OPERATION
The SIStec PC1 electronic pump controller automatically regulates the ON and OFF periods of pump
equipment, by monitoring the current flow of the pump while operating under normal load conditions
and switching the pump OFF when the sump runs dry. The pump is then restarted after a time
calculated from the condition of the jumper settings and the amount of time taken to drain the sump.
In this way a regular ON OFF cycle is maintained and automatically adjusted to balance the flow rate
of the pump and the flow rate into the sump.
JUMPER SETTINGS
Connecting the following jumpers selects a "cycle time".
One link must be made. No link or more than one link will prevent proper operation.
Link…………….17 - 18 = 2.5 min.
Link………….…17 - 19 = 5 min.
Link………….…17 - 20 = 10 min.
With no jumper connection between terminals 15 and 16 the previous cycle times are multiplied by 2.
For convenience a switch can be connected between terminals 15 and 16.
Closed Contact…15 - 16 = multiply by 1.
Open Contact…..15 - 16 = multiply by 2.
Minimum rest time = 20 seconds
Minimum run time = 3 seconds
Maximum rest time = 20 minutes (Link 17 - 18 closed and 15-16 open)
Maximum run time = Continuous
The cycle time is divided into a RUN and a REST time. The rest time is equal to the cycle time minus
the run time.
E.g. For a cycle time of 10 minutes. If the pump runs for 6 minutes, it will restart after 4 minutes.
If the pump runs for longer than the cycle time and then stops, the controller will rest for a minimum of
20 seconds before restarting.