Sunlover SL6 AV User manual

WARRANTY – SL6AV
This range of product is covered by a limited 3 year warranty against component failure or
faulty workmanship from the date of installation.
A faulty unit should be returned in the first instance to the dealer from which the unit was
purchased.
Damage to the unit due to misuse, power surges, lightning strikes or installation that is not
in accordance with the manufacturer’s instruction may void the warranty.
Valves and actuators are covered by a twelve month warranty at the discretion of their
manufacturer.
arranty does not cover travel costs to or from installation site.
If the power cord is damaged, do not use the controller; return the unit to the supplier for
repair.
Customer Record. (To be retained by the customer)
Dealer/Installer Name ………………………………………………
Serial Number ………………………………………………
Date Installed ………………………………………………
For service assistance phone 1300 130 693
VIC 03 9887 2131
NS 02 9838 0000
QLD 07 5597 7360
Factory 6
62 Parkhurst Drive
7-9 Activity Crescent
Knoxfield VIC 318
Molendinar 4214
Victoria Australia
Queensland Australia
Unit 2
20-22 Foundry Road,
Seven Hills 2147
New South Wales Australia
www.sunloversolar.com.au
MODEL SL6 AV Deluxe Digital Solar Co troller
OPERATING INSTRUCTIONS
AUTO is normal operating mode used during the Pool Swimming Season. You may set
the desired pool limit by pressing the UP or Down Buttons. The display shows the pool
temperature then flashes the limit setting and light; the HEAT light will be on when
solar gain is available.
Ma ual is used to test the system. To select manual mode press the SELECT button
until the HEAT light is illuminated. The valve will then open, or close if it has been
running. To return to normal run simply press the SELECT button till the AUTO light is
illuminated. The SL6 AV will automatically return to AUTO run after 30 minutes, with a
limit of 30 degrees.
Roof displays the roof sensor temperature, a hot roof indicates that solar gain
(heating) is available, if left unattended in this mode the SL6 AV will automatically
return to AUTO run after 3 minutes.
Wi ter should be selected when the pool is not being used for extended periods. The
valve will be turned for 3 minutes every day at the same time inter Mode was
selected. This will assist in the systems off-season maintenance. To enter this mode
press the SELECT button till the INTER light is illuminated, the display will then go
blank and the valve will turn to roof for three minutes. Ensure winter mode is activated
during the filter run times only. If the power is interrupted during winter mode the SL6
AV will continue to count time accurately.
Tropical is used to assist in cooling over heated pools. If the limit has been reached,
which is indicated by the limit light on, and the roof temperature drops below the limit
temperature (usually some time late at night) the valve will turn and divert pool water
to the roof to cool it down. The filter pump must be set to filter at night for this
operation. To set this function press the SELECT button till the TROP light is
illuminated. To switch back to Summer Mode press the SELECT button till the AUTO
light is illuminated.
OPERATION
The SL6 AV will turn the motorised valve when the roof temperature is higher than the
pool (pipe) temperature by 8°C and off at 4°C. The HEAT light will flash for 30 seconds
when constant flow from the main filter pump is first detected (if fitted), then turn the
divert valve. hen the pool temperature reaches the limit setting the limit light will
flash, it will remain in this state while the pool is at limit then divert back to the roof if
the pool temperature drops and the roof is still hot.

