manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Smartgen
  6. •
  7. Controllers
  8. •
  9. Smartgen HGM7100N Series User manual

Smartgen HGM7100N Series User manual

HGM7100N SERIES
(HGM7110N/7120N)
GENSET CONTROLLER
USER MANUAL
SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 3 of 48
CONTENTS
1 OVERVIEW.............................................................................................................................................. 5
2 PERFORMANCE AND CHARACTERISTICS......................................................................................... 5
3 SPECIFICATION OPERATION ............................................................................................................... 7
4 OPERATION............................................................................................................................................ 8
4.1 KEY FUNCTION............................................................................................................................ 8
4.2 CONTROLLER PANEL.................................................................................................................. 9
4.3 AUTO START/STOP OPERATION.............................................................................................. 10
4.3.1. ILLUSTRATION.................................................................................................................. 10
4.3.2. AUTO START SEQUENCE................................................................................................ 10
4.3.3. AUTO STOP SEQUENCE.................................................................................................. 10
4.4 MANUAL START/STOP OPERATION..........................................................................................11
4.5 EMERGENCY START UP............................................................................................................11
5 BREAKER CONTROL PROCESS OF GENSET CONTROLLER ........................................................ 12
5.1 HGM7120N BREAKER CONTROL PROCESS.......................................................................... 12
5.1.1. MANUAL SWITCHING PROCESS.................................................................................... 12
5.1.2. AUTO SWITCHING PROCESS......................................................................................... 12
5.2 HGM7110N BREAKER CONTROL PROCESS .......................................................................... 13
5.2.1. MANUAL SWITCHING PROCESS.................................................................................... 13
5.2.2. AUTO SWITCHING PROCESS......................................................................................... 13
6 PROTECTION ....................................................................................................................................... 14
6.1 WARNINGS ................................................................................................................................. 14
6.2 SHUTDOWN ALARM .................................................................................................................. 16
6.3 TRIP AND STOPALARM ............................................................................................................ 18
6.4 TRIPALARM................................................................................................................................ 18
7 WIRINGS CONNECTION...................................................................................................................... 19
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS ............................................... 22
8.1 CONTENTS AND SCOPES OF PARAMETERS......................................................................... 22
8.2 DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1~6................................... 22
8.2.1. CUSTOM PERIOD OUTPUT............................................................................................. 35
8.2.2. CUSTOM COMBINED OUTPUT........................................................................................ 35
8.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS 1~7............................................ 36
