Configuration
Thefollowingconfigurationsare possiblethroughcontrolleror configurationtool:
lAfter activating the output remains:
Steadyoutput
Pulseoutput: Howlong the contact remainsactivecan be configured bycontroller or
configuration tools(pulseduration).
lFailsafebehavior when the FD18-BUSdetector line iscurrent-free or indegraded mode.
The error behavior definesthe position of the output incaseof an error:
Off: Output remainsinthe same position asbefore the error
Activation:Output isactivated incaseof an error
Deactivation: Outputisdeactivated incaseof an error
Thecontroller doesnot monitor externalequipmentstatus(activated/inactivated).
Invertedoperation (outputlinesnotmonitored)
-Beused for controlling(e.g. closingadoor).
-Themoduleswitchestheexternallysupplied 24 VDC voltage inactivestatusonthe
output.
-Innormalstatusthere isnomonitoringfor openlineandshort circuit.
-Thejumper ontheinput/output modulemust be plugged ontoJ2/J4(Fig. 4).
Fig. 4Input/output modulejumper positionJ2, J4
Fig. 5Connectiondiagramfor inverted operation, e.g. whenused asdoor retainer.
Ininactivestatusthe24 VDC are permanentlyapplied totheoutput andmaykeep adoor
open, for example.Whentheoutputisswitched toactive,theoutput goesinto"open"status
(= no24 VDC voltage)andthedoor isclosed.
Comment:
Inthisexample, thedoor wouldalsocloseifthe 24 VDC supplywere tofail, e.g. duetoaline
problem(short circuit, openline).
Configuration
Under inverted mode, thefollowingconfigurationsare possiblethroughcontroller or
configurationtools:
lAfter activatingtheoutput remains:
Steadyoutput
Pulseoutput: Howlongthecontact remainsactivecanbeconfigured bycontroller or
configurationtools(pulseduration).
lFailsafebehavior whentheFD18-BUSdetector lineiscurrent-free or indegraded mode.
Theerror behaviordefinesthepositionoftheoutput throughcontroller or configuration
toolsincaseofanerror:
Off: Output remainsinthesamepositionasbefore theerror
Activation: Outputisactivated incaseofanerror
Deactivation: Output isdeactivated incaseofanerror
Thecontroller doesnot monitor externalequipmentstatus(activated/inactivated).