
The Pocket Wall Unit (PWU) has been designed for a recessed wall application. The unit can be installed
either directly to the studwork by using the adjustable side mounting brackets set to suit the associated
sheetrock thickness or mounting directly to the sheetrock by removing the side mounted brackets and
securing with screws (field supplied) through the holes located in the chassis flanges. The front grille
assembly is secured to the side flanges via screws. The area in front of this unit must not be obscured or
restricted. Vertical surfaces in front of this unit will impede the air flow and reduce it’s capacity.
INSTALLATION PROCEEDURES
Preparation.
Carefully unpack the unit from the carton. The front cover grille has been packed separately and should
be stored safely until required.
Stud Wall (on top of sheet rock)
Remove the side mounting brackets from the unit chassis.
Mark a distance up from the floor to the desired mounting height. Cut the rough between the studwork to
the dimensions, which correspond to the unit size being installed. (Table 2) Place the unit chassis with
the top facing up, level with the mark between studs and ½” to the top of the opening and secure with
suitable wood screws (field supplied) through the four vacant screw holes (two in each flange). The grille
cover will be installed on the chassis after the piping, wiring and air bleeding has been completed.
Stud wall (prior to sheet rock)
Mark a distance up from the floor to the desired mounting height. Select the desired thickness of sheet
rock to be used, loosen the screws and adjust the side mounting brackets to the appropriate size, tighten
the screws. Place the unit chassis with the top facing up, level with the mark between the studs and
secure with suitable wood screws (field supplied) through the four screw holes in the side brackets (two
in each flange).
The appropriate size sheet rock can now be fitted around the unit, care must be taken to ensure there is
a ½” gap between the top of the unit and the sheetrock. The grille cover will be installed on the chassis
(using the four screws provided) after piping, wiring and air bleeding has been completed.
Table 1
Unit A B
PWU 4/6 19½” 17 1/8 “
PWU 6/8 19½” 17 1/8 “
PWU 8/10 19½” 21”
PWU 13/15 19½” 31½“
Note: When fixing unit to studwork ensure there is a ½” gap between the chassis and
the top of the cut-out.
Table 2
Unit C D E F
PWU 4/6 17½ “ 1¼” 14 1/8”3½”
PWU 6/8 17½ “ 1¼” 14 1/8” 3½”
PWU 8/10 17 ½” 1¼” 18 3/8 “ 3½”
PWU 13/15 17½ “ 1¼” 28 ½” 3½”
Piping location
Solder the heating system Supply tube to the “back” chassis tube first. Then solder the return line to the
“front” chassis tube. After soldering the Return connection (front tube), check that both connections are
leak free.
Note: isolation valves are recommended on both supply and return piping to allow for
service and balancing if necessary.
When filling the PWU recess unit with system water, it will be necessary to remove the air from it. A built
in manual air vent is accessible on the top left hand side of the unit (this is only accessible with the front
cover grille removed). Using a slotted screwdriver turn counter clockwise until the air is purged (some
water may also be bled along with the air).
Check to make sure that the PWU will receive the flow (GPM) required to achieve it’s duty point, it may
be necessary to balance the system to achieve the desired flow rate.
Electrical.
ALL ELECTRICAL CONNECTIONS MUST COMPLY WITH LOCAL AND/OR NATIONAL
CODES AND REGULATIONS. IF IN DOUBT, CONSULT A QUALIFIED ELECTRICIAN.