8.4 SELECTION OF SENSORS........................................................................................................ 38
8.5 CONDITIONS OF CRANK DISCONNECT SELECTION............................................................ 39
9 PARAMETERS SETTING...................................................................................................................... 40
9.1 MENU ITEMS .............................................................................................................................. 40
9.2 CONTROLLER PARAMETER SETTINGS.................................................................................. 40
9.3 LANGUAGE SELECTION ........................................................................................................... 40
9.4 EVENT LOG ................................................................................................................................ 40
9.5 CONTROLLER INFORMATION.................................................................................................. 40
9.6 TIME SETTING............................................................................................................................ 41
9.7 CYCLE START SETTING............................................................................................................ 41
9.8 BATTERY UNDER VOLTAGE START SETTING........................................................................ 41
10 GENSETS CYCLE START.................................................................................................................... 41
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 4 of 48
11 SENSOR SETTING............................................................................................................................... 42
12 COMMISSIONING................................................................................................................................. 43
13 TYPICALAPPLICATION........................................................................................................................ 44
14 INSTALLATION...................................................................................................................................... 46
14.1 FIXING CLIPS.............................................................................................................................. 46
14.2 OVERALL DIMENSION............................................................................................................... 46
15 TROUBLESHOOTING........................................................................................................................... 48
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 8 of 48
4 OPERATION
4.1 KEY FUNCTION
Table 3 - Key Function Descriptions
Icon
Function
Description
Stop/ Reset
Stop running generator in Auto/Manual mode;
In stop mode, in case of alarm condition, pressing the button will
reset alarm;
Pressing and holding the button for 3 seconds will test indicator
lights (lamp test);
During stopping process, press this button again to stop generator
immediately.
Start
Under manual mode, press this button will start genset;
Manual
Pressing this key will set the module into manual mode.
Auto
Pressing this key will set the module into auto mode.
C/O
Pressing this key to control breaker close or open in C/O interface
under manual mode.
(only suit for HGM7120N)
Close
Pressing this key to control breaker close under user manual mode.
(only suit for HGM7110N)
Open
Pressing this key to control breaker open under user manual mode.
(only suit for HGM7110N)
Set/Confirm
Pressing this key will enter into Main Menu;
In setting parameter status, press this key will shift cursor or confirm
setting value.
Up/Increase
Scrolls the screen up; Shift the cursor up or increase the set value
in parameter setting menu.
Down/Decrease
Scrolls the screen down; Shift the cursor down or decrease the set
value in parameter setting menu.
Homepage/Return
Controller returns to homepage if pressed this key in main screen;
controller returns to the previous page if pressed this key in
parameter setting page; hold and press this key for 3 seconds, trip
alarm can be reset.
Note: press any key to mute alarms in main screen.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 9 of 48
4.2 CONTROLLER PANEL
Figure 1 - HGM7110N Front Panel Indication
