  9. SMC Networks ZSE10 Series Instruction Manual

SMC Networks ZSE10 Series Instruction Manual

ZISE##-TFM113GB
Installation & Maintenance Manual
Digital Pressure Switch
Series ZSE10/ZSE10F/ISE10
Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety
and must be followed in addition to International standards (ISO/IEC),
Japan Industrial Standards (JIS) and other safety regulations.
To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.
•Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
•After maintenance is complete, perform appropriate functional
inspections and leak tests.
Stop operation if the equipment does not function properly or there is a
leakage of fluid.
When leakage occurs from parts other than the piping, the product is
faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.
NOTE
•The direct current power supply to be used should be UL approved as
follows:
(1) Limited voltage current circuit in accordance with UL508
A circuit which power is supplied by secondary coil of a transformer that
meets the following conditions
•Maximum voltage (with no load): less than 30Vrms (42.4V peak)
Maximum current: (1) less than 8A (including when short circuited)
(2) limited by circuit protector (such as fuse) with the
following ratings
(2) Circuit (of class 2) which is of maximum 30Vrms (42.4V peak) or less,
with UL 1310 class 2 power supply unit or UL 1585 class 2 transformer.
•The Pressure switch is a approved product only if it has a mark on the
body.
Operator error could result in serious injury or loss
of life.
In extreme conditions, there is a possibility of
serious injury or loss of life.
Operator error could result in injury or equipment
damage.
Caution
Warning
Danger
•Do not disassemble, modify (including changing the printed circuit
board) or repair.
An injury or failure can result.
•Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
•Do not operate in an atmosphere containing flammable or
explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
•Do not use the product in a place where static electricity is a
problem.
Otherwise it can cause failure or malfunction of the system.
•If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical
system
•Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
•The following instructions must be followed during maintenance:
•Turn off the power supply
•Stop the air supply, exhaust the residual pressure and verify that
the air is released before performing maintenance.
Otherwise an injury can be caused.
Caution
Names and Functions of Individual Parts
Installation
Model Indication and How to Order
Installation
Mounting
*: The tightening torque of piping port must be 1Nm for M5 and 7 to 9 Nm for R1/8 and
NPT1/8.
•Mount with the set screws M3 size (2 pcs.) for direct installation.
The tightening torque of the mounting screw must be 0.5 to 0.7 Nm.
Warning
Safety Instructions (Continued)
Refer to the operation manual,and catalogue for this product.
LED display
Output (OUT1) Light (Green)
button (UP)
button (SET)
button (DOWN)
Output (OUT2)
Light (Red)
Connector
Output (OUT1) Light (Green): Lights ON when the switch output (OUT1) is
turned ON.
Output (OUT2) Light (Red): Lights ON when the switch output (OUT2) is
turned ON.
LED display: Displays the current status of pressure, setting mode and error
code.
button (UP): Selects the mode or increases the ON/OFF set value.
Press this button to change to the peak display mode.
button (DOWN): Selects the mode or decreases the ON/OFF set value.
Press this button to change to the bottom display mode.
button (SET): Press this button to change to either mode and to set a
value.
No-load voltage (V peak) Max. current rating (A)
0 to 20 [V] 5.0
20 to 30 [V] 100 / peak voltage
Mounting with panel mount adapter
•Panel mount adapter + Front protective cover (Model: ZS-39-D)
Panel
Panel mount adapter
Front protective cover
Piping
Connection using One-touch fitting
1. Cut the tube perpendicularly.
2. Hold the tube and insert it into the One-touch fitting slowly until it
bottoms out.
•Allow sufficient tube length to prevent twist, tensile and moment load
from being applied to the fitting and tube.
•When using a tube manufactured by a company other than SMC,
check its outside diameter accuracy satisfies the following conditions.
1) Nylon tube: ±0.1 mm maximum
2) Soft nylon tube: ±0.1 mm maximum
3) Polyurethane tube: +0.15 mm/-0.2 mm maximum
M3
One-touch fitting
Tube
Removal and mounting of DIN rail
•It is necessary to prepare a DIN rail adapter for mounting on the DIN rail
(Model: ZS-39-R)
•Take care not to bend the claws of the DIN rail adapter when mounting.
Claw 1 Claw 2
<Mounting of DIN rail adapter>
Engage the pressure switch with claw 2 of the DIN rail adapter ,than
