
P
i
p
i
n
g
Water supply and return connections are 1/2” copper tube for the PSU10, 15, 23 and 3/4” for the PSU30 and 40.
The water supply is fed at the bottom connection and the return is the top connection (with the built-in bleeder air
vent). Check to see that both soldered connectionsare leak free.
Note: Isolation valvesare recommended on both supply and return piping to allow for service and balancing if
n
ecess
a
r
y
.
After filling the fan convector with water, it will be necessary to remove the air from it. A built in bleeder air vent is
located on the return pipe at the top left of the unit. This vent may be operated with a screwdriver. Be careful as
some water may be bled along with air. Since air accumulates at the high points of a system, it may be necessary to
repeat this step after initial operation.
See diagrams for recommended piping diagrams.
E
lec
t
r
ic
a
l
C
o
nn
ec
t
io
n
s
ALL
ELECTRICAL CONNECTIONS
MUST COMPLY WITH LOCAL OR NATIONAL
R
E
G
U
L
A
T
I
O
NS.
IF IN DOUBT, CONSULT A QUALIFIED
ELE
C
T
R
I
C
I
AN.
Smith’s Profile fan convectors are UL approved.
Remove the electrical junction box cover through the screw provided. There are two knockouts in the back and side
of the junction box. Select the most convenient and bring wiring through it. Supply conductors should be 14 AWG
and protected by a 15 AMP over current protector. Connect line input to black lead, neutral to white lead and
ground to pillar marked G inside the junction box. Refer to diagram below for complete wiring instructions.
O
p
e
r
a
t
io
n
Before replacing the outer cover, ensure that the fan convector is operating properly. Activate the system thermostat
and place speed switch in position I. Because of the low limit aquastat, it may be several minutes before the fan
comes on. When it does come on, make sure that the switch is operational by moving to Off then II. Best results are
obtained by leaving the switch in position I and reserving II for quick heat up or extreme conditions. If the unit is
not operating, see the troubleshooting tips at the end of the manual.
U
n
i
t
m
a
i
n
t
e
n
a
n
ce
The Profile series fan convectors are designed for years of trouble free operation with very little maintenance. It is
recommended however, that the unit be vacuumed occasionally through the front grille. This is especially important
in areas with lots of dust, pet hair and dirt.
If servicing is required beyond this, contact the installing contractor or
Smith’s
Environmental
P
r
o
du
c
t
s
Customer Service
300 Pond St
Randolph, MA 02368
(781) 986 – 2525
T
r
o
ub
les
h
oo
t
i
n
g
T
i
p
s
If the fan convector does not operate:
Verify that supply voltage is 120 VAC, all wires are connected and fan switch is in Min or Max position.
Verify that hot water is going to and through the unit at 130ºF or above. Both supply and return pipes should be
hot. An air bound coil will prevent the fan from operating. Bleed air from the coil if necessary.
By pass the low limit aquastat using a jumper wire. If the fan now runs, replace the aquastat.
If the fan does not run while the aquastat is jumped, replace the motor assembly.