Figure 2 - HGM7120N Front Panel Indication
NOTE: Part of indicator lights illustration:
Table 4 - Alarm Indicator Description
Alarm Type
Alarm Indicators
Warning alarm
slowly flash (once per second)
Trip alarm
slowly flash (once per second)
Shutdown alarm
fast flash (5 times per second)
Trip and stop alarm
fast flash (5 times per second)
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 19 of 48
7 WIRINGS CONNECTION
Compared with HGM7120N, HGM7110N is missing one mains voltage three-phase input terminal.
HGM7120N controller back panel is as follows:
Figure 3 - HGM7120N Back Panel
Table 9 - Terminal Wiring Connection
No.
Function
Cable Size
Remarks
1
B-
2.5mm2
Connected with negative of starter battery
2
B+
2.5mm2
Connected with positive of starter battery. If wire length
is over 30m, better to double wires in parallel. Max. 20A
fuse is recommended.
3
Emergency Stop
2.5mm2
Connect emergency stop button with B+.
4
Fuel (16A)
1.5mm2
B+ is supplied by No.3 terminal, rated 16A.
5
Crank (16A)
1.5mm2
B+ is supplied by No.3 terminal, rated 16A.
Connect with starting coil of starter.
6
Aux. Output 1(7A)
1.5mm2
B+ is supplied by No.2 terminal, rated 7A.
7
Aux. Output 2(8A250VAC)
1.5 mm2
Normally close output,
rated 8A.
Details see Table 11
8
Relay common port
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 20 of 48
No.
Function
Cable Size
Remarks
9
Normally open output,
rated 8A.
10
Aux. Output 3(16A250VAC)
2.5 mm2
Relay normally open volt
free contact, rated 16A,
volt free contact output.
11
12
Aux. Output 4(16A250VAC)
2.5 mm2
13
14
Charger(D+)
1.0mm2
Connected with charger starter’s D+ (WL) terminals.
Being hang up If there is no this terminal.
15
Aux. Output 5(7A)
1.5 mm2
B+ is supplied by No.2
terminal, rated 7A
Details see Table 11
16
Aux. Output 6(7A)
1.5 mm2
17
Speed Sensor Input
Connect with speed sensor, shielded wire is recommended.
18
Speed sensor input, battery
negative electrode has been
connected to the inside of
controller.
19
Engine Temp.
Connected with temperature sensor
Details to see table 13
20
Oil Pressure
Connected with pressure sensor
21
Fuel Level
Connected with fuel level sensor
22
Aux. Input 1
1.0mm2
Ground connected is active (B-)
Details to see table 12
23
Aux. Input 2
1.0mm2
Ground connected is active (B-)
24
Aux. Input 3
1.0mm2
Ground connected is active (B-)
25
Aux. Input 4
1.0mm2
Ground connected is active (B-)
26
Aux. Input 5
1.0mm2
Ground connected is active (B-)
27
Sensor Common Port
Sensor common port, battery negative electrode has been
connected to the inside of controller.
28
Aux. Input 6
1.0mm2
Ground connected is active (B-)
Details to see table 12
29
Aux. Input 7
1.0mm2
Ground connected is active (B-)
30
Configurable Sensor 1
Connected with temp/pressure/fuel level
sensor.
Details to see table 13
31
Configurable Sensor 2
32
CTA-phase Monitoring Input
1.5mm2
Outside connected to secondary coil of CT (5A rated).
33
CT B-phase Monitoring Input
1.5mm2
Outside connected to secondary coil of CT (5A rated).
34
CT C-phase Monitoring
Input
1.5mm2
Outside connected to secondary coil of CT (5A rated).
35
CT Common Port
1.5mm2
Details to see the following installation description.
36
Gen U-phase Voltage
Monitoring Input
1.5mm2
Connected to U-phase output of genset (2Afuse
recommended).
37
Gen V-phase Voltage
Monitoring Input
1.0mm2
Connected to V-phase output of genset (2Afuse
recommended).
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 21 of 48
No.
Function
Cable Size
Remarks
38
Gen W-phase Voltage
Monitoring Input
1.0mm2
Connected to W-phase output of genset (2A fuse
recommended).
39
Gen N2-line Input
1.0mm2
Connected to N-line output of genset.
40
Mains R-phase Voltage
Monitoring Input
1.0mm2
Connected to R-phase of mains (2Afuse recommended).
(HGM7110N without)
41
Mains S-phase voltage
monitoring input
1.0mm2
Connected to S-phase of mains (2Afuse recommended).
(HGM7110N without)
42
Mains T-phase voltage
monitoring input
1.0mm2
Connected to T-phase of mains (2Afuse recommended).
(HGM7110N without)
43
Mains line N1 Input
1.0mm2
Connected to N-line of mains. (HGM7110N without)
44
RS485 Common Ground
0.5mm2
120Ωshielded wire is recommended with single end
ground.
45
RS485-
0.5mm2
46
RS485+
0.5mm2
47
VOUT(+5V)
0.5mm2
Output DC +5V.
NOTE: USB ports in controller rear panel are programmable parameter ports, user can directly configure
the controller via PC.
