1
VISION.NET GATEWAY
QUICK START GUIDE
443581626884 REV A 10/21
OVERVIEW
Vision.Net Gateway Module 65710
Vision.Net Interface Gateway Module 65730
Vision.Net 4-port DMX Interface Gateway Module 65720
This document provides basic setup instructions and safety
warnings for the following product(s):
INSTALLATION AND SET UP
POWER REQUIREMENTS
Vision.Net Gateway may be powered via either a Power over Ethernet (PoE) supply or from an external DC power
supply connected via a set of screw terminals.
NOTE: DC and PoE power connections will not operate as a redundant power solution.
A CR1225 backup battery (pre-installed) is used for the real-time clock. External modules are powered from the
Gateway module through the DIN rail bus system, and do not require their own power supply. The Gateway draws
up to 40W of power, depending on the configuration of modules added. For PoE supplies it is best to use an
803.2bt class7-8 high power source,however in some circumstances, it may be powered from an 803.2af PoE+
supply. Consult the table below for further information to select the right options.
DIN RAIL MOUNTING
WARNING! Do not power the system until all modules are placed and connected as described in the steps
below.
To mount Vision.Net gateway and other modules on compatible TS35/7.5 DIN rail:
Step 1. Unpack module(s), taking precautions against ESD.
Step 2. Place the DIN rail bus connector into the DIN rail.
Step 3. Mount Vision.net Gateway module on DIN rail, taking care to orient the modules as shown. Take special
care aligning, to prevent bending the pins
SERIAL USB
WAN
LAN
−
24 VDC
2.7 A
+PoE
VISION.NET GATEWAY
+
D
–
D
+–+–+–
VISION.NET INTERFACE
GATEWAY MODULE
GATEWAY -DMX 4 PORT
RS485 MODULE
−+−+
−
+−
+
PoE REQUIREMENTS
COMBINATION PoE PSE TYPE DESCRIPTION
Gateway standalone 802.3af 12W @ the gateway
Gateway + modules 802.3bt class 5 or higher 40W @ the gateway