Comfort Plus Commercial Installation n 3.08
Installation
AIR CONDITIONER/HEAT PUMP INTERFACE
When inter acing the Com ort Plus system with a heat pump, the
indoor coil MUST be placed on the return side o the Com ort Plus
system in a position that will provide even air low through the coil. I
using a actory supplied return air plenum, the plenum is con igured to
be the housing or the indoor coil. Remove the screws to the plenums
access cover and slide the coil into place inside the plenum. I not using
a Ste es supplied return air plenum, the installer will need to make
provisions in the plenum to accommodate the coil and air ilter.
When inter acing a Com ort Plus system with an air conditioner, the
indoor coil can be placed on either the supply air or the return air side
o the system.
The condensate drain trap, in a heat pump or air conditioner installation,
should be designed or the vacuum in which the system is operating.
Typically, taller traps are better suited or these types o applications.
Re er to the Room Thermostat Connections Diagrams (Figures 14, 15 and 16) or more in ormation on inter acing
the Com ort Plus with a heat pump or air conditioner.
WARNING
Risk of fire. Any one ducting system
MUST NOT contain more than one
air handling (blower) system. If the
application requires multiple Com-
fort Plus systems or it is necessary to
have multiple air handlers share the
same ductwork, you MUST contact
Steffes Corporation. There are
special installation requirements
that MUST be performed in an
application such as this.
LINE VOLTAGE ELECTRICAL CONNECTIONS
In standard con iguration, the system is wired or connection to
240V; however, the element circuits can also be connected to
208V. A 208V connection derates the charging input o the
system by 25%. I a system rated speci ically or 208V is
required, contact the actory. The controls circuit in the system
MUST be connected to 240V/208V.
277/480V and 347/600V Comfort Plus Commercial
systems are configured to use single feed only.
208/240V System Connections Only: The 60 amp breakers
located in the electrical compartment eed the core charging (ele-
ment) circuits. The 15 amp breaker eeds the controls and blowers
circuit. All 240V/208V systems are actory con igured to be ield
connected to multiple line voltage circuits. I a single eed line
voltage circuit is desired, an optional single eed kit is available rom
the actory.
277/480V and 347/600V System Connections Only: The use
block connection points and neutral connection block, located in the
line voltage side o the electrical compartment, eed the core
charging (heating element) circuits. This also provides power and the terminal block connections or the primary
side o the optional control voltage step-down trans ormer. Adjacent to these terminals are the connection points
or the trans ormer secondary. See Figure 12B.
To determine the correct wire size required or each circuit eeding the system, re er to the Speci ications (Page
A.01) and the system's identi ication label located on the lower le t side o the system. (Re erence Sample Label
Figure 11.)
Step 1 Route all line voltage wires through a knockout and into the electrical panel.
Step 2 Make proper ield wiring connections to the Com ort Plus Commercial breakers. Re er to the Line Voltage
Wiring Diagrams (Pages A.03 - A.04) or more in ormation on these connections.
HAZARDOUS VOLTAGE Risk of electric
shock. Can cause injury or death. Do not
energize the system until installation is
complete. Equipment MUST be installed
by a qualified technician in compliance
with all applicable local, state, and
national codes and regulations.
WARNING
wTo ensure proper operation and
safety, all line voltage circuits
must be segregated from low
voltage wiring in the system.
wTo reduce electro magnetic fields
associated with electrical circuits
and to avoid induced voltage on
sensors and electronic devices, the
circuit phases MUST be alternated
as shown in Figure 12A.