NOTE: ETHERNET port in controller rear panel is network monitoring port, user can directly monitor the
controller via PC.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 22 of 48
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Table 10 - Parameters Settings and Scope
No.
Items
Range
Default
Description
Mains
1
AC System
(0-3)
0
0: 3P4W;
1: 3P3W
2: 2P3W
3: 1P2W
2
Mains Rated
Voltage
(30-30000)V
230
Provide standard for judging whether mains
over/under voltage or not; if used voltage
transformer, this value is primary voltage of
transformer.
3
Mains Rated
Frequency
(10.0-75.0)Hz
50.0
Provide standard for judging whether mains
over/under frequency or not.
4
Mains Normal
Delay
(0-3600)s
10
The time from mains abnormal to normal.
5
Mains Abnormal
Time
(0-3600)s
5
The time from mains normal to abnormal.
6
Mains Voltage
Transformer (PT)
(0-1)
0
0: Disabled; 1: Enabled
7
Mains Over Voltage
(0-200)%
120
The setting value is mains rated voltage
percentage; return value and delay value also
can be set.
8
Mains Under
Voltage
(0-200)%
80
9
Mains Over
Frequency
(0-200)%
Disabled
The setting value is mains rated frequency
percentage; return value and delay value also
can be set.
10
Mains Under
Frequency
(0-200)%
Disabled
11
Mains Loss of
Phase Check
(0-1)
1
0: Disabled; 1: Enabled
12
Mains Reverse
Phase
(0-1)
1
Timers
1
Start Delay
(0-3600)s
1
Time from mains abnormal or remote start
signal is active to start gen-set.
2
Return Delay
(0-3600)s
1
Time from mains normal or remote start
signal is deactivated to genset stop.
3
Preheat Delay
(0-3600)s
0
Power-on time of heater plug before starter is
powered up.
4
Cranking Time
(3-60)s
8
Each starter power-on time.
5
Crank Rest Time
(3-60)s
10
The waiting time before second power up
when engine starts fail.
6
Safety On Time
(0-3600)s
10
Alarms for low oil pressure, high temp, under
speed, under frequency/voltage, charge alt
failure are deactivated.
7
Start Idle Time
(0-3600)s
0
Idle speed running time when gen-set start up.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 23 of 48
No.
Items
Range
Default
Description
8
Warming Up Time
(0-3600)s
10
Warming time between gen-set switch on and
high speed running.
9
Cooling Time
(0-3600)s
10
Radiating time before gen-set stop, after it
unloads.
10
Stop Idle Time
(0-3600)s
0
Idle running time while gen-set closing down.
11
ETS Solenoid Hold
(0-3600)s
20
Stop electromagnet’s power on time when
gen-set is closing down.
12
Wait For Stop Time
(0-3600)s
0
When ―ETS Solenoid Hold‖ is set as 0, it is
the time between gen-set idle delay expired
and stopped completely;
When ―ETS Solenoid Hold‖ is not 0, it is time
between ETS hold delay expired and
stopped.
13
After Stop Time
(0-3600)s
0
Time from gen-set stopped to standby.
Engine
1
Engine Type
(0-39)
0
Default: conventional engine.
2
Flywheel Teeth
(1.0-300.0)
118
It is tooth number of the engine, which is used
for judging starter crank disconnect
conditions and inspecting engine speed.
Details to see the following installation
description.
3
Engine Rated
Speed
(0-6000)RPM
1500
Provide standard for judging over/under
speed and on-load speed.
4
Speed On-load
(0-100)%
90
The setting value is rated speed percentage.
The controller detects it while gen-set
preparing to take the load, if the speed is less
than the on-load speed, gen-set will not enter
the normal operation period.
5
Speed Signal Loss
Delay
(0-3600)s
5
Time from the speed is detected as 0 to the
action confirmed.
6
Speed Signal Loss
Action
(0-1)
0
0: Warning; 1: Shutdown
7
Over Speed
Shutdown
(0-200)%
114
The setting value is the percentage of rated
speed, and delay value can be set.
8
Under Speed
Shutdown
(0-200)%
80
9
Over Speed
Warning
(0-200)%
110
The setting value is the percentage of rated
speed, return value and delay value can be
set.
10
Under Speed
Warning
(0-200)%
86
11
Battery Rated
Voltage
(0-60.0)V
24.0
Provide standard for judging battery
over/under voltage.
12
Battery High
Voltage Warning
(0-200)%
120
The setting value is the percentage of rated
voltage, return value and delay value can be
set.
13
Battery Low Voltage
Warning
(0-200)%
85
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 24 of 48
No.
Items
Range
Default
Description
14
Charge Alt Fail
(0-60.0)V
8.0
If the voltage of charger D+(WL) is lower than
the setting value during gen-set normal
