Spectra 1759ex User manual

1759EX V1.0
REFERENCE & INSTALLATION MANUAL
(433MHZ/ 868MHZ)
1759EX


SPECTRA SERIES 1
TABLE OF CONTENTS
Introduction..................................................................... 2
Features ..................................................................................................... 2
Specifications ............................................................................................. 2
Installation ...................................................................... 3
Location and Mounting............................................................................... 3
Earth Ground.............................................................................................. 3
AC Power ................................................................................................... 3
Backup Battery........................................................................................... 3
Auxiliary Power Terminals*......................................................................... 5
Telephone Line Connection........................................................................ 5
Bell Output Connection............................................................................... 5
Programmable Output Connections*.......................................................... 5
Single Zone Inputs...................................................................................... 6
Keypad and Keypad Zone Connections..................................................... 6
Keyswitch Connections .............................................................................. 7
Fire Circuits ................................................................................................ 7
Programming Methods.................................................... 8
WinLoad Software for Windows*................................................................ 8
Programming Using a Keypad.................................................................... 8
Configuring The LED Keypads................................................................... 9
Programming Using A Paradox Memory Key* ......................................... 10
Access Codes................................................................ 11
Access Code Length ................................................................................ 11
Installer Code ........................................................................................... 11
System Master Code................................................................................ 11
User Code Options................................................................................... 11
Lock Master Code .................................................................................... 12
Duress Code............................................................................................. 12
Zone Programming........................................................ 13
What is an Expansion Input?.................................................................... 13
Reassign Keypad Zone 2......................................................................... 13
Reassign Zones to Expansion Inputs....................................................... 14
Zone Programming................................................................................... 14
Zone Definitions........................................................................................ 15
Exclusive Zone Definitions ....................................................................... 16
Zone Partition Assignment ..................................................................... 17
Zone Options............................................................................................ 17
Zone Speed.............................................................................................. 18
EOL Zones ............................................................................................... 18
Wireless Features ......................................................... 19
Wireless Transmitter Programming.......................................................... 19
Viewing the Wireless Transmitter Signal Strength ................................... 19
Serial Number Display.............................................................................. 20
Supervision Options ................................................................................. 20
Remote Control Programming.................................................................. 21
Arming and Disarming Options..................................... 24
Switch To Stay Arming............................................................................. 24
Stay Arming with Delay............................................................................ 24
Regular Arming switches to Force Arming (Not to be used with UL Installa-
tions)......................................................................................................... 24
Restrict Arming On Battery Fail................................................................ 24
Restrict Arming On Tamper Failure.......................................................... 24
Timed Auto-Arming................................................................................... 24
No Movement Auto-Arming...................................................................... 25
Auto-Arming Options................................................................................ 25
One-Touch Arming................................................................................... 25
Exit Delay ................................................................................................. 25
Bell Squawk On Arm/Disarm With Keypad............................................... 26
Bell Squawk On Arm/disarm with Remote Control................................... 26
No Exit Delay When Arming with Remote Control ................................... 26
No Exit Delay Beeps and No Bell Squawk When Stay Arming................ 26
Alarm Options............................................................... 26
Bell Cut-Off Timer..................................................................................... 26
Recycle Alarm .......................................................................................... 26
Tamper Recognition................................................................................. 26
Keypad Panic Options.............................................................................. 27
Panic Lockout Timer................................................................................. 27
Reporting and Dialer settings....................................... 28
Reporting/Dialer (Enable/Disable)............................................................ 29
Report Codes ........................................................................................... 29
Central Station Telephone Numbers........................................................ 31
Partition Account Numbers....................................................................... 31
Reporting Formats.................................................................................... 31
Pager Delay.............................................................................................. 33
Event Call Direction.................................................................................. 33
Dialing Method.......................................................................................... 33
Pulse Ratio............................................................................................... 33
Bell on Communication Failure................................................................. 33
Dial Tone Delay........................................................................................ 34
Maximum Dialing Attempts....................................................................... 34
Delay Between Dialing Attempts.............................................................. 34
Alternate Dial Option ................................................................................ 34
Recent Close Delay.................................................................................. 34
Auto Test Report ...................................................................................... 34
Power Failure Report Delay ..................................................................... 34
Disarm Reporting Options........................................................................ 34
Zone Restore Report Options................................................................... 35
Telephone Line Monitoring (TLM) ............................................................ 35
Programmable Outputs................................................ 35
PGM Activation Event............................................................................... 35
PGM Deactivation Event .......................................................................... 36
PGM Delay............................................................................................... 36
PGM Normal State ................................................................................... 36
PGM2 Strobe Options .............................................................................. 36
Alarm Relay Options................................................................................. 36
System Settings............................................................ 37
Hardware Reset........................................................................................ 37
Installer Lock ............................................................................................ 37
Keypad Lockout Feature .......................................................................... 37
Battery Charge Current ............................................................................ 37
Partitioning................................................................................................ 37
System Real-Time Clock.......................................................................... 37
Clock Adjust.............................................................................................. 37
Keypad Tamper Supervision.................................................................... 38
Keypad Audible Trouble Warning............................................................. 38
Confidential Mode..................................................................................... 38
Installer Quick Functions Keys................................................................. 39
PGM Modules Supervision....................................................................... 39
Printer Module Supervision ...................................................................... 39
Zone Expansion Bus Module Supervision................................................ 39
Wireless Transmitter Low Battery Supervision......................................... 40
Wireless Transmitter Supervision Options ............................................... 40
ReProgram All Expansion Modules.......................................................... 40
Settings for WinLoad Software..................................... 41
Panel Answer Options.............................................................................. 41
Panel Identifier.......................................................................................... 41
PC Password............................................................................................ 41
PC Telephone Number............................................................................. 41
Call WinLoad Software............................................................................. 41
Answer WinLoad Software....................................................................... 42
Auto Event Buffer Transmission............................................................... 42
Call Back WinLoad................................................................................... 42
User Operation............................................................. 42
Trouble Display......................................................................................... 42
Programming Access Codes.................................................................... 43
Disarming & Deactivating an Alarm.......................................................... 44
Regular Arming......................................................................................... 44
Stay Arming.............................................................................................. 44
Instant Arming .......................................................................................... 45
Force Arming............................................................................................ 45
Manual Bypass Programming .................................................................. 45
One-Touch Arming................................................................................... 45
Keyswitch Arming..................................................................................... 46
Panic Alarms ............................................................................................ 46
Auto-Arming.............................................................................................. 46
Alarm Memory Display ............................................................................. 46
Programming Chime Zones...................................................................... 46
Keypad Muting.......................................................................................... 47
Keypad Backlight...................................................................................... 47
FCC WARNINGS............................................................. 48
Index.............................................................................. 50

