified in advance).
•The operator unit (D) incorporates the room temperature sensor element, keys,
LCD panel, KNX PL-Link plug, tool plug, and spring clamps to hold the operator
unit in the base plate.
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
•Dispose of the device through channels provided for this purpose.
•Comply with all local and currently applicable laws and regulations.
3 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
Engineering notes
•The room operator units offer plug & play functionality.
•The room operator units receive their power from the connected room
automation station via the KNX PL-Link interface.
•KNX PL-Link supports plug & play functionality for pre-configured devices out of
the library
•For KNX PL-Link wiring (topology, allowed cables and cable length), see the
Desigo installation guide, CM111043.
•Normally, electrical installers only install the base plate and the KNX PL-Link
plug. These two items are packed in a plastic bag for easy handover to
installers.
•Use the tear-off label with the barcode on the packaging / on the display and
stick it on the floor plan to prepare commissioning for several room operator
units per room automation station.
The same barcode label with unique identifier is available on the device.
Furthermore, the unique identifier (HEX number) is displayed on screen when
starting the device.
Mounting and installation
•The room operator unit is suitable for flush mounting.
•Recommended height: 1.50 m above floor.
•Do not mount the unit in recesses, shelves, behind curtains or doors, or above
or near heat sources.
•Avoid direct solar radiation and drafts.
•Seal the conduit box internally, as air currents in the conduit can affect sensor
readings.
•Adhere to allowed ambient conditions.
Location
4 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
•The base plate contains:
– A hook to attach a securing strap to protect against tampering
(the strap is not provided)
– An earthing plate (quick slide connector) to connect an earthing cable
•The installing tube must be sealed or cold or warm air may enter the conduit box
and cause faulty temperature readings by the internal sensor.
•Mounting instructions are printed inside the device package and are also on the
plastic bag.
The operator unit may need to be dismounted from the base plate to exchange the
operator unit.
1. Hold bezel with one hand.
2. Pull operator unit with the other hand.
Mounting
Dismounting
5 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
•For KNX PL-Link wiring (topology, allowed cables and cable length), see the
Desigo TRA installation guide, CM111043.
•Use the correct cables for the KNX PL-Link bus
•Do not interchange the wires of the KNX PL-Link cable.
– The red terminal is for KNX PL-Link +
– The gray terminal is for KNX PL-Link –
•Observe all local installation regulations.
•Use the earthing plate (quick slide connector) to connect an earthing cable in the
conduit box (in case a switch or a mains plug is in the same conduit box).
STOP
Caution
•The unit is not protected against accidental connection to AC 230 V.
•The installing tube must be sealed or cold or hot air may enter the conduit box
and cause faulty temperature readings by the internal sensor.
Prerequisite for commissioning
The room automation station must be running and an application must be loaded.
The application is not loaded on the room operator unit, but the room automation
station.
Download of the application is done using the SSA-DNT (Pack & Go) or the ABT.
For this purpose (or for service), connect the ABT to the room automation station
(USB or Ethernet).
Manual commissioning
All commissioning work is done via the PXC3... room automation station, using the
SSA-DNT or the ABT.
The ABT is never connected directly to a room operator unit.
When more than one QXM3.P36... room operator unit is on the same trunk of
the KNX PL-Link bus, manually commission is done as follows:
1. Connect the SSA-DNT or the ABT to the room automation station and
activate the online commissioning function.
2. Load the web page "KNX PL-Link identification".
Activate the identification function.
The room automation station now waits for a signal from the room operator
unit.
3. On the room operator unit, simultaneously press the upper left and bottom
right button for at least 5 seconds.
4. The page "System info" is displayed.
Go to the network function page (last line)
5. Press "Prog. Mode" (first line).
The display below "Prog. Mode" changes to "Enabled".
The tool identifies the current room operator unit that is operated and
assigns it.
After the device is commissioned, programming mode is automatically reset to
“disabled”. Note: Programming mode also resets to “disabled” each time the
device restarts.
Installation
Load application on the
room automation
station
6 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
Diagnostics Press "Conn. Test" to test the KNX PL-Link connection.
A popup window shows the progress of the connection test:
Reset to factory
setting
STOP
Note! This operation resets all user preference data and
configuration settings to factory default.
This operation is irreversible.
Press "Fact. Reset". The device is locked and reboots within 10 seconds. The
room automation station deletes it from its device list. During this time, it is
safe to remove the device from the network.
If the room operator unit is not unplugged, it acts like a newly inserted device
requiring again automated or manual configuration.
Commissioning (plug & play)
When only one room operator unit is connected to the KNX PL-Link bus, the unit
automatically establishes communications with the room automation station, from
where the functions are downloaded to the room operator unit (plug & play).
