Troubleshooting
Problem: Outlet pressure drops off sharply even when the flow is within regulator capabilities.
Cause: The upstream filter has an obstruction.
Solution: Replace the obstructed filter element or elements.
Problem: The outlet pressure has changed without adjusting the regulator.
Cause: Changes to the inlet pressure result in changes to the outlet pressure.
o A decrease in the inlet pressure results in an increase in the outlet pressure.
o An increase in the inlet pressure results in a decrease in the outlet pressure.
Solution: Maintain a constant regulator inlet pressure. See “dependency” in section 3, Operation.
Problem: The outlet pressure slowly increases, without increasing the dome pressure.
Cause: A damaged valve or seat or both.
Solution: Replace the valve or the seat or both.
Problem: The outlet pressure does not decrease when adjusted to decrease the pressure.
Causes: The regulator is non-self-venting.
Solutions: Open a downstream shutoff valve to reduce the outlet pressure.
Problem: Ice forms on the regulator.
Cause: Most gases cool with a sudden pressure drop. Moisture in the gas promotes icing.
Solution: Remove moisture from the gas or heat the regulator.
Problem: Leakage around the body plug.
Causes: A damaged O-ring or back-up ring or both.
Insufficient torque on the body plug.
Solutions: Replace the O-ring or back-up ring or both.
Tighten the body plug according to the recommended torque.
Problem: Leakage between the top cover and the spring housing
Causes: A damaged diaphragm
Insufficient torque on the spring housing
Solutions: Replace the diaphragm.
Tighten the spring housing to the recommended torque.
Problem: Leakage between the set screw and the spring housing
Causes: A damaged diaphragm and spring guide O-ring
Insufficient torque on the cap screws
Solutions: Replace the diaphragm and spring guide O-ring.
Tighten the cap screws to the recommended torque.
Warranty Information
Swagelok® products are backed by The Swagelok Limited Lifetime Warranty.
For a copy, visit swagelok.com or contact your authorized Swagelok representative.
For additional information, see www.swagelok.com.
Swagelok, Snoop—TM Swagelok Company
© 2011-2021 Swagelok Company
MS-CRD-0181, RevC, October 2021
WARNING:
Do not mix/interchan
ge Swagelok products or components
not governed by industrial design standards, including
Swagelok tube fitting end connections, with those of other