2REFERENCE & INSTALLATION MANUAL
PART 1: INTRODUCTION
1.1 FEATURES
• Up to 15 fully programmable zones
• Two completely independent partitions. Many of the features and options in the Spectra System can be independently set for
each partition such as event reporting, entry/exit delay, auto-arming and many more. All zones, the keyswitches and all user
codes are assigned to specific partitions, which makes this a true partitioned system.
• Communication bus facilitates the adding, programming and monitoring of all expansion modules.
• 1 Installer Code and 48 User Codes (including: 1 System Master, 2 Masters, and 1 Duress)
• 2 on-board, fully programmable outputs (PGMs) and one 5A alarm relay
• Simple, direct and logical programming
• Event Call Direction: The Spectra 1759EX control panel events are divided into 5 groups of events. Each of these event groups
can be programmed with a separate dialing sequence.
• Two 32-digit Central Station Telephone Numbers and one 32-digit Backup Telephone Number
• Contact ID, Pager Format and many more High-Speed Communication Formats
• "False Alarm Prevention" features such as: Intellizone, Auto Zone Shutdown, Beep on Exit Delay, Programmable Delay Before
Alarm Transmission, and Recent Closing Report
• Regular Arming, Stay Arming, Instant Arming, Force Arming, One-Touch Arming, Auto-Arming, or Keyswitch Arming
• 256 Event Buffer with time stamp
• Telephone Line Supervision
• Keypad activated panic alarms
• Compatible with Winload Security System Management Software for Windows®
1.2 SPECIFICATIONS
1.2.1 SPECTRA 1759EX CONTROL PANEL
• AC Power: 16Vac transformer (refer to Table 1 on page 3) with minimum 20VA rating (Rec.:
40VA), 50 to 60Hz
• Battery: 12Vdc, 4Ah/7Ah
•Aux.Power:
+600mA typical, 700mA maximum, fuseless shutdown @ 1.1A
• Bell Output:++ 1A, fuseless shutdown @ 3A
• PGM Outputs: PGM1 = 150mA low-current output, PGM2 = 1A high-current output
• Alarm Relay: One form “C” relay rated @ 125V, 5A receptive load
• Approvals: 433MHz
868MHz
Compliant to all EU and EFTA countries except Greece according
to RTT&E directives.
1.2.2 SPECTRA KEYPADS (1686H, 1686V, 1689 AND 1641)
• Power input: Typically 9-16Vdc
• 1 standard keypad zone
• On-board tamper switch (optional)
1686H and 1686V 10-Zone LED Keypad
• Current consumption: 62 to 116mA
1689 16-Zone LED Keypad
• Current consumption: 50 to 117mA
1641 32-Character LCD Keypad
• Current consumption: 60 to 80mA
• PGM: 1 with 50mA current limit
• LCD: Super Twisted Nematic display (STN), Wide viewing angle, Backlight & Contrast
adjustable
Specifications may change without prior notice
+Cannot exceed 200mA for UL installations
++ Cannot exceed 1A for UL installations

SPECTRA 1759EX 3
PART 2: INSTALLATION
2.1 LOCATION AND MOUNTING
Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet
and prepare them for connection before mounting the circuit board into the back of the cabinet. Select a centralized installation
site on the main floor that isn't easily accessible to intruders and leave at least 5cm (2in.) around the panel box to permit
adequate ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and
telephone line connection. Avoid installation near or in the path of strong RF fields (i.e. neon lights, computers), on or near metal
objects, circuit breaker boxes, air conditioners and heater ducts since they may cause interference and reduce sensitivity. Avoid
installing the 1759EX in the basement.
Do not cut, bend or alter the antennae and ensure that electrical wires do not cross over the antennae as these
may affect the signal reception.
2.2 EARTH GROUND
Connect the zone and dialer ground terminals from the control panel to the metallic enclosure and cold water pipe or grounding
rod as per local electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in
Figure 2.2 on page 4. For UL installations, the metallic enclosure must be grounded to the cold water pipe.
2.3 AC POWER
Do not use any switch-controlled outlets to power the transformer. Connect the transformer as shown in Figure 2.1 on page 3.
Use Table 1 to determine the required transformer.
2.4 BACKUP BATTERY
To provide power during a power loss, connect a 12Vdc 4Ah rechargeable acid/lead or gel cell backup battery as shown in Figure
2.1 on page 3. Use a 7Ah battery to comply with UL fire requirements. Connect the backup battery after applying AC power. When
installing, verify proper polarity as reversed connections will blow the battery fuse. Also, refer to Battery Charge Current on page 37.
2.4.1 BATTERY TEST
If the battery is disconnected or if the battery fuse is blown, a No/Low Battery failure will appear in the keypads’ Trouble
Display (see page 42). This trouble will also appear if the battery’s capacity is too low or if the voltage drops to 10.5
volts or lower while the control panel is running on the backup battery. At 8.5 volts or lower, the panel shuts down and
all outputs close.
Figure 2.1: AC Power and Backup Battery Connections
Table 1:
Transformer Requirements Table
Transformer: Amseco XP-1620 16VAC 20VA
(not verified by UL) UL: Basler Electric BE156240CAA007
16.5VAC 40VA
Spectra DC Power Supply rated at: 1.2A 1.5A
Auxiliary Supply can provide a maximum of: typ: 600mA, max: 700mA typ: 600mA, max: 700mA
Do not exceed 200mA for UL installations
Acceptable Battery Charge Currents 350mA 350mA/700mA

4REFERENCE & INSTALLATION MANUAL
Figure 2.2: Spectra 1759EX Control Panel Overview
For the keypad’s zone, EOL and tamper
configurations, refer to Configuring The
LED Keypads on page 9.
Refer to Single Zone Inputs on
page 6
Refer to AC Power
and Backup Battery
Connections on
page 3.
To connect the 5A Alarm Relay and the PGMs,
refer to Relay and PGM Connections on page 6.
To connect AC power, refer to AC Power and
Backup Battery Connections on page 3.
For UL Listed Warnings, refer to UL AND ULC WARNINGS on page 49.
Warning: Donotcut,
bend or alter the
antennae & ensure
that electrical wires
do not cross over the
antennae as these
may affect the signal
reception.

