KM2130B-O3 Us e r Ma nual http://www.sonbus.com/
Sha nghai Sonbest Industrial Co., Ltd Page4
(1) Read baud rate
The device default factory baud rate is 9600. If you need to change it, you can change it
according to the following table and the corresponding communication protocol. For
example, read the current device's baud rate ID, the command is:01 03 00 67 00 01 35
D5 , its format is parsed as follows.
Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is
4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example the response data
is: 01 03 02 00 03 F8 45, the format of which is as shown in the following table:
coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
(2)Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3
to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .
Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new
baud rate will take effect immediately, at which point the device will lose its response and
the baud rate of the device should be queried accordingly. Modified.
4 Read Correction Value
(1) Read Correction Value
When there is an error between the data and the reference standard, we can reduce the
display error by adjusting the correction value. The correction difference can be modified
to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example,
when the display value is too small, we can correct it by adding 100. The command is: 01
03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can
set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C,
which is calculated as 100-65535=65435, and then converted to hexadecimalto 0x FF 9C.
The correction value starts from 00 6B. We take the first parameter as an example. The