
Installation 3
2.0 Installation
The following sections describe the correct installation procedures for the Summit 3000 floor scale.
2.1 Overview
Standard installation of the Summit 3000 floor scale consists of the following steps:
1. Select a site.
2. Check levelness and smoothness of site.
3. Unpack the floor scale.
4. Adjust the four feet on the scale.
5. Install mounting plates to the floor (optional).
6. Connect cable to the system.
7. Calibrate the system.
Access ramps and pit installations are described in Section 2.6 and Section 2.7.
2.2 Site Preparation
Do not load the scale beyond its capacity, even momentarily. Avoid areas where the scale might receive
damaging side impacts from wheels or forklift tines, or shock damage from falling objects. Avoid areas where
water may damage a scale which is not meant for a washdown environment.
The interface cable between the scale and the indicator must be protected against crushing, cutting, or moisture
damage. If the chosen site has such potential dangers, some method of protection, such as running the cable in
conduit, is necessary.
In operation, the scale must be level within 1/4 inch (6.35 mm). Either choose a site where the floor is close to
this standard or modify the floor at the chosen site to meet this standard, to avoid excessive shimming.
2.3 Unpacking
Remove all packing material and visually inspect the floor scale for visible damage caused during shipment. The
shipping container should contain the floor scale, this manual and a 20 ft length of load cell cable.
All Summit 3000 models have one threaded eyebolt hole located in the center of the deck to allow installation of
an eyebolt hook for use when lifting the scale with chains.
Lift the scale only with a properly designed spreader bar as shown in Figure 2-1.
Lifting force must be vertical to avoid bending the eye bolt.
Eye bolts must always be inserted into the top of the scale. Lifting should always
occur with the top plate facing up and the eye bolts securely attached through the
nuts welded to the bottom side of the top plate. Lifting from the bottom of the plate
could cause nuts to break loose and the scale to fall.
It’s recommended to use a 1/2 inch-13NC eyebolt inch 2000 to 10,000 lb capacity scales.
Figure 2-1. Proper Lifting Technique
Large Platform
(Larger then 5
’
x 5
’
, and /or more than 10,000 lb capacity)
Use two 3/4
”
eye bolts, insert into threaded holes in
opposite corners of top plate for lifting.
Small Platform
(5
’
x 5
’
or smaller and/or 10,000 lb or less capacity)
Use one 1/2
”
eye bolt, insert into threaded hole in
center of top plate for lifting.