running, controller will initiate fail to charge
warning alarms.
15
StartAttempts
(1-10)times
3
Maximum crank times when engine starts fail.
If reach this number, controller will send start
failure signals.
16
Crank Disconnect
Condition
(0-6)
2
Details please to see table 14
There are 3 cranking disconnect conditions,
which can be used separately or together,
aiming to disconnect starter motor with
engine as soon as possible.
17
Frequency of Crank
Disconnect
(0-200)%
24
The setting value is the percentage of rated
frequency, when generator frequency is
higher than the set value, starter will be
disconnected. Details to see the following
installation description.
18
Speed of Crank
Disconnect
(0-200)%
24
The setting value is the percentage of the
rated speed, when speed is higher than the
setting value, starter will disconnect. Details
to see the following installation description.
19
Oil Pressure of
Crank Disconnect
(0-1000)kPa
200
When engine oil pressure is higher than the
setting value, starter will disconnect. Details
to see the following installation description.
20
Battery Low Voltage
Start Enabled
(0-1)
0
0: Disabled; 1:Enabled
21
Battery Low Voltage
Start Value
(1.0-60.0)V
10.0
It is the low-battery-start value.Active when in
auto mode.
22
Battery Low Voltage
Stop Value
(1.0-60.0)V
24.0
The shutdown value after low-battery-start
and charged.Active when in auto mode.
23
Battery Low Voltage
Start/Stop Delay
(0-3600)s
60
When battery voltage reached to engine start
threshold, engine will start up after delay
expired; when battery voltage reached to
engine stop threshold, engine will stop after
delay expired.
Generator
1
Power Supply
System
(0-3)
0
0: 3P4W;
1: 3P3W
2: 2P3W
3: 1P2W
2
Engine Poles
(2-64)
4
It is the number of engine poles, which can
help engine without installing speed sensor to
calculate engine speed.
3
Rated Voltage
(30-30000)V
230
Provide standard for judging gen over/under
voltage, and on-load voltage. If voltage
transformer is used, this value is transformer
primary voltage.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 25 of 48
No.
Items
Range
Default
Description
4
Voltage On-load
(0-200)%
85
The setting value is rated voltage percentage.
The controller detects it while gen-set
preparing to take the load, if voltage is less
than the on-load voltage, gen-set will not
enter normal operation period.
5
Rated Frequency
(10.0-600.0) Hz
50.0
Provide standard for judging over/under
frequency and on-load frequency.
6
Frequency On-load
(0-200)%
85
The setting value is rated frequency
percentage. The controller detects it while
gen-set preparing to take the load, if
frequency is less than the on-load frequency,
gen-set will not enter normal operation
period.
7
Voltage
Transformer (PT)
(0-1)
0
0: Disabled; 1: Enabled
8
Gen. Over Voltage
Shutdown
(0-200)%
120
The setting values are rated voltage
percentage of generator, and delay value can
be set.
9
Gen. Under Voltage
Shutdown
(0-200)%
80
10
Gen. Over
Frequency
Shutdown
(0-200)%
114
The setting values are rated frequency
percentage of generator, and delay value can
be set.
11
Gen. Under
Frequency
Shutdown
(0-200)%
80
12
Gen. Over Voltage
Warning
(0-200)%
110
The setting values are rated voltage
percentage of generator, and return value
and delay value can be set.
13
Gen. Under Voltage
Warning
(0-200)%
84
14
Gen. Over
Frequency Warning
(0-200)%
110
The setting values are rated frequency
percentage of generator, and return value
and delay value can be set.
15
Gen. Under
Frequency Warning
(0-200)%
84
16
Gen. Loss of Phase
Check
(0-1)
1
0: Disabled; 1:Enabled
17
Gen. Reverse
Phase Check
(0-1)
1
Load
1
Current
Transformer Ratio
(5-6000)/5
500
It is the ratio of external connected current
transformer.
2
Rated Current
(5-6000)A
500
It is the rated current of generator, which is
used as the standard for load current.
3
Rated Power
(0-6000)kW
276
It is the rated power of generator, which is
used as the standard for load current.
4
Over Current
Enable
(0-200)%
120
The setting value is the percentage of rated
full-load current, and delay value can be set
as DMT or IDMT.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 26 of 48
No.
Items
Range
Default
Description
5
Over Power Setting
(0-1)
0
0: Disabled; 1: Enabled
6
Reverse Power
Setting
(0-1)
0
0: Disabled; 1: Enabled
Switch
1
Switching Time
(0-7200)s
5
Time from open mains to close generator or