The following routine is executed:
Step
Function
Description
1
Splash screen
The unique serial number of the device is displayed below the company
logo.
2 Busy
During configuration, 6 animated dots appear in the center of the screen
to indicate the device is busy.
This step is skipped if the device is already configured.
Note: The configuration file can be downloaded any time; as a result,
these dots are displayed every time the room automation station
initializes download.
7 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
Step
Function
Description
3 Normal operation
After startup, the device goes to normal operation
(example view; picture depends on application in room automation
station).
4
Configuration required
When configuration is faulty, the default page
"Initial Menu" is displayed: temperature that is
measured by the local temperature sensor along
with a menu for network commissioning and
diagnostics.
Operating notes
Operation and display of the room operator unit depend on the control program on
the room automation station.
The display has 4 lines to display information.
Texts, icons, read-only data point information, or operable data point information
can be displayed.
With a multi-page navigation-driven page set, the information usually is laid out in
the following format:
Line 1
Title/read-only data point information
Line 2 Information
Operable data point information (display or setpoint)
Temperature, air quality, fan speed, etc.
Line 3
Read-only / operable data point information
Line 4
Information or navigation between several "pages"
Info
Operable
Read-only
Navigation
Info
Operable
Navigation
Info
Operable
Navigation
3 lines of information
List operation
Single-line operation
Usability concept
Multi-page display
with navigation
8 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
With a single-page page set, information is usually is laid out in the following
format:
Line 1
Title / read-only data point information
Line 2 Operable data point information
Temperature, air quality, fan speed, etc.
Line 3
Read-only/operable data point information
Line 4
Read-only/operable data point information
Example:
Title (empty), temperature setpoint, fan speed and room
operating mode
The leaf symbol / (green, red) at the top right of the
device tells the user if the settings are energy-efficient or not.
Pressing the upper right key resets the application to energy-
efficient parameter values

Save a changed scene by long pressing the key (approx. 3 sec).
1
2
3
4
5
6
7
8
Notes
•A scene can only be saved if Scene Teaching is
enabled in the application.
•The key event to save a scene can be freely
engineered.
In the default page set, it is set to “long-press key
6" (the keys are numbered left top to bottom and
then right top to bottom).
1
2
3
4
5
6
7
8
•Lock the buttons:
Press button 6 6
•Unlock the buttons:
Press buttons 2, 3 and 7 one after the other
Single-page display
RoomOptiControl,
Green Leaf
Saving scenes
Key lock
9 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24
A list item provides status information:
•Tick: Indicates the current selection from the room automation station. A change
from hourglass to tick indicates that the automation station has confirmed the
modifications the user just made.
•Hourglass: Indicates the progress of the selected activity.
•Lock: Indicates locked entries that cannot be selected / enabled.
•Floppy disk: Is only used in scene saving, and will be displayed for 1 second,
then go back to "Tick".
Maintenance
The device can be cleaned with off-the shelf, solvent-free cleaning agents.
Do not use mechanical aids (rough sponge or similar materials) – only a soft, damp
cloth.
Dismounting: see page 5.
Technical data
Supply voltage
Operating voltage range
KNX PL-Link DC 21...30 V
The
room operator unit receives its power from the connected room automation station
via the KNX PL-Link interface
Power consumption
(from room automation station)
Max.10 mA at DC 24 V
Series A: Max.12.5 mA at DC 24 V
Operating data
Temperature sensor
Measuring element
NTC resistance sensor
Measuring range
0...50 °C
Measuring accuracy (5 … 30 °C)
±0.61 K
Measuring accuracy (25 °C)
±0.35 K
Display
Type
Dot matrix LCD, resolution 96 x 128
Information displayed depend
s on the
application in the
PXC3... room automation
station
−Room temperature
−
Setpoint adjustment
−
Control mode
−
Manually selected fan speed
−
Control sequence
−
Scenes
−etc.
Ports/interfaces
Type of port between
room automation station
and room operator unit
KNX
PL-Link
Baud rate
9.6 kbps
Standard KNX
plug
Wire diameter0.8 mm
, max. 1.0 mm
(solid conductors only)
Cable type
Solid conductors 2-core, twisted pair
Single cable length (from
room automation
station to room operator unit)
<1000 m
Cables must comply with KNX specifications, see TRA Installation manual, CM111043
Housing protection
Protection standard as per EN 60529
IP 30
Protection class
Insulation protection class
III
Status information
STOP
Note!
10 / 14
Siemens QMX3... Freely configurable flush-mounted room operator unit for KNX PL-Link CM2N1601en_04
Building Technologies 2016-03-24