MGC120 Petrol Genset Controller User Manual
MGC120 Petrol Genset Controller Version 1.02017-11-07 Page 8 of 19
Auto Stop Sequence
1) When remote start signal is invalid or mains normal delay is expired, “Stop Delay” timer is
initiated;
2) Once this “stop delay” has expired, the “Cooling Down Delay” is then initiated;
3) During “Stop Idle” Delay (if configured), idle relay is energized.
4) “ETS Solenoid Hold” begins, ignition control relay is energized while fuel relay is de-energized,
and then genset entry standby status.
Note:
1) Press stop key in auto start status, generator-set will stop and enter into manual mode simultaneously.
2) Total running timer initiate when generator meet crank disconnected conditions, meanwhile, the last
decimal point of the nixie tube flashes to indicate that the generator is running.
4.5 MANUAL START/STOP OPERATION
After pressing key, indicator besides this key lights off, which stands for generator-set states
in manual mode.
a) Manual start: press button to start genset (Please refer to Start Sequence 2-7). With low
oil pressure and voltage abnormal during genset running, controller can protect it to stop quickly.
b) Manual Stop: Press button to stop the running genset (Please refer to Stop Sequence
2-4).
4.6 AIR FLAP CONTROL
a) With engine cylinder temperature sensor
When generator-set starts up, If the engine cylinder temperature is below the set air flap
closing cylinder limit, the air flap is closed.
After entering safety on delay, If the engine cylinder temperature is above the set air flap
opening cylinder limit, the air flap is open;
if engine cylinder temperature is always below the set air flap opening cylinder limit, it will
stay in closed status, and generator-set cannot take load.
b) Without engine cylinder tempoerature sensor or sensor is open circuit
Generator-set starts up, during the first start attempt, the air flap full block, the second start
attempt, the air flap block 2/3, after the third start attempt, the air flap blocked 1/3. After the
crank disconnect, air flap is open after the delay.
4.7 ATS SWITCHING CONTROL
Auto mode: mains is available, ATS switches to mains; if mains failure and generator-set is normal
running, ATS switches to generator. Other status, ATS stays in mains station.
Manual mode: if close generator input is active, then generator closed; if close generator input is
deactivated, then mains closed.
Note: if use ATS control function, the programmable output need to be configured as GCB close output
and MCB close output, meanwhile, input need to be configured as GCB close input.