SPECTRA 1759EX 5
2.5 AUXILIARY POWER TERMINALS*
The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the
security system. A fuseless circuit protects the power supply against current overload and automatically shuts down if the current
exceeds 1.1A. If this occurs, the Maximum Auxiliary Current failure will appear in the keypads’ Trouble Display (see page 42).
Therefore, the combined current consumption of devices connected to the auxiliary power supply should not exceed 700mA. If
the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before
reconnecting any load back to the auxiliary output.
Modules with the APR- prefix are compatible with the Spectra 1759EX and Digiplex. Modules with the APR3- prefix are
compatible with the Spectra 1759EX, Digiplex and DigiplexNE.
2.6 TELEPHONE LINE CONNECTION
In order to report system events to the central station, you must connect the incoming telephone company wires into the TIP and
RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as shown in
Figure 2.2 on page 4.
2.7 BELL OUTPUT CONNECTION
The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm.
The bell output supplies 12VDC upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless
circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will only
appear in the keypads’ Trouble Display (see page 42) during an alarm. If the load on the BELL terminals returns to normal, the
control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens, please verify correct
polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the control panel as
shown in Figure 2.2 on page 4.
If the BELL output is not being used, the Bell Disconnected failure will remain in the keypads’ Trouble Display
(see page 42). To avoid this connect a 1KΩresistor across the BELL terminals.
2.8 PROGRAMMABLE OUTPUT CONNECTIONS*
When a specific event occurs in the system, a PGM can reset smoke detectors, activate strobe lights, open/close garage doors
and much more.
2.8.1 ALARM RELAY AND PGMS
The Spectra 1759EX control panel includes two on-board programmable outputs (PGMs). For details on how to
program the PGM, refer to PGM Programming on page 35. PGM1 can support up to 150mA while PGM2 supports up
to 1A (see Figure 2.3 on page 6) and can be used as a strobe output (see page 36). The PGMs are limited by the
power source being used. If powered by:
•The AUX terminals. The current consumption of the AUX terminals cannot exceed 700mA. Therefore, whatever
devices are connected to the AUX terminals (i.e. modules and PGMs) cannot exceed 700mA combined. For
example, if there are six modules connected to the AUX terminals that are using 600mA and you wish to power the
PGM using the AUX terminals, the PGM’s current consumption will not 100mA.
•An external power supply. If using an external power supply, the current consumption cannot exceed 150mA for
PGM1 and 1A for PGM2. If the external power supply’s current consumption limit is less than that of the PGM it is
connected to, than the current consumption will not exceed the power supply’s current limit.
The Spectra 1759EX control panel also has a 5A relay. This relay can be connected as shown in Figure 2.3 on page 6.
The Alarm Relay can be programmed to follow the bell output or the activation and deactivation of the Global PGM
(see Alarm Relay Options on page 36).
* UL Note: The AUX and PGM terminals cannot exceed 200mA for UL installations.
Table 2:
Current Consumption Table
Modules Current Consumption
Typical Maximum
Spectra 1686H and 1686V 10-Zone LED Keypad 62mA 116mA
Spectra 1689 16-Zone LED Keypad 50mA 117mA
Spectra 1641 LCD Keypad 60mA 80mA
4-Zone Hardwire Modules (APR3-ZX4/SPC-ZX4) 12mA 12mA
8-Zone Hardwire Modules (APR3-ZX8/SPC-ZX8) 30mA 30mA
4-PGM Output Module (APR3-PGM4) 13mA 150mA
Printer Module (APR3-PRT1) 22mA 40mA
InTouch Voice-Assisted Arm/Disarm Module (APR3-ADM2) 70mA 105mA
Motion Detectors (see detector instructions for details) 10 to 50mA

6REFERENCE & INSTALLATION MANUAL
Figure 2.3: Relay and PGM Connections
2.9 SINGLE ZONE INPUTS
Detection devices such as motion detectors and door contacts are connected to the control panel's zone input terminals. Figure
2.4 (below) demonstrates single zone input terminal connections recognized by Spectra. Once connected, the associated zone's
parameters must be defined. For details refer to Zone Programming on page 13.
Figure 2.4: Single Zone Input Connections
2.10 KEYPAD AND KEYPAD ZONE CONNECTIONS
To connect the keypads to the control panel, remove the back cover and wire the GRN, YEL, RED, and BLK terminals of each
keypad to the corresponding terminals on the control panel as shown in Figure 2.2 on page 4. There is no limit to the number of
keypads that can be connected to the control panel so long as the current consumption does not surpass 700mA*. See Keypad
Tamper Supervision on page 38.
Each keypad has one zone input terminal, allowing you to connect one motion detector or door contact directly to a keypad. The
keypad can then communicate the status of the zone to the control panel. A maximum of two keypad zones can be used with
AUX+ or External Power Supply. See
Programmable Output
Connections* on page 5
*UL Note: Cannot exceed 200mA for UL installations.

SPECTRA 1759EX 7
each control panel. After connecting the device, the zone's parameters must be defined. For details on zone recognition and
Zone Programming on page 13. Also, refer to the feature Reassign Keypad Zone 2 on page 13.
Example: A door contact located at the entry point of an establishment can be wired directly to the input terminal of the entry
point keypad instead of wiring the door contact all the way to the control panel.
Figure 2.5: Keypad Zone Connections
When a 1641 LCD keypad is connected to Spectra, the Keypad Zone Sending option (Option [2] key [1]) determines
whether the status of the keypad zone will be transmitted to the control panel. The Keypad Zone Sending option of the
1641 keypad must be enabled during the following conditions:
• If you are using both keypad zones and at least one is from a 1641 keypad.
• If you are using the keypad zones of other types of keypads, such as a 1686H 10-zone LED keypad, and the
keypad zone definition of the 1641 keypad (keypad zone 1 or keypad zone 2; Option [2] key [3]) matches that of
another connected keypad.
2.11 KEYSWITCH CONNECTIONS
Keyswitches allow users to arm or disarm a partition by pushing a button or by activating a
switch with a key. Connect the keyswitch as shown in Figure 2.6 directly to the control
panel terminals. Once a keyswitch is connected, it must be assigned to a zone and its
parameters must be programmed (see Zone Programming on page 13 and Keyswitch
Options on page 18).
2.12 FIRE CIRCUITS
When a zone is programmed as a Fire zone, the zone becomes normally open and requires
an EOL resistor. If a line short occurs or if the smoke detector becomes active, whether the
system is armed or disarmed, the control panel will generate an alarm. If a trouble occurs on a
Fire zone, the Fire Loop Trouble will appear in the keypads’ Trouble Display (see page 42) and
the control panel can transmit the Fire Loop Trouble report, if programmed, in section [206].
2.12.1 4-WIRE INSTALLATION:
Any on-board zone can be defined as a Fire Zone (see page 15) when using the 4-
wire installation. Connect the smoke detectors as shown in Figure 2.7 directly to the
control panel terminals. Program the PGM with the “[PG]/[FNC1] Key was Pressed”
Activation Event (see page 35) so the smoke detectors can be reset by pressing the
[PG] or [FNC1] key. Pressing the [PG] or [FNC1] key will interrupt power to the smoke
detectors for 4 seconds (see PGM Delay on page 36).
It is recommended that all smoke detectors be connected using a daisy chain configuration.
Figure 2.6: Keyswitch
Figure 2.7: Fire Zones

