LINE VOLTAGE ELECTRICAL CONNECTIONS
In standard config ration, the Comfort Pl s is wired for connec-
tion to 240V, however, the element circ its can also be con-
nected to 208V. A 208V connection derates the charging inp t
of the system by 25%. If a system rated specifically for 208V
or 277V is req ired, contact the factory. The controls circ it in
the Comfort Pl s system MUST be connected to 240V/208V.
The 60 amp breakers located in the electrical compartment on
the Comfort Pl s feed the core charging (element) circ its. The
15 amp breaker feeds the controls and blowers circ it.
Installation
HAZARDOUS VOLTAGE Risk of electric
shock. Can cause injury or death. Do not
energize the system until installation is
complete. Equipment MUST be installed
by a qualified technician in compliance
with all applicable local, state, and
national codes and regulations.
WARNING
AIR CONDITIONER/HEAT PUMP INTERFACE
When interfacing the Comfort Pl s system with a heat p mp, the
indoor coil MUST be placed on the ret rn side of the Comfort Pl s
system in a position that will provide even air flow thro gh the coil.
If sing a factory s pplied ret rn air plen m, the plen m is config-
red to be the ho sing for the indoor coil. Remove the screws to the
plen ms access cover and slide the coil into place inside the ple-
n m. If not sing a Steffes s pplied ret rn air plen m, the installer
will need to make provisions in the plen m to accommodate the coil
and air filter.
When interfacing a Comfort Pl s system with an air conditioner, the
indoor coil can be placed on either the s pply air or the ret rn air
side of the system.
The condensate drain trap, in a heat p mp or air conditioner installa-
tion, sho ld be designed for the vac m in which the system is
operating. Typically, taller traps are better s ited for these types of applications.
Refer to the Room Thermostat Connections Diagrams (Fig res 13, 14 and 15) for more information on interfacing
the Comfort Pl s with a heat p mp or air conditioner.
Installation n 3.08 Comfort Plus
WARNING
Risk of fire. Any one ducting system
MUST NOT contain more than one
air handling (blower) system. If the
application requires multiple Com-
fort Plus systems or it is necessary to
have multiple air handlers share the
same ductwork, you MUST contact
Steffes Corporation. There are
special installation requirements
that MUST be performed in an
application such as this.
All Comfort Plus systems are factory configured to be field connected to multi le line voltage
circuits. If a single feed line voltage circuit is desired, an o tional single feed kit is available.
SAMPLE SYSTEM IDENTIFICATION LABEL
FIGURE 11
To determine the correct wire size req ired for
each circ it feeding the Comfort Pl s, refer to
the Specifications (Page A.01) and the system's
identification label located on the lower front of
a 3100 series system and on the lower left side
of a 4100 series system. (Reference Sample
Label Fig re 11.)
Ste 1 Remove the electrical panel cover.
Ste 2 Ro te all line voltage wires thro gh a
knocko t and into the electrical panel
of the Comfort Pl s.
Ste 3 Make proper field wiring connections
to the Comfort Pl s breakers. Refer
to the Line Voltage Wiring Diagrams
(Pages A.09 - A.12) for more informa-
tion on these connections.