6Installations
Rail mountingdimensions:35mm;screwsinstallation size:
73X26.8mm;as showninFigure7(inmm).
Figure7:Mountingdimensions
7 Product sService
1Installation
1.1DIN railinstallationmethod:
①Fixthetransduceronthesideofthecardslotandhookon
themountingrail;
②Pull thespringpindown;
③Clipthetransducermounton themountingrail;
④Release thespringpinand clipthetransmitteron the
mountingrail.
1.2Screwmountingmethod:
①4mmdiameterholeinthefixedplateaccordingtothescrew
holepositionshowninFig.5;
②Use thescrew Φ3toinsert intoholeandsecureit.
2Producthas beenaccuratelysetaccordingtothe"product
standard".Applypowerafterdeterminethecorrectwiring.
3Themaximumwirediameteroftheterminalblockis2mm
(16-26AWG).Removethe4mm~5mminsulationlayerfromthe
end ofthemountingwireand insert it intotheterminalblock,then
tightenthescrew.
4Productsupplypowerrequires theisolationvoltage ≥2000VAC,
ACripple<10mV. Multipletransducerscanshareacommon setof
powersupplies,butthepowercircuit cannolongerbeusedto
driverelaysand othercanproduce spikes intheload,inorderto
avoidinterference signaltransmission tothetransducer.
5 Thetransducersoutput0-20mA(or4-20mA),theRLstandardis ≤
250Ω,and0-5VvoltageoutputRLstandardis ≥2KΩ,canguarantee
theoutputaccuracyand linearityovertheentireratedinputrange.
8 Example ofproductaccuracy levelverification
1Accordingtothedefinitionofthetransducerterminalstoconnect
thetestcircuitas shown.
Figure6, accuracytestwiringdiagramofvoltageorcurrentoutput
Note: Thevoltageoutputismeasuredwithavoltmeterand the
currentoutputismeasuredwithanIometer.
2Thetestshallbecarriedoutunderthefollowingenvironmental
conditions:
◆Powersupply:nominal ±5%, ripple ≤10mV;
◆Ambienttemperature:25 C ±5 C;
Relativehumidity:RH (45 ~80)%;
◆Theaccuracyofthesignalsource and measurement
instrumentis0.05%above.
3Powerpreheat2min;
4Assumingthetransmitterinputfrequencyrangeis0-10KHz,he
outputis0-5VDC,givenanyinputvalueFinthetransducerrange,
thetheoreticaloutputvalue(Vz)ofthetransduceriscalculatedas
follows:
Vz=(F÷10KHz)×5V
Iftheoutputis4-20mA, thenIz=4+F÷10KHz×16mA;
Iftheoutputis0-20mA, thenIz=F÷10KHz×20mA;
5ThemonitoringtablemeasurestheDC voltageoutputvalueVoor
thecurrentoutputvalueIo.
│Vo-Vz│≤25mVisnormal, orexcessive(0-5Voutput, 0.5);
│Io-Iz│≤80uAisnormal, orexcessive(4-20mAoutput,0.5);
│Io-Iz│≤100uAisnormal, orexcessive(0-20mAoutput,0.5);
6Repeatthe5operation,theresultingpointvalueis
│Vo-Vz│≤25mVor │Io-Iz│≤80uA(100uA),thetransduceraccuracy
levelisqualified.
Note: please consult withourcompanyfortheverification method
detailedofothertechnicalindicators.