8REFERENCE & INSTALLATION MANUAL
PART 3: PROGRAMMING METHODS
3.1 WINLOAD SOFTWARE FOR WINDOWS*
Program the Spectra Series control panels remotely or on-site using the Winload Software for Windows®. For more information,
contact your local Paradox Distributor or visit our web site at http://www.paradox.ca. If you are using the WinLoad software, you
must program the features explained on pages 41 and 42.
*Not investigated by UL.
3.2 PROGRAMMING USING A KEYPAD
Use the supplied Spectra 1759EX Programming Guide to keep track of which sections were programmed and how. We
recommend you read this entire manual before you begin programming.
3.2.1 SINGLE DIGIT DATA ENTRY METHOD (HEXADECIMAL AND DECIMAL)
Single Digit Data Entry is used in all sections except those specified in the Feature Select Programming Method
(below). After entering the programming mode as described in the shaded box above, some sections will require that
you enter Decimal values from 000 to 255. Other sections will require that you enter Hexadecimal values from 0 to F.
The required data will be clearly indicated in this manual as well as in the Spectra 1759EX Programming Guide. When
entering the final digit in a section, the control panel will automatically save and advance to the next section. Except
sections 001 to 016, after entering the first two digits the control panel will switch to Feature Select Programming.
3.2.2 FEATURE SELECT PROGRAMMING METHOD
After entering sections [001] to [016], [126] to [138], and [302] to [348], each option from [1] to [8] represents a specific
feature or option. Press the key corresponding to the desired option and the corresponding light will illuminate or the
option number will appear in the LCD display. This means the option is on. Press the key again to extinguish the
corresponding light or remove the digit from the LCD display, thereby, turning off the option. Press the [FORCE]key to
set all 8 options to off. Press the keys until the current section’s options are set. When the options are set, press the
[ENTER]key to save and advance to the next section.
3.2.3 DATA DISPLAY MODE (LED KEYPADS ONLY)
In the Data Display Mode you can view the programmed contents of each section one digit at a time. After entering the
desired 3-digit section (see step 3 of the shaded box on page 8), press the [ENTER]key to access the Data Display
Mode (will not function with sections using Multiple Feature Select Programming).
How Do I Enter Programming Mode?
STEP 1: Press [ENTER]
STEP 2: Enter your [INSTALLER CODE] (default: 0000 / 000000)
STEP 3: Enter 3-digit [SECTION] you wish to program
STEP 4: Enter required [DATA]
Table 3:
Decimal and Hexadecimal Programming Table
Value or Action What Do I Press? What Do I See?
10-Zone LED 16-Zone LED LCD
Values 1 to 9 [1] to [9]
[1]
to
[9] [1]
to
[9] [1]
to
[9]
A (hexa only) [0] [0 (10)] [10] 0
B (hexa only) [STAY][STAY][11] B
C (hexa only) [BYP][BYP][12] C
D (hexa only) [MEM][MEM][13] D
E (hexa only) [TBL] / [TRBL][TBL][14] E
F (hexa only) [PG] / [FNC1] [PG][15] F
Exit Without Saving [CLEAR][ENTER] flashes [ARM1] & [STAY1] flash “SECTION [ ]”
Insert Blank Digit [FORCE] Displays next digit or next section
Save Data [ENTER] Advances to the next section

SPECTRA 1759EX 9
Figure 3.1: Data Display Mode (LED Keypads Only)
3.3 CONFIGURING THE LED KEYPADS
Depending on the version of the keypad, two methods can be used to configure the LED keypads (1686H, 1686V and 1689):
3.3.1 CONFIGURING THE 1686H, 1686V AND 1689 KEYPADS V2.0 OR HIGHER
The keypad’s zone number, EOL definition and tamper switch are programmed through the control panel’s
programming mode. To do so:
PLEASE NOTE: After two minutes, the keypad exits programming mode.
Key [1] - Keypad Zone Selection
Key [1] determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When key [1] is OFF (not
illuminated), the keypad’s zone is Keypad Zone 1. When key [1] is ON (illuminated), the keypad’s zone is Keypad Zone
2. Refer to the Table 4 on page 13 for more information.
Key [1] OFF - Keypad Zone 1 (default)
Key [1] ON - Keypad Zone 2
Key [2] - EOL Definition
Key [2] determines the keypad zone’s EOL definition. When key [2] is OFF (not illuminated), EOL is disabled and the
keypad zone will use the on-board EOL resistor. When key [2] is ON (illuminated), EOL is enabled and the keypad
zone requires that an external EOL resistor be connected (refer to Spectra 1759EX Control Panel Overview on page 4
for more details).
Key [2] OFF - EOL disabled
Key [2] ON - EOL enabled (default)
Key [3] - On-Board Tamper
Key [3] enables or disables the keypad’s on-board tamper switch. When key [3] is OFF (not illuminated), the tamper
switch is disabled. When key [3] is ON (illuminated), the tamper switch is enabled.
Key [3] OFF - On-board tamper switch disabled
Key [3] ON - On-board tamper switch enabled
NOTE: The keypad can be ordered with or without a tamper switch. If the keypad has no tamper switch,
key [3] will be OFF by default. If the keypad has a tamper switch, key [3] will be ON by default.
How Do I Configure The Keypad?
STEP 1: Press [ENTER]
STEP 2: Enter your [INSTALLER CODE] (default: 0000 / 000000)
STEP 3: Press the [PG] (1686H/V) / [FNC1] (1689) key and hold it for 3 seconds.
STEP 4: Press the desired key ([1] to [3]. See below)
STEP 5: Press [ENTER] to exit programming mode