INSTALLATION INSTRUCTIONS
Co troller Mou ti g
Find a suitable location to mount the control box. Ideally as with all pool equipment it should
be installed out of direct weather and no closer than 3 meters from the waters edge. Lift up
the two mounting tabs and use two appropriate screws to mount the control box to the wall,
keeping in mind that the power cable is 1.8m long and should be plugged directly into a
general power outlet, not into an extension lead.
Pressure Switch or Flow Switch - Optio al
A pressure switch can be fitted between the main filter pump and filter or a flow switch
straight after the filter. All must be in a vertical position and plugged into the socket beneath
the controller marked FLO . This will ensure that the valve only activates if the main pool
pump is operating. hen a pressure or flow switch is to be used the jumper wire in the
FLO plug must be replaced with the flow or pressure switch wires.
Valve
If a valve is not supplied, the colour coding for the valve wiring is Red, Black and hite
(looking from left to right when looking at the screw terminals). Solder the wire-ends to
prevent corrosion to the exposed copper wire.
Pool Se sor
The pool sensor must be fitted in the suction line of the main filter pump or between the
outlet of the filter and before the solar take off Tee, preferably in a position out of direct
sunlight. It is recommended that a 14.5mm hole be drilled in the side of the PVC pipe (not
the top of the pipe where water will collect), this can be carried out using a Dontek PD01
grinding drill or a small pilot hole can be drilled and a 14.0mm drill-bit used spinning in a
counter clockwise direction to minimize the chance of shattering pipe. Insert the grommet
into the pipe and gently push in the black sensor barb. The green sensor plug is to be fitted
to the centre plug socket.
Roof Se sor
Roof sensors must be fitted into a small piece of solar collector or equivalent and attached to
the roof. The best location is within arms length of the gutters edge of the house or shed as
long as the sensor end is not shaded and is on a roof of similar aspect of the main collector.
It must ot be fitted on top of the solar collector or fitted to high points on the roof like
Ridge Capping as false readings will be detected.
Keep in mind that it is of the utmost importance to keep the roof sensor as short as possible
as this will assist in the longevity of the sensor and controller in the event of electrical storm
activity and power surges. Sensor cables must ot be ru parallel to power cables and
run lengths should be less than 50m. Cable ties should be used to fasten the sensor cable to
the cold water inlet pipe making sure that the ties are approximately 10mm from PVC
fittings. Cable ties should be tightened only firm, over tightening can cause breaks in the
outer PVC if not careful. If the cable is to be run under ground a conduit must be used to
protect the wire and there is to be no cable joins within, conduit ends must be sealed to
prevent water ingress. A y excess cable should be removed a d re-fitted e suri g
that the wire e ds are ti ed with solder. The sensor plug is to be fitted to the right
hand socket.
INSTALLATION INSTRUCTIONS
Notes
All excess cable must be removed; coils of cable are not permitted under any circumstances and must ot
be tied to 240V wiring. If the cable is to be extended with non genuine cable a size of 14/020 should be
used. A y cable joi s must be soldered a d this i cludes where the cable e ters the termi al
block at the case base. Heat shrink is to be used over soldered joints to eliminate moisture ingress. If the
cable end is to be refitted to the plug sockets then the polarity must be observed as incorrect polarity will
show an error as stated in Fault Diagnosis. The sensor cable with the thin white trace is the positive and
should be fitted to the right hand cable entry when the screws are in a vertical position.
Once cables have been correctly fitted the unit can be turned on.
Fault Diag osis:
The unit will be factory set with the black jumper link marked J1 to ON, a 33 will briefly be displayed during
start up.
In the event of a cable or sensor failure, the display will indicate the type of failure as follows;
ROOF SENSOR.
A display of 99 indicates a broken or disconnected sensor cable or open circuit sensor.
A display of 88 indicates wrong polarity connection or short-circuited cable or sensor.
A display of 85 indicates a damaged cable.
A display of 98 indicates a high sensor reading (above 98°C).
A display of 00/03 indicates an over extended or coiled sensor cable.
POOL SENSOR
A display of 77 indicates a broken or disconnected sensor cable.
A display of 66 indicates wrong polarity or short-circuited sensor cable.
A display of 67 indicates a sensor reading out of normal operating range.
Other Sunlover Controllers manuals
Popular Controllers manuals by other brands

ADTRAN
ADTRAN NetVanta 5305 quick start guide

D-Link
D-Link PowerLine DHP-W611AV user manual

HANGZHOU WORLDE MUSIC ELECTRONIC
HANGZHOU WORLDE MUSIC ELECTRONIC KX61/76/88HC user manual

sauter
sauter equitherm M60 operating instructions

BGS technic
BGS technic 8603 instruction manual

Xilinx
Xilinx XC4000 Series manual