from open generator to close mains.
2
Close Delay
(0-20.0)s
5.0
Pulse width of mains closed and generator
closed; 0s stands for constant output.
3
Open Delay
(0-20.0)s
3.0
Pulse width of open mains and open
generator.
4
Switching Detection
Time
(0-20.0)s
5.0
It is the time to detect auxiliary contactor after
ATS switching.
5
Switch Failure
Warning Enabled
(0-1)
0
0: Disabled; 1: Enabled
6
Open Detection
Enabled
(0-1)
0
7
Immediately Trip
when Mains
Dropout
(0-1)
1
0: Disabled; 1: Enabled
Module
1
Power On Mode
(0-2)
0
0: Stop Mode; 1: Manual Mode; 2: Auto Mode
2
Communication
Address
(1-254)
1
Controller address while in remote monitoring
status.
3
Communication
Stop-bit Setting
(0-1)
1
0: 2-bit stop bit; 1: 1-bit stop bit
4
Language Selection
(0-2)
0
0: Simplified Chinese; 1: English; 2: Other
5
Password Setting
(0-65535)
00318
This password used to enter into advanced
parameter setting.
6
Backlight Time
(0-3600) s
300
When it is 0s, LCD always light.
Schedule & Maintenance
1
Scheduled Start
Setting
(0-1)
0
0: Disabled; 1: Enabled
2
Scheduled Not Run
Setting
(0-1)
0
0: Disabled; 1: Enabled
3
Maintenance
Setting
(0-1)
0
0: Disabled; 1: Enabled
Analog Sensors
Temperature Sensor
1
Curve Type
(0-15)
7
SGX. Detail to see Table 13
2
Open CircuitAction
(0-2)
0
0: Warning; 1: Shutdown; 2: None
3
High Temp
Shutdown Setting
(0-300)ºC
98
When temperature value of external
connected temperature sensor is higher than
the setting point, controller will initiate high
temperature shutdown alarm (judgment only
starts after safety on delay expired). Delay
value can be set.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 27 of 48
No.
Items
Range
Default
Description
4
High Temp Warning
Setting
(0-300)ºC
95
When temperature value of external
connected temperature sensor is higher than
the setting point, controller will initiate high
temperature warning alarm (judgment only
starts after safety on delay expired). Return
value and delay value can be set.
5
Low Temp Warning
Setting
(0-1)
0
0: Disabled; 1: Enabled
Oil Pressure Sensor
1
Curve Type
(0-15)
7
SGX. Details to see table 13.
2
Open CircuitAction
(0-2)
0
0: Warning; 1: Shutdown; 2: None
3
Low Oil Pressure
Shutdown Setting
(0-1000)kPa
103
When pressure value of external connected
oil pressure sensor is lower than the setting
point, controller will initiate low oil pressure
shutdown alarm (judgment only starts after
safety on delay expired). Delay value can be
set.
4
Low Oil Pressure
Warning Setting
(0-1000)kPa
124
When pressure value of external connected
oil pressure sensor is lower than the setting
point, controller will initiate low oil pressure
warning alarm (judgment only starts after
safety on delay expired). Return value and
delay value can be set.
5
Sensor Type
(0-2)
0
0: Resistor type; 1: Current type; 2: Voltage
type.
Level Sensor
1
Curve Type
(0-15)
4
SGH. Details to see table 13.
2
Open CircuitAction
(0-2)
0
0: Warning; 1: Shutdown; 2: None
3
Low Level Warning
(0-300)%
10
When the value of external connected fuel
level sensor is lower than the setting point,
controller will initiate low liquid level warning
alarm (always judge). Return value and delay
value can be set.
4
Low Level
Shutdown
(0-300)%
8
When the value of external connected level
sensor is lower than the setting point,
controller will initiate low liquid level shutdown
alarm (always judge). Delay value can be set.
Flexible Sensor 1
1
Flexible Sensor 1
Setting
(0-3)
0
0: Not Used; 1:Temperature Sensor;
2:Pressure Sensor; 3:Fuel Level Sensor
2
Sensor Type
(0-2)
0
0: Resistor type; 1: Current type; 2: Voltage
type.
Flexible Sensor 2
1
Flexible Sensor 2
Setting
(0-3)
0
0: Not Used; 1:Temperature Sensor;
2:Pressure Sensor; 3:Fuel Level Sensor
Digital Inputs
Digital Input 1
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 36 of 48
8.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS 1~7
Table 12 - Enable Programmable Inputs 1~7 (Ground connected is active (B-))
No
Items
Description
0
User Configured
Users can define content as bellows:
Indication: only display without warning and shutdown.
Warning: only warning without shutdown.
Shutdown: alarm and shutdown immediately.
Trip and stop: alarm, generator ramp-off load and stop after
high-speed cooling.
Trip: alarm, generator ramp-off load but not stop.
Inactive: input doesn’t work.