10 REFERENCE & INSTALLATION MANUAL
3.3.2 CONFIGURING THE 1686H, 1686V AND 1689 KEYPADS PRIOR TO V2.0
The keypad’s zone number and EOL definition are defined through the jumpers located on the PCB board. The
jumpers are as follows:
J1 - Keypad Zone Select Jumper
Jumper J1 determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When the jumper is OFF, the
keypad’s zone is Keypad Zone 2. When the jumper is ON, the keypad’s zone is Keypad Zone 1. Refer to the Table 4 on
page 13 for more information.
J1 OFF - Keypad Zone 2
J1 ON - Keypad Zone 1
J2 - EOL Definition Jumper
Jumper J2 determines the keypad zone’s EOL definition. When the jumper is OFF, EOL is disabled and the keypad zone
uses the on-board EOL resistor. When the jumper is ON, EOL is enabled and the keypad zone requires that an external
EOL resistor be connected (refer to Spectra 1759EX Control Panel Overview on page 4 and more details).
J2 OFF - EOL disabled
J2 ON - EOL enabled
3.4 PROGRAMMING USING A PARADOX MEMORY KEY*
Copy the sections of one Spectra control panel into the Paradox Memory Key (PMC-3). Then copy the contents of the Memory
Key into as many Spectra control panels as needed. Each panel is programmed in less than 3 seconds.
Download to DESTINATION Control Panel
1) Remove AC and battery power from the control panel.
2) Place the Memory Key on the serial connector labeled KEY of the Spectra Control Panel that is
to receive the contents of the Memory Key.
3) Reapply AC and battery power.
4) In installer programming mode, enter section [900], then press [ENTER] to acknowledge.
5) When the keypad emits a Confirmation Beep, remove the Memory Key.
6) Enter section [750] to reprogram the modules with the information downloaded from the
Paradox Memory Key.
Copy to Memory Key from SOURCE Control Panel
1) Remove AC and battery power from the control panel.
2) Place Memory Key on the serial connector labeled KEY of the Spectra Control Panel that you
want to copy. Make sure the write protect jumper of the Memory Key is on.
3) Reapply AC and battery power.
4) In installer programming mode, enter section [902], then press [ENTER] to acknowledge.
5) When the keypad emits a Confirmation Beep, remove the Memory Key. Remove the Memory
Key’s jumper if you do not wish to accidentally overwrite its contents.
Figure 3.2: Paradox Memory Key
*Not investigated by UL

SPECTRA 1759EX 11
PART 4: ACCESS CODES
The Spectra 1759EX control panel supports the following access codes:
4.1 ACCESS CODE LENGTH
Section [127]: System Options
Option [2] OFF = 6-Digit Access Codes
Option [2] ON = 4-Digit Access Codes (default)
All access codes can be set to lengths of either 4- or 6-digits. When the 4-digit option is selected, entering a 4-digit code will allow
access. Using the 6-digit option, entering 6 digits is required to allow access.
If the Access Code Length is changed from four digits to six digits when access codes have already been
programmed, the control panel will automatically add the last 2 digits by using the first 2 digits. For example, if
the access code is 1234 and you switch to 6 digits, the code will become 123412. Be sure to verify the access
codes after switching from 4-digit access codes to 6-digit codes. When switching from six digits to four digits,
the control panel will simply remove the final two digits of the access code. For example, 123456 will become
1234.
4.2 INSTALLER CODE (Default: 0000 / 000000)
The Installer Code is used to enter the control panel's programming mode (see page 8), which allows you to program all the
features, options and commands of the control panel. The Installer Code can be 4- or 6-digits in length (see above) where each
digit can be any value from 0 to 9. The Installer Code cannot be used to program Master Code 1, Master Code 2 or User Access
Codes. To program the Installer Code press:
[ENTER]+ [CURRENT INSTALLER CODE]+ [281] + new 4- or 6-digit Installer Code
4.3 SYSTEM MASTER CODE (Default: 1234 / 123456)
The Installer Code can be used to program the System Master Code. With the System Master Code a user can use any arming
method and can program any User Access Code, but not the User Code Options. The System Master Code can be 4 or 6 digits in
length Access Code Length on page 11, where each digit can be any digit from 0 to 9. To change the System Master Code press:
[ENTER]+ [INSTALLER CODE]+ [301] + new 4- or 6-digit System Master Code
4.4 USER CODE OPTIONS
Sections [302] to [348]: Options [1] to [7]
The User Code Options define which arming methods each user can use to arm or disarm the system. Regardless of these
settings, all users can Regular Arm assigned partitions and all users except those with the Arm Only option can disarm an
assigned partition, regardless of how it is armed. Select one or more of the options described on the following pages for each
User Access Code, where sections [302] to [348] represent User Access Codes 002 to 048. For more information please refer to
Programming Access Codes on page 43.
4.4.1 PARTITION 1 ASSIGNMENT
Sections [302] to [348]: User Codes 002 to 048
Option [1] OFF = Deny access to partition 1
Option [1] ON = User code has access to partition 1 (default)
If Partitioned (see page 37), user codes with this option enabled can arm and disarm partition 1.
If the system is not partitioned, you must assign partition 1 to the User Access Code. Otherwise, the
User Access Code will be considered disabled.
INSTALLER CODE: Used to program all control panel settings except User Access Codes.
SYSTEM MASTER CODE (001) Provides full access. Arm and disarm using any method described in the User Code Options
in section 4.4 as well as program the User Access Codes.
Master Code 1 (002): Permanently assigned to partition 1. Same as a regular User Code except it can also
program access codes for User Codes assigned to partition 1.
Master Code 2 (003): Permanently assigned to partition 2. Same as a regular User Code except it can program
access codes for User Codes assigned to partition 2. If the system is not partitioned Master
Code 002 will be assigned to partition 1.
45 User Codes (004 to 048): Can arm and disarm as per User Code Options on page 11.

12 REFERENCE & INSTALLATION MANUAL
4.4.2 PARTITION 2 ASSIGNMENT
Sections [302] to [348]: User Codes 002 to 048
Option [2] OFF = Deny access to partition 2 (default)
Option [2] ON = User code has access to partition 2
If the system is partitioned (see page 37), user codes with this option enabled can arm and disarm partition 2. If the
system is not partitioned, the control panel ignores this option.
4.4.3 BYPASS PROGRAMMING
Sections [302] to [348]: User Codes 002 to 048
Option [3] OFF = Bypass Programming Disabled
Option
[3]
ON = Bypass Programming Enabled (default)
User codes with this option enabled can perform Bypass Programming in assigned partitions.
4.4.4 STAY ARMING
Sections [302] to [348]: User Codes 002 to 048
Option [4] OFF = Stay Arming Disabled
Option
[4]
ON = Stay Arming Enabled for selected User Code (default)
User codes with this option enabled can Stay Arm assigned partitions.
4.4.5 FORCE ARMING
Sections [302] to [348]: User Codes 002 to 048
Option [5] OFF = Force Arming Disabled (default)
Option [5] ON = Force Arming Enabled for selected User Code
User codes with this option enabled can Force Arm assigned partitions.
4.4.6 ARM ONLY
Sections [302] to [348]: User Codes 002 to 048
Option [6] OFF = Arm Only Disabled (default)
Option [6] ON = Arm Only Enabled for selected User Code
The user code with this option enabled can arm assigned partitions, but cannot disarm any partitions. The type of
arming is dependent on the other User Code Options selected. Please note that with the Arm Only option, the user can
cancel a recently armed system by re-entering the access code before the end of the Exit Delay.
4.4.7 PGM ACTIVATION
Sections [302] to [348]: User Codes 002 to 048
Option
[7]
OFF = User Code follows User Code Options and can activate a PGM (default)
Option [7] ON = User Code can activate a PGM only
With option [7] off, entering the access code will arm or disarm according to the programmed User Code Options as
well as activate or deactivate a PGM. The appropriate PGM Activation/Deactivation Event must also be programmed
(see Programmable Outputs on page 35). With option [7] on, the control panel will ignore all other User Code Options.
Therefore, entering the access code will only activate or deactivate the PGM.
4.5 LOCK MASTER CODE
Section [127]: System Options
Option [4] OFF = Lock System Master Code Disabled (default)
Option [4] ON = Lock System Master Code Enabled
With this feature enabled, the control panel will lock the System Master Code (001). This means that the System Master Code
cannot be deleted, but it can be changed.
4.6 DURESS CODE
Section [127] = System Options
Option [6] OFF = Duress Code Disabled (default)
Option [6] ON = User Code 048 becomes a Duress code
With this feature enabled, User Code 048 becomes a Duress Code. When forced to arm or disarm their system, users can enter
a Duress Code (User Code 048) to arm or disarm the system which can immediately transmit a silent alert to the Central Station,
transmitting the duress report code programmed in section [196].