press down horizontally on to claw 1 until it clicks.
Claw 1
Claw 2
[1]
[2]
[3]
<Mounting on DIN rail>
Engage claw 1 of the adapter on to the DIN rail as indicated [1], apply
force in direction [2] indicated, then press downward horizontally [3] until
claw 2 clicks on to the DIN rail.
<Removal of DIN rail>
Claw 1
Claw 2
[2]
[1]
Move in the direction [1], and remove claw 1 as indicated with [2].
Installation (Continued)
MPa
kPa
Nil or M
P
Unit specification Default setting
PSI
ISE10
ZSE10(F)
Pressure range
ISE10
ZSE10(F)
ZISE##-TFM113GB
Pressure Setting
<How to operate>
•Hysteresis mode
1, Press the button once in measurement mode.
Set ON point and OFF point of the Pressure switch.
Operation
When the pressure exceeds a set point, the Pressure switch will be
turned on.
When the pressure falls below the set point by the amount of hysteresis or
more, the Pressure switch will be turned off.
The default setting of the output set value is the central value between the
atmospheric pressure and the upper limit of the rated pressure range.
If the operation shown below does not cause any problem, keep this
operation setting.
2, [P_1] or [n_1] and the set value are displayed in turn.
3, Press the or button to change the set value.
The button is for increase and the button is for decrease.
•Press the button once to increase by one figure, and press it
continuously to keep increasing the set figure.
•Press the button once to decrease by one figure, and press it
continuously to keep decreasing the set figure.
4, Press the button to finish the setting.
If 2 outputs specification is selected, [P_2] is displayed.
Set OUT2 in the same way as OUT1.
The Pressure switch operates within a set pressure range (from P1L to
P1H) during window comparator mode. Set P1L (switch lower limit) and
P1H (switch upper limit) using the setting procedure above.
Zero clear of indication
Indication is reset to zero when and buttons are pressed
simultaneously for 1 second.
For the first operation, perform zero clear without pressure supply.
Switch ON
For normal output Switch OFF
set value
P_1 hysteresis
H_1
[Pa]
Time [s]
Pressure
Displays in turn
Normal output
Reversed output
Setting
Internal Circuit and wiring(Continued)
Internal circuit and wiring example
-B
PNP open collector 2 outputs
Max. 80 mA
Residual voltage 2 V or less
Brown DC(+)
Black OUT1
White OUT2
Blue DC(-)
Main Circuit
12 to
24 VDC
+
-
Load
Load
Grey FUNC
-C
NPN open collector 1 output
Max. 28 V, 80 mA
Residual voltage 2 V or less
Analogue voltage output
Output impedance approx. 1 k
Brown DC(+)
Main Circuit
12 to
24 VDC
Black OUT1
White OUT2
Blue DC(-)
+
-
Load
Load
Grey FUNC
-A
NPN open collector 2 outputs
Max. 28 V, 80 mA
Residual voltage 2 V or less
Brown DC(+)
Black OUT1
White OUT2
Blue DC
(
-
)
12 to
24 VDC
+
-
Load
Load
Grey FUNC
Main Circuit
-E
PNP open collector 1 output
Max. 80 mA
Residual voltage 2 V or less
Analogue voltage output
Output impedance approx. 1 k
Brown DC(+)
Main Circuit
12 to
24 VDC
Black OUT1
White OUT2
Blue DC(-)
+
-
Load
Load
Grey FUNC
Item
Output mode
Reversed output
Pressure setting
Hysteresis
Explanation
Selects hysteresis mode,
window comparator mode or
OFF mode.
Selects reversed output.
Sets ON point or OFF point of
the switch output.
Chattering can be prevented by
setting hysteresis.
Default setting
Hysteresis mode
Normal output
ISE10: 0.500 MPa
ZSE10: -50.5 kPa
ZSE10F: 50.0 kPa
5%
Default setting
At the time of shipment, the following settings are provided.
If the setting is acceptable, keep it for use.
To change setting, enter function selection mode.
To set each function in detail, refer to the operation manual.
•[F 0] Unit conversion function
•[F 1] Setting of OUT1
•[F 2] Setting of OUT2
Same setting as [F 1] OUT1.
[F 3] Setting of response time
[F 4] Setting of auto-preset
[F 6] Setting of fine adjustment of display value
[F11] Setting of display resolution
[F80] Setting of power saving mode
[F81] Setting of security code
[F90] Setting of all functions
[F97] Selection of copy function
[F98] Check of output
[F99] Reset to the default setting
Item
2.5 ms
Manual
0%
1000-split
OFF
OFF
OFF
OFF
Normal
OFF
Default setting
Measurement mode
The measurement mode is the condition where the pressure is detected
and indicated, and the switch function is operating.
This is the basic mode, and other modes should be selected for setting
change and other function setting changes.
Measurement mode
1s
1s
1s
Display to show the unit specification
Display to show the product
The power is supplied
1s
Display to show the standard product
Display to show the pressure range
DC(+)
Brown
Pin No.
OUT1
Black
OUT2
White
(FUNC)
Grey
DC(-)
Blue
5
4
3
2
1
Internal Circuit and wiring
Wiring
Connection