Always active: input detects all the time.
From crank: start detecting at the beginning of startup.
From safety on: start detecting after safety on delay is expired.
1
Reserved
2
Alarm Mute
When input is active, ―Audible Alarm‖output is inhibited.
3
Reset Alarm
When input is active, shutdown alarms and trip alarms can be reset.
4
Reserved
5
Lamp Test
When input is active, all LED indicators are light.
6
Panel Lock
When input is active, all buttons on the panel are inactive except
for , and displays on the right side of the first line
of LCD status page.
7
Reserved
8
Idle Control Mode
Under speed, under frequency and under voltage are not protected
in this mode.
9
InhibitAuto Stop
After generator is normal running in auto mode, when input is active,
generator-set auto stop function is inhibited.
10
InhibitAuto Start
After input is active in auto mode, generator-set auto start is
inhibited.
11
Inhibit Scheduled Start
After input is active in auto mode, generator-set auto timing start
gen-set is inhibited.
12
Master Select
Duty unit selection in cycle running.
13
Aux. Gen. Closed
Connecting the auxiliary contact of generator loading switch.
14
Inhibit Gen. Load
When input is active, gen-set will inhibit to close.
15
Aux Mains Closed
Connecting the auxiliary contact of mains loading switch.
16
Inhibit Mains Load
When input is active, mains will inhibit to close.
17
Auto Mode Input
When input is active, controller will enter into auto mode, and all
buttons on the panel are inactive except for , and
displays on the right side of the first line of LCD status page.
18
Auto Mode Invalid
When input is active, controller will not works in auto mode,
key and ―Simulate Auto Mode‖key are unavailable.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 44 of 48
13 TYPICAL APPLICATION
Figure 5 - HGM7100N Typical Application
Figure 6 - HGM7120N Typical Application
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 45 of 48
Figure 7 - Single Phase 2-Wire Connection Diagram
Figure 8 - 2Phase 3Wire Connection Diagram
NOTE: Expand relay with high capacity in start and fuel output is recommend.
HGM7100N GENSETCONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 46 of 48
14 INSTALLATION
14.1 FIXING CLIPS
Controller is panel built-in design; it is fixed by clips when installed.
Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
Pull the fixing clip backwards (towards the back of the module) ensuring two clips are inside their
allotted slots.
Turn the fixing clip screws clockwise until they are fixed on the panel.
Note: Care should be taken not to over tighten the screws of fixing clips.
14.2 OVERALL DIMENSION
Figure 9 - Overall Dimensions
HGM7100N series controller can suit for widely range of battery voltage DC (8~35) V. Negative of
battery must be connected with the engine shell. Diameter of wire that connects from power supply to
battery must be over 2.5mm2. If floating charge configured, please firstly connect output wires of charger
to battery’s positive and negative directly, then, connect wires from battery’s positive and negative to
controller’s positive and negative input ports in order to prevent charge disturbing the controller’s normal
working.
a) SPEED SENSOR INPUT
Speed sensoris the magnetic equipmentwhich be installed in starter and for detecting flywheel teeth.
Its connection wires to controller should apply for 2 cores shielding line. The shielding layer should
connect to No. 18 terminal in controller while another side is hanging in air. The else two signal wires are
connected to No.17 and No.18 terminals in controller. The output voltage of speed sensor should be
within (1~24) VAC (effective value) during the full speed. 12VAC is recommended (in rated speed).When
install the speed sensor, let the sensor is spun to contacting flywheel first, then, port out 1/3 lap, and lock
the nuts of sensor at last.
b) OUTPUT AND EXPAND RELAYS
All outputs of controller are relay contact output type. If need to expand the relays, please add
freewheel diode to both ends of expand relay’s coils (when coils of relay has DC current) or, increase
resistance-capacitance return circuit (when coils of relay has AC current), in order to prevent disturbance
to controller or others equipment.
c) AC INPUT
Current input of HGM7100N series controller must be connected to outside current transformer. And