SPECTRA 1759EX 13
PART 5: ZONE PROGRAMMING
The Spectra 1759EX control panel’s zone assignment depends on where the detection devices are connected (see Table 4).
5.1 WHAT IS AN EXPANSION INPUT?
An expansion input allows you to connect modules to the system to increase the number of zones available up to 15 zones. Each
hardwired input on a zone expansion bus module or wireless transmitter can be assigned to an expansion input. The expansion
inputs can be used in any combination. For example, 5 wireless transmitters and 3 hardwire inputs can be assigned to the
expansion inputs. Spectra control panels cannot support more than eight expansion inputs. Refer to the appropriate module’s
Instruction Sheet for details.
Do not assign inputs from different modules to the same expansion input.
5.2 REASSIGN KEYPAD ZONE 2
Section [126]: General Options
Option [7] OFF = Reassign Keypad Zone 2 Disabled (default)
Option [7] ON = Reassign Keypad Zone 2 Enabled
Reassign Keypad Zone 2 changes the keypad zone into an expansion input. In Table 4 above, the effects of enabling this feature
are shown. For example, when option [7] is enabled, Zone 4 moves to Expansion Input 1 (see Table 5 on page 14). Then, you are
able to use Expansion Input 1.
When Reassign Keypad Zone 2 is enabled, the Keypad Tamper Supervision (see page 38) for keypad zone 2 is
lost. Keypad Tamper Supervision will ONLY function on Keypad Zone 1.
Table 4:
Zone Recognition Table
Device connected to
which input? 1759EX
Control Panel
Input 1 = Zone 1
Input 2 = Zone 2
Input 3 = Zone 3
Input 4 = Zone 4
Input 5 = Zone 5
Keypad
Zone 1 = Zone 6
Zone 2 = Zone 7
Expansion
Input 1 = Zone 8
Input 2 = Zone 9
Input 3 = Zone 10
Input 4 = Zone 11
Input 5 = Zone 12
Input 6 = Zone 13
Input 7 = Zone 14
Input 8 = Zone 15

14 REFERENCE & INSTALLATION MANUAL
5.3 REASSIGN ZONES TO EXPANSION INPUTS
Section [126]: General Options
Option [8] OFF = Reassign Zones to Expansion Inputs Disabled (default)
Option [8] ON = Reassign Zones to Expansion Inputs Enabled
Reassign Zones to Expansion Inputs changes the zone numbering to increase the number of expansion inputs that can be
displayed on 10-Zone LED Keypads. In installations that require using mostly the expansion inputs, such as using wireless
zones, the 10-Zone LED Keypads may be unable to display some of the zones. In the following table, the effects of enabling this
feature and Reassign Keypad Zone 2 (see page 13) are shown:
5.4 ZONE PROGRAMMING
After connecting a hardwired detection device to one of the control panel's or zone expansion bus module’s input terminals or
after setting up any wireless transmitters, define the associated zone's parameters. The Zone Parameters define the type of
zone, the zone's partition assignment and how the control panel will react when an alarm condition occurs on that zone. These
Zone Parameters are programmed into one section as detailed in Figure 5.1 on page 15.
Only the control panel’s on-board inputs can be defined as a Fire, Delayed Fire or a Keyswitch zone. The on-
board zones are zones 01 to 05.
Table 5:
Zone Display with 10-Zone LED Keypad
Option [8]:
OFF Option [8]:
ON Option [8]: ON and
Option [7]: OFF (Reassign Keypad Zone 2) Option [8]: ON and
Option [7]: ON (Reassign Keypad Zone 2)
1759EX 1759EX 1759EX 1759EX
Control Panel
Input 1 = Zone 1 Zone 1 Zone 1 Zone 1
Input 2 = Zone 2 Zone 2 Zone 2 Zone 2
Input 3 = Zone 3 N/A N/A N/A
Input 4 = Zone 4 N/A N/A N/A
Input 5 = Zone 5 N/A N/A N/A
Keypad
Zone 1 = Zone 6 Zone 3 Zone 3 Zone 3
Zone 2 = Zone 7 Zone 4 Zone 4 N/A
Expansion
Input 1 = Zone 8 Zone 5 Zone 5 Zone 4
Input 2 = Zone 9 Zone 6 Zone 6 Zone 5
Input 3 = Zone 10 Zone 7 Zone 7 Zone 6
Input 4 = Zone 11 Zone 8 Zone 8 Zone 7
Input 5 = Zone 12 Zone 9 Zone 9 Zone 8
Input 6 = Zone 13 Zone 10 Zone 10 Zone 9
Input 7 = Zone 14 Zone 11 Zone 11 Zone 10
Input 8 = Zone 15 Zone 12 Zone 12 Zone 11
= not displayed on 10-Zone LED Keypads