•Make connection after turning the power off.
•Use a separate route for wiring to the Pressure switch.
Malfunction stemming from noise may occur if the wire is installed in the
same route as that of power or high-voltage cable.
•Be sure to ground terminal FG when using a commercially available
switch-mode power supply. When the switch-mode power supply is
connected to the Pressure switch, switching noise will be
superimposed and product specification can no longer be met. This can
be prevented by inserting a noise filter, such as a line noise filter and
ferrite core, between the switch-mode power supply and the Pressure
switch, or by using a series power supply instead of the switch-mode
power supply.
Connector
Connecting/Disconnecting
•When mounting the connector, insert it straight into the socket, holding
the lever and connector body, and fit the hook of the lever into the
groove in the housing to lock.
•When removing the connector, press down the lever to release the hook
from the groove and pull the connector straight out.
Housing
Socket
Connector
Groove Lever
Cable
(Model: ZS-39-5G)
Pin No. of the Connector
Setting (Continued) Setting (Continued)
To set [F 2] setting of OUT2 in detail, refer to the operation manual.
•Window comparator mode
ZISE##-TFM113GB
Specification
Refer to the operation manual and catalogue for this product.
Outline with Dimensions (in mm)
Refer to the operation manual and catalogue for this product.
Contact
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888
BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20
CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600
DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880
FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725
FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412
GERMANY (49) 6103 4020 SPAIN (34) 945 184 100
GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200
HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131
IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888
ITALY (39) 02 92711
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer.
©2008 SMC Corporation All Rights Reserved.
Troubleshooting
Refer to the operation manual for this product.
Error Indication Function
If the error can not be reset after the above measures are taken, then
please contact SMC.
This function is to display error location and content when a problem or
an error occurs.
Maintenance
Other Functions
•Peak/Bottom hold value indication
•Zero clear
•Key lock
To set each function in detail, refer to the operation manual.
How to reset the product for power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or
de-energizing.
The output condition is also basically recovered to that before a power
cut or de-energizing, but may change depending on the operating
environment. Therefore, check the safety of the whole system before
operating the product.
If the system is using accurate control, wait until the pressure switch has
warmed up (approximately 10 minutes)
Function selection mode
In measurement mode, press the button for 2 seconds or longer to
display [F 0]. Select to display the function setting to be changed, [F ].
Press the button for 2 seconds or longer in function selection mode to
return to measurement mode.
*: Some functions are not available depending on part number. All functions are
displayed with [F ] and followed with function description. If a function is not
available for specified type, the function is displayed as [---].
To set each function in detail, refer to the operation manual.
Setting (Continued)
Measurement mode
Function selection mode
Setting functions
Press the button
for 2s or longer.
System
Error
Turn the power off and
turn it on again.
If resetting fails, an
investigation by
SMC CORPORATION
will be required.
Error Name Troubleshooting
Method
Error type
Error
Display
Displayed in the case of
an internal
data error.
Error Name Troubleshooting
Method
Error Nature
Over
current
Error
Zero-clear
Error
Error
Display
Pressurizing
Error
A load current of switch
output is 80 mA or
more.
During zero clear
operation, pressure
over ±7%F.S.
(±3.5%F.S.for
compound pressure) is
applied. After 1 s, the
mode will reset to the
measurement mode.
±1%F.S. of the zero
clear range varies
with individual product
differences.
Pressure has exceeded
the upper limit of the set
pressure range.
Turn the power off and
remove the output
factor for the over
current.
Then turn the power
on.
Perform zero clear
operation again after
restoring the applied
pressure to an
atmospheric pressure
condition.
Reset applied pressure
to a level within the set
pressure range.
Pressure has exceeded
the lower limit of the set
pressure range.
Error Indication Function (Continued)