Other manuals for HGM7100N Series

1

This manual suits for next models

2

Other Smartgen Controllers manuals

Smartgen HAT700 SERIES User manual

Smartgen

Smartgen HAT700 SERIES User manual

Smartgen HAT160 User manual

Smartgen

Smartgen HAT160 User manual

Smartgen HAT163 User manual

Smartgen

Smartgen HAT163 User manual

Smartgen HAT220A User manual

Smartgen

Smartgen HAT220A User manual

Smartgen HGM6100U2C Series User manual

Smartgen

Smartgen HGM6100U2C Series User manual

Smartgen HEM4300 User manual

Smartgen

Smartgen HEM4300 User manual

Smartgen HAT833 Series User manual

Smartgen

Smartgen HAT833 Series User manual

Smartgen HGM4100LT User manual

Smartgen

Smartgen HGM4100LT User manual

Smartgen GENSET HGM8100N Series User manual

Smartgen

Smartgen GENSET HGM8100N Series User manual

Smartgen HMC6 User manual

Smartgen

Smartgen HMC6 User manual

Smartgen HGM6510 User manual

Smartgen

Smartgen HGM6510 User manual

Smartgen HGM9510 User manual

Smartgen

Smartgen HGM9510 User manual

Smartgen HAT520N User manual

Smartgen

Smartgen HAT520N User manual

Smartgen HPM6 User manual

Smartgen

Smartgen HPM6 User manual

Smartgen HAT530N User manual

Smartgen

Smartgen HAT530N User manual

Smartgen HGM8156 User manual

Smartgen

Smartgen HGM8156 User manual

Smartgen HGM7100N Series User manual

Smartgen

Smartgen HGM7100N Series User manual

Smartgen HAT530 User manual

Smartgen

Smartgen HAT530 User manual

Smartgen HAT160 User manual

Smartgen

Smartgen HAT160 User manual

Smartgen HGM400N Series User manual

Smartgen

Smartgen HGM400N Series User manual

Smartgen HGM6100K Series User manual

Smartgen

Smartgen HGM6100K Series User manual

Smartgen HGM9520N User manual

Smartgen

Smartgen HGM9520N User manual

Smartgen APC615 User manual

Smartgen

Smartgen APC615 User manual

Smartgen MGC120 User manual

Smartgen

Smartgen MGC120 User manual

Popular Controllers manuals by other brands

METRON FD2 manual

METRON

METRON FD2 manual

Zengge D Series manual

Zengge

Zengge D Series manual

Velleman AER Domus Assembly & instruction manual

Velleman

Velleman AER Domus Assembly & instruction manual

Texas Instruments UCC28600 manual

Texas Instruments

Texas Instruments UCC28600 manual

NXP Semiconductors TWR-K60N512 user manual

NXP Semiconductors

NXP Semiconductors TWR-K60N512 user manual

Wilo Stratos Demo Installation and operating instructions

Wilo

Wilo Stratos Demo Installation and operating instructions

ABB ACS 600 MultiDrive installation guide

ABB

ABB ACS 600 MultiDrive installation guide

HP 9000 Series 300 Service handbook

HP

HP 9000 Series 300 Service handbook

ABB Galaxy Millennium J2011002 product manual

ABB

ABB Galaxy Millennium J2011002 product manual

Eldes ESIM120 user guide

Eldes

Eldes ESIM120 user guide

Millipore Tylan General FC-2900 instruction manual

Millipore

Millipore Tylan General FC-2900 instruction manual

Victron energy CCGX Troubleshooting

Victron energy

Victron energy CCGX Troubleshooting

Woodward SPM-D2-11 manual

Woodward

Woodward SPM-D2-11 manual

Leviton Decora Smart install guide

Leviton

Leviton Decora Smart install guide

AUMA SAVEx 07.2 Operation instructions

AUMA

AUMA SAVEx 07.2 Operation instructions

Timotion TDH6 user manual

Timotion

Timotion TDH6 user manual

Flycolor FlyDragon V4-80A WP user manual

Flycolor

Flycolor FlyDragon V4-80A WP user manual

TWR Lighting E-1DB manual

TWR Lighting

TWR Lighting E-1DB manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.