ZISE##-TFM113GB
Installation & Maintenance Manual
Digital Pressure Switch
Series ZSE10/ZSE10F/ISE10
Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety
and must be followed in addition to International standards (ISO/IEC),
Japan Industrial Standards (JIS) and other safety regulations.
To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.
•Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
•After maintenance is complete, perform appropriate functional
inspections and leak tests.
Stop operation if the equipment does not function properly or there is a
leakage of fluid.
When leakage occurs from parts other than the piping, the product is
faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.
NOTE
•The direct current power supply to be used should be UL approved as
follows:
(1) Limited voltage current circuit in accordance with UL508
A circuit which power is supplied by secondary coil of a transformer that
meets the following conditions
•Maximum voltage (with no load): less than 30Vrms (42.4V peak)
Maximum current: (1) less than 8A (including when short circuited)
(2) limited by circuit protector (such as fuse) with the
following ratings
(2) Circuit (of class 2) which is of maximum 30Vrms (42.4V peak) or less,
with UL 1310 class 2 power supply unit or UL 1585 class 2 transformer.
•The Pressure switch is a approved product only if it has a mark on the
body.
Operator error could result in serious injury or loss
of life.
In extreme conditions, there is a possibility of
serious injury or loss of life.
Operator error could result in injury or equipment
damage.
Caution
Warning
Danger
•Do not disassemble, modify (including changing the printed circuit
board) or repair.
An injury or failure can result.
•Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
•Do not operate in an atmosphere containing flammable or
explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
•Do not use the product in a place where static electricity is a
problem.
Otherwise it can cause failure or malfunction of the system.
•If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical
system
•Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
•The following instructions must be followed during maintenance:
•Turn off the power supply
•Stop the air supply, exhaust the residual pressure and verify that
the air is released before performing maintenance.
Otherwise an injury can be caused.
Caution
Names and Functions of Individual Parts
Installation
Model Indication and How to Order
Installation
Mounting
*: The tightening torque of piping port must be 1Nm for M5 and 7 to 9 Nm for R1/8 and
NPT1/8.
•Mount with the set screws M3 size (2 pcs.) for direct installation.
The tightening torque of the mounting screw must be 0.5 to 0.7 Nm.
Warning
Safety Instructions (Continued)
Refer to the operation manual,and catalogue for this product.
Output (OUT1) Light (Green): Lights ON when the switch output (OUT1) is
turned ON.
Output (OUT2) Light (Red): Lights ON when the switch output (OUT2) is
turned ON.
LED display: Displays the current status of pressure, setting mode and error
code.
button (UP): Selects the mode or increases the ON/OFF set value.
Press this button to change to the peak display mode.
button (DOWN): Selects the mode or decreases the ON/OFF set value.
Press this button to change to the bottom display mode.
button (SET): Press this button to change to either mode and to set a
value.
No-load voltage (V peak) Max. current rating (A)
0 to 20 [V] 5.0
20 to 30 [V] 100 / peak voltage
Mounting with panel mount adapter
•Panel mount adapter + Front protective cover (Model: ZS-39-D)