Other manuals for ZSE10 Series

2

This manual suits for next models

2

Other SMC Networks Switch manuals

SMC Networks EZ Switch SMC-EZ1016DT Owner's manual

SMC Networks

SMC Networks EZ Switch SMC-EZ1016DT Owner's manual

SMC Networks ZSE20A User manual

SMC Networks

SMC Networks ZSE20A User manual

SMC Networks ZSE30A series User manual

SMC Networks

SMC Networks ZSE30A series User manual

SMC Networks SMC TigerSwitch 10/100 SMC6110L2 User manual

SMC Networks

SMC Networks SMC TigerSwitch 10/100 SMC6110L2 User manual

SMC Networks TigerSwitch SMC8708L2 User manual

SMC Networks

SMC Networks TigerSwitch SMC8708L2 User manual

SMC Networks 8504T FICHE User manual

SMC Networks

SMC Networks 8504T FICHE User manual

SMC Networks ZSE20CF-L User manual

SMC Networks

SMC Networks ZSE20CF-L User manual

SMC Networks PF3W5 Series User manual

SMC Networks

SMC Networks PF3W5 Series User manual

SMC Networks ISE70G-N02-L2 User manual

SMC Networks

SMC Networks ISE70G-N02-L2 User manual

SMC Networks 6624FMSC - annexe 1 User manual

SMC Networks

SMC Networks 6624FMSC - annexe 1 User manual

SMC Networks SMC6724AL2 User manual

SMC Networks

SMC Networks SMC6724AL2 User manual

SMC Networks EZ Connect User manual

SMC Networks

SMC Networks EZ Connect User manual

SMC Networks FS5 - FICHE TECHNIQUE Operating and safety instructions

SMC Networks

SMC Networks FS5 - FICHE TECHNIQUE Operating and safety instructions

SMC Networks SMC8606T User manual

SMC Networks

SMC Networks SMC8606T User manual

SMC Networks ZSE40A User manual

SMC Networks

SMC Networks ZSE40A User manual

SMC Networks ISE80 User manual

SMC Networks

SMC Networks ISE80 User manual

SMC Networks D-F7K Installation instructions

SMC Networks

SMC Networks D-F7K Installation instructions

SMC Networks D-M9 Series User manual

SMC Networks

SMC Networks D-M9 Series User manual

SMC Networks IS3000 Series User manual

SMC Networks

SMC Networks IS3000 Series User manual

SMC Networks D-F8B Series Instruction Manual

SMC Networks

SMC Networks D-F8B Series Instruction Manual

SMC Networks 6724AL2 Programming manual

SMC Networks

SMC Networks 6724AL2 Programming manual

SMC Networks EZ Connect User manual

SMC Networks

SMC Networks EZ Connect User manual

SMC Networks TigerSwitch SMC8708L2 User manual

SMC Networks

SMC Networks TigerSwitch SMC8708L2 User manual

SMC Networks 6924MT User manual

SMC Networks

SMC Networks 6924MT User manual

Popular Switch manuals by other brands

Samsung WAM250 user manual

Samsung

Samsung WAM250 user manual

FXC FXC5024 user manual

FXC

FXC FXC5024 user manual

EuroLite LVH-7 user manual

EuroLite

EuroLite LVH-7 user manual

Dungs AA-A1-0 Series installation instructions

Dungs

Dungs AA-A1-0 Series installation instructions

Lightwave Communications ServerSwitch 8200 user manual

Lightwave Communications

Lightwave Communications ServerSwitch 8200 user manual

Lutron Electronics Maestro MS-OPS6-DDV manual

Lutron Electronics

Lutron Electronics Maestro MS-OPS6-DDV manual

Digitus DN-80111 manual

Digitus

Digitus DN-80111 manual

SsecureNetworx StreamBuddy user guide

SsecureNetworx

SsecureNetworx StreamBuddy user guide

Hawking HKS104 Quick installation guide

Hawking

Hawking HKS104 Quick installation guide

Huawei CR-SRUB Specifications

Huawei

Huawei CR-SRUB Specifications

EUCHNER STP AS1 Series operating instructions

EUCHNER

EUCHNER STP AS1 Series operating instructions

D-Link DSS-100E-18P Quick installation guide

D-Link

D-Link DSS-100E-18P Quick installation guide

Clas Ohlson MA-001 quick start guide

Clas Ohlson

Clas Ohlson MA-001 quick start guide

Kathrein EXD 158 Twin manual

Kathrein

Kathrein EXD 158 Twin manual

3Com SuperStack 4 Configuration guide

3Com

3Com SuperStack 4 Configuration guide

Cisco Intelligent Gigabit Ethernet Switch Module manual

Cisco

Cisco Intelligent Gigabit Ethernet Switch Module manual

Farnell SY-UHD-S41A installation guide

Farnell

Farnell SY-UHD-S41A installation guide

DRIESCHER-WEGBERG LDTM Operation and assembly instructions

DRIESCHER-WEGBERG

DRIESCHER-WEGBERG LDTM Operation and assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.