Model 340i / 680i / 1220i DC drive product manual HG102938 iss 8 3
The up / down ramps can now be set between 20 and 1
seconds, and the Min spd adjusted up to 30%.
(Note, down ramp becomes up ramp for negative input).
Speed droop on heavy loads may occur when armature voltage
feedback is used. This is compensated for by
clockwise rotation of IR comp. Excessive rotation may lead to instability.
Note, IR comp is not used with tach feedback, leave preset anticlockwise.
The tach feedback signal on terminal 11 must be negative with
respect to terminal 10 COMMON.
Whilst still in AVF mode measure the tach volts on the wire intended for T11 when running at
100% speed. (Warning, possible high voltage). This is the tach full speed voltage. Make a note of it
to assist in selecting the speed range. Stop the motor and turn off the supply.
Set Avf/Tach switch OFF (right). Adjust the Max spd preset anti-clockwise. (With Spd x 2 switch
OFF (right) maximum speed range = 40 to 100V. With Spd x 2 switch ON (left) the maximum
speed range = 80 to 200V). Re-connect the tach wire to T11, re-start and adjust Max spd as
required.
WARNING. A+, A-, F-, F+, N, L, are at high potential.
DO NOT TOUCH the terminals or any connected conductor
1 +10V output. 10mA max. (Use a 10K Ohm pot for external speed reference).
2 MIN Speed. 5K Ohms preset to COM. (Connect to minimum end of speed pot).
3 IP. Speed input to ramp. 0 to 10V from speed pot wiper. 47K internal pull down.
4 OP+/-. (+/-10.5V range). 10mA max. T6 is the input for this function. Invert with T8
PB- input open. Non-invert with T7 PB+ open and T8 PB- connected to T5 COM. (This
function may be used to buffer or invert system signals).
5 COM. Common. (0 Volts)
6 IP+/-. Input to pushbutton controlled +/- signal channel. OP on T4. 50K Ohms.
Note. This channel can invert input signals in the range +/-10.5V. It can also buffer (i.e.
non-invert) signals in the range 0V to +10.5V. (It cannot buffer negative signals. If you
try to buffer negative signals the output swings positive).
7 PB+ Pushbutton input. 47K Ohm pull up to +12V. Connect to T5 COM. Latches T4 to
buffer (non-invert) positive T6 signals when opened, provided T8 PB- is connected to T5
COM.
8 PB- Pushbutton input. 47K Ohm pull up to +12V. Connect to T5 COM. Latches T4 to
invert T6 when opened. T7 PB+ may be open or connected to T5 COM.
9 RUN. Internal 12K pull up to +12V. Open to reset, close to T5 COM to run. WARNING.
RUN is an electronic inhibit function. The field remains energised, and all power terminals
‘live’. RUN must not be relied on during hazardous operations.
10 COM. Common. (0 Volts)
11 TACH input. The tach voltage must be negative on T11. 1.5 MOhms.
12 RLOP. Relay driver output. +10V active high at 10mA. Flywheel diode to COM.
13 RLIP. Relay driver input. Accepts 0 to +/-10.5V signal inputs. The threshold to activate
the relay driver is symmetrical around zero, and set by the Level preset between +/-
0.05V and +/-10.5V. When the T13 input exceeds the positive or negative threshold,
then the T12 RLOP is turned ON. Typical uses include zero speed detector, zero current
detector, stall detector etc. The input will accept any output from other terminals. 50K
Ohm pull down to COM.
RAMP and MIN SPEED
IR COMP
TACH FEEDBACK
TERMINAL LISTING