SPECTRA 1759EX 15
Figure 5.1: Spectra Zone Programming
5.5 ZONE DEFINITIONS
As demonstrated in Figure 5.1, sections [001] to [015] represent zones 1 through 15 respectively, where the first digit in each of
these sections represents the zone's definition. Also, refer to Zone Speed on page 18. To disable a zone, clear the contents of the
section corresponding to the desired zone by pressing the [FORCE]key 3 times and pressing [ENTER]. There are 9 available Zone
Definitions, which are described as follows.
5.5.1 ENTRY DELAY 1
Sections [001] to [015]: Zones 1 to 15, First Digit = 1
When the system is armed and a zone defined with Entry Delay 1 opens, the control panel will generate an alarm after
the programmed Entry Delay 1 Timer elapses. This is to provide users with enough time to enter the protected area
and disarm the system. To program the Entry Delay 1 Timer, key in the desired 3-digit delay value (000 to 255
seconds, Default = 45 seconds) into section [069]. Entry Delay zones are commonly used at the entry/exit points of the
protected area (i.e. front/back door, garage, etc.). Using different Entry Delays (see Entry Delay 2 below) is useful
when, for example, one entry point requires a longer delay than the other entry point or in a partitioned system where
each partition may require a different Entry Delay.
5.5.2 ENTRY DELAY 2
Sections [001] to [015]: Zones 1 to 15, First Digit = 2
Entry Delay 2 zones are identical to the Entry Delay 1 zones (see section 5.5.1), except it uses a separate Entry Delay
Timer. To program the Entry Delay 2 Timer, key in the desired 3-digit delay value (000 to 255 seconds, Default = 45
seconds) into section [070].
This timer is also used as the Stay Delay timer (see Stay Arming with Delay on page 24).
Zone Definitions
1 - Entry Delay 1
2 - Entry Delay 2
3 - Follow
4 - Instant
5 - 24Hr. Burglary
6 - 24Hr. Buzzer
Additional definitions for
on-board terminals:
7 - Keyswitch
8 - 24Hr. Fire
9 - 24Hr. Delayed Fire
Press the
[ENTER]key
Enter the
[INSTALLER CODE]
Key in 3-digit
[SECTION]
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Zone Options
Feature Select
Press [ENTER]
[001] = Zone 1 [009] = Zone 9
[002] = Zone 2 [010] = Zone 10
[003] = Zone 3 [011] = Zone 11
[004] = Zone 4 [012] = Zone 12
[005] = Zone 5 [013] = Zone 13
[006] = Zone 6 [014] = Zone 14
[007] = Zone 7 [015] = Zone 15
[008] = Zone 8
Zone Partition Assignment
1 - Zone Assigned to Partition 1
2 - Zone Assigned to Partition 2
3 - Zone Assigned to both Partitions
Zone Options
[1] Auto Zone Shutdown Enabled
[2] Bypass Enabled
[3] Stay Zone
[4] [5] Zone Alarm Type
OFF OFF Audible Alarm (steady)
OFF ON Audible Alarm (pulsed)
ON OFF Silent Alarm
ON ON Generates only a report
[6] Intellizone
[7] Delay alarm transmission
[8] Force Zone
Keyswitch Options
[1] OFF= Maintained
ON = Momentary
[2] OFF = Regular Arm
ON = Stay Arm
Keypads beep twice
Select
one Select
one

16 REFERENCE & INSTALLATION MANUAL
5.5.3 FOLLOW ZONES
Sections [001] to [015]: Zones 1 to 15, First Digit = 3
When an armed Follow Zone opens, the control panel will immediately generate an alarm, unless an Entry Delay zone
opens first:
• If an armed Follow Zone opens after an Entry Delay zone opens, the control panel waits until the Entry Delay Timer
has elapsed before generating an alarm.
• If an armed Follow Zone opens after more than one Entry Delay zone opens, the control panel will wait until the
Entry Delay Timer of the zone that opened first has elapsed.
This feature is commonly used when a motion detector is protecting the area occupied by the entry point keypad. This
will prevent the motion detector from causing an alarm when a user enters through the entry point to disarm the system.
5.5.4 INSTANT ZONES
Sections [001] to [015]: Zones 1 to 15, First Digit = 4
When an armed Instant Zone opens, the control panel immediately generates an alarm. Instant Zones are commonly
used for windows, patio doors, skylights and other perimeter type zones.
5.5.5 24HR. BURGLARY ZONES
Sections [001] to [015]: Zones 1 to 15, First Digit = 5
Whenever a 24Hr. Burglary Zone opens, whether the system is armed or disarmed, the control panel will immediately
generate an alarm.
5.5.6 24HR. BUZZER
Sections [001] to [015]: Zones 1 to 15, First Digit = 6
Whenever a 24Hr. Buzzer Zone opens, whether the zone is armed or disarmed, the control panel sets off the keypads’
buzzers to indicate that the zone was breached. The control panel will report the alarm, but will not enable the bell/
siren output. Enter any valid access code on the keypad to stop the buzzer. This zone definition is particularly useful
when a user wishes to be notified when something such as a safe or locker within the home has been accessed
(i.e. a child accessing a valuable collection).
5.6 EXCLUSIVE ZONE DEFINITIONS
The following three zone definitions can only be used for devices connected directly to the control panel’s on-board input
terminals. When a zone is programmed as a Keyswitch Zone, the control panel will ignore all other Zone Options. When a zone is
programmed as a Standard Fire Zone or Delayed Fire Zone, the control panel will ignore the Zone Options that may have been
programmed, except Auto Zone Shutdown. Wireless devices and devices connected to the zone expansion bus modules cannot
be programmed with these definitions.
5.6.1 KEYSWITCH ZONE
Sections [001] to [005]: Zones 1 to 5, First Digit = 7
Connecting a keyswitch to a zone allows users to arm the system by pressing a button or by turning a switch on or off
with a key. Please refer to Keyswitch Connections on page 7 and Keyswitch Options on page 18.
5.6.2 STANDARD 24HR. FIRE ZONE
Sections [001] to [005]: Zones 1 to 5, First Digit = 8
Whenever a Standard 24Hr. Fire Zone opens, whether it is armed or disarmed, the control panel will generate the following:
• The control panel can send the corresponding Alarm Report Code from sections [187] to [190].
• If a tamper/wiring fault occurs on a Fire Zone, the control panel can send a Fire Loop Trouble report code
programmed in section [206] to the Central Station. The keypads will display a Fire Loop Trouble in their Trouble
Display (see page 42).
• Alarms are always audible regardless of other settings. Fire alarms generate an intermittent (pulsed) bell/siren
output signal as shown in Figure 5.2 on page 16.
For information on how to connect smoke detectors to the control panel, refer to Fire Circuits on page 7.
5.6.3 DELAYED FIRE ZONE
Sections [001] to [005]: Zones 1 to 5, First Digit = 9
When a Delayed 24Hr. Fire Zone opens, whether it is armed or disarmed, the control panel will react as shown in
Figure 5.3 on page 17. Delayed 24Hr. Fire Zones are commonly used in residential homes where a smoke detector
often generates false alarms (i.e. burning bread, etc.).
Figure 5.2: Bell Output During Fire Alarm

SPECTRA 1759EX 17
5.7 ZONE PARTITION ASSIGNMENT
Sections [001] to [015]: Zones 1 to 15
The control panel provides the option of partitioning the security system into
two completely independent systems. As demonstrated in Figure 5-1 on
page 15, sections [001] to [015] represent zones 1 through 15 respectively,
where the second digit in each of these sections represents the zone's
partition assignment. The zone is assigned to Partition 1 if second digit = 1,
Partition 2 if second digit = 2, or both partitions is second digit = 3. For more
details, refer to Partitioning on page 37.
5.8 ZONE OPTIONS
As demonstrated in Figure 5.1, sections [001] to [015] represent zones 1
through 15 respectively. After entering the first two digits, select one or
more of the following Zone Options by using the Multiple Feature Select
Programming Method (see page 8):
5.8.1 AUTO ZONE SHUTDOWN
Sections [001] to [015] = Zones 1 to 15
Option [1] OFF = Auto Zone Shutdown Disabled
Option [1] ON = Auto Zone Shutdown Enabled for
selected zone (default)
If, in a single armed period, the number of alarms generated by a
zone with the Auto Zone Shutdown option enabled exceeds the
number defined by the Auto Zone Shutdown Counter, the control
panel will no longer generate an alarm for that zone. To program
the Auto Zone Shutdown Counter, key in the desired limit
(000=Disabled, 001 to 015, Default = 5) into section [089]. The
Auto Zone Shutdown Counter resets every time the partition that
is assigned to the corresponding zone is armed.
5.8.2 BYPASS ZONES
Sections [001] to [015] = Zones 1 to 15
Option [2] OFF = Bypass Zone Disabled
Option [2] ON = Selected Zone is Bypass Enabled
(default)
When a user utilizes the Bypass Programming feature (see page 45), only zones with the Bypass option enabled can
be programmed as bypassed.
Do not program a Fire Zone with the Bypass option, as the control panel will never bypass Fire Zones.
5.8.3 STAY ZONES
Sections [001] to [015]: Zones 1 to 15
Option [3] OFF = Stay Zone Disabled (default)
Option [3] ON = Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is Stay Armed (see page 44).
Do not program a Fire Zone with the Stay option, as the control panel will never bypass Fire Zones
when Stay Arming.
5.8.4 ALARM TYPES
Sections [001] to [015]: Zones 1 to 15
[4] OFF / [5] OFF: Audible Steady (default)
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 29) and provides a steady output for any bells or sirens connected to the control panel’s bell output.
[4] OFF / [5] ON: Audible Pulsed Alarm
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 29) and provides a pulsed output (see Figure 5.2 on page 16) for any bells or sirens connected to the
control panel’s bell output.
[4] ON / [5] OFF: Silent Alarm
When the conditions for an alarm are met, the control panel can transmit the appropriate Zone Alarm report code (see
page 29) and will not activate the control panel’s bell output. The appropriate ARM or STATUS LED on the keypads will
flash to indicate an alarm and the user will still have to disarm the system.
Figure 5.3: Delayed 24Hr. Fire Zone

18 REFERENCE & INSTALLATION MANUAL
[4] ON / [5] ON: Report Only
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 29). The system will not have to be disarmed.
5.8.5 INTELLIZONE
Sections [001] to [015]: Zones 1 to 15
Option [6] OFF = Intellizone Disabled (default)
Option [6] ON = Intellizone Enabled for Selected Zone
This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the panel does not
immediately generate an alarm. First it triggers the Intellizone Delay Timer. To program the Intellizone Delay Timer, key
in the desired 3-digit value (010 to 255 seconds, Default = 48 seconds) into section [084]. If any of the following
conditions occur during this period, the panel will generate an alarm:
• During the Intellizone Delay, a second zone has caused an alarm.
• During the Intellizone Delay, the zone in alarm has restored (closed) and re-occurred (opened).
• The zone in alarm remains open for the entire Intellizone Delay.
5.8.6 DELAY BEFORE ALARM REPORT CODE TRANSMISSION
Sections [001] to [015]: Zones 1 to 15
Option [7] OFF = Delay Alarm Transmission Disabled (default)
Option [7] ON = Delay Alarm Transmission Enabled for Selected Zone
When an alarm condition occurs on a zone with this option enabled, the control panel enables the bell/siren output, but does
not report the alarm to the central station until the end of the Alarm Before Transmission Delay. To program the Alarm
Transmission Delay, key in the desired 3-digit delay value (000 = Disabled, 001 to 255 seconds) into section [080]. During this
period, disarming the system disables the bell/siren output and cancels the report code transmission. This feature is
commonly used with Entry Delay zones to reduce false alarms created by new users who may not disarm the system in time.
5.8.7 FORCE ZONES
Sections [001] to [015]: Zones 1 to 15
Option [8] OFF = Force Zone Disabled (default)
Option [8] ON = Selected Zone is Force Enabled
Any open Force Zones at the time of arming will be considered deactivated by the control panel (see page 45). If
during this period a deactivated zone is closed, the control panel will revert that zone to active status. Consequently,
the control panel will generate an alarm if the zone is breached.
Do not program a Fire Zone with the Force option, as the control panel will never bypass Fire Zones
when Force Arming.
5.8.8 KEYSWITCH OPTIONS
Sections [001] to [005]: Option [1] and [2]
When an on-board zone is programmed as a Keyswitch Zone (see page 16), the control panel will ignore any other
Zone Option. The keyswitch can be programmed as a Maintained or Momentary Keyswitch and to Regular or Stay Arm
(see page 44). A Maintained Keyswitch will arm the system when it is set to the ON position and will disarm when set to
the OFF position. To arm with a Momentary Keyswitch, set the keyswitch to the ON position then turn it back to the OFF
position. Repeating this sequence will disarm the system. Program the keyswitch with the following:
5.9 ZONE SPEED
Sections [050] to [064]: Zones 1 to 15
001 to 255 X 10ms, Default = 600ms
The Zone Speed defines how quickly the control panel will respond to an open zone. The control panel will not display an open zone on
the keypad or generate an alarm until theprogrammed Zone Speed has elapsed. All other zone definitions and options donot come into
effect until the Zone Speed has elapsed. This feature prevents any momentary glitches from causing an alarm or unnecessary reporting.
5.10 EOL ZONES
Section [132]: Zone Options
Option [4] OFF = Zones do not use EOL resistors (default)
Option [4] ON = Zones require EOL resistors
If all detection devices connected to the control panel have input terminals that require 1KΩend of line resistors, enable option [4]
in section [132]. For details on using EOL resistors, refer to Single Zone Inputs on page 6.
Option [1] OFF = Maintained (default) Option [2] OFF = Regular Arming (default)
Option [1] ON = Momentary Option [2] ON = Stay Arming