Synel 785 User manual

Synel Americas
8665 E Hartford Dr Suite 100
Scottsdale, AZ. 85255
480-37 4-7700
www.synel-americas.com
V Feb 2020

- 1 -
1.0 Technical Specifications
1.1 Specifications
Dimensions
9.8” x 6.7” x 3.7”
Weight
2.5 lbs.
Memory
512K RAM, Battery backed.
Reader
Magnetic Stripe (track 1, 2, or 3) – Optional
Bar Code (0-of-9, 2-of-5, 128)
Proximity Reader (HID 26 Bit) – Optional
Fingerprint (1:1 validation 1:N identification) – Optional
Display
2x16 LCD backlit Alphanumeric with Decimal point
Programming
ASCII-based, Over Communication Port
Communications
Standard: RS-232 Port - Bi-directional Local Communications
Standard: RS-485 Port
Optional: 14.4 Baud Modem
Optional: 10/100 Ethernet
Power
Voltage: 110/230 Vac + 10%, 100mA
Environment
Operating Temperature -20o-60oC
Humidity: up to 95% RH
1.2 Available Options
Ethernet Communications:
With the optional internal Ethernet card, the terminal can be connected to any 10/100
Ethernet network.
Wi-Fi (Wireless) Communications:
The TA-785’s wireless card allows the 745 to communicate over a standard
802.11b network. The wireless network must be configured with an IP address, gateway, subnet, and WEP key (if
available).
P.O.E. (Power over Ethernet:
The TA-785’s has the optional capability of drawing its power from the Ethernet
communications line. This eliminates the need for high voltage power at the terminal locations. Note: The Ethernet
Network must support POE communications.
Biometric Fingerprint Reader:
The TA-785 can store up to 9,090 fingerprint templates for biometric verification (1 to 1)
or identification (1 too many). The terminal utilizes a high resolution 500 dpi finger template.
External Readers:
The TA-785 has two reader ports to connect external devices such as a Bar code Gun or an
Access Control Swipe Reader that could be mounted outside a door.
1.3 Features
The TA-785 is constructed of injection molded plastic, which, pound for pound is stronger than steel, yet lightweight
and attractive. The terminals have recessed membrane keypads, which create a watertight seal against external
elements.

- 2 -
1.3.1 Front Panel
The TA-785 Terminal has the following front panel features:
1. 2x16 Character LCD backlit display.
a. The terminal comes with a highly advanced filtered LCD display. This means that under almost any
lighting condition, the terminal will give you a clear picture to read the screen.
2. Two arrow keys are located to the right of the display panel for line up
and line down maneuvering.
a. The arrow keys are also used for getting into Technician mode.
3. Eight Function keys located on the left, below the display.
a.
[IN]
,
[OUT]
,
[F1]
,
[F2]
,
[F3]
,
[F4]
,
[F5]
and
[F6]
.
4. A numerical keyboard of fourteen keys, including
[Enter]
,
[Back Space]
,
[Dot]
and
[Clear]
.
5. The
Alarm
light
“!”
, is located to the left of the display.
a.
The alarm light is an LED that lights when at least half of the memory is used; its blinks when the
memory is almost full.
6. The
ON
button enables a 15 second manual operation window if the terminal is on battery back-up power.
1.3.2 Bottom Connector Panel
The connector panel is located at the lower part of the casing, withholding the socket openings for all external
connections as follows (from left to right):
1. External secondary Reader 2 – for optional external readers
2. External secondary Reader 1 – for optional external readers
3. I2C – I/O Extension (N/A) – not used
4. Network
5. Serial I – Serial port connection for printer (N/A) – not used
6. Host – RS-232 / RS-485 Communications
1.4 Internal Components
The TA-785 has two back-up battery modules, one for the real time clock memory and the other for operation during
a power failure.
The standard memory back-up module is a lithium battery, which will keep the internal clock running and the memory
intact, for 30 days during a power failure.
The back-up battery provided (in addition to the standard memory back-up) is a self-recharging system which allows
the terminal to operate during a power failure. The battery provides power for one and a half net hours of use. A shut
down timeout feature enables the terminal to operate for more extended periods of time.

- 3 -
During a power failure, the user presses the battery key to activate the terminal. Data can then be entered and stored
in the TA-785 memory. The time-out will cause the terminal to shut down automatically after the last use of the
terminal, until the battery key is pressed again.
1.4.1 Memory
Asa standard feature, the TA-785 Terminal contains a 256 Kbyte user memory, providing storage for data from more
than 10,000 simple operations. This number depends on the length of the programming tables contained in the
memory, and the complexity of the collected data.
The Alarm light “!”, is located to the left of the display. The alarm light is an
LED that lights when at least half of the memory is used; its blinks when the
memory is almost full.
1.2 Internal Components
The TA-785 has two back-up battery modules, one for the real time clock memory and the other for operation during
a power failure.
The standard memory back-up module is a lithium battery, which will keep the internal clock running and the memory
intact, for 30 days during a power failure.
The back-up battery provided (in addition to the standard memory back-up) is a self-recharging system which allows
the terminal to operate during a power failure. The battery provides power for one and a half net hours of use. A shut
down timeout feature enables the terminal to operate for more extended periods of time.
During a power failure, the user presses the battery key to activate the terminal. Data can then be entered and stored
in the TA-785 memory. The time-out will cause the terminal to shut down automatically after the last use of the
terminal, until the battery key is pressed again.
1.2.1 Memory
As a standard feature, the TA-785 Terminal contains a 512 Kbyte user memory, providing storage for data from more
than 10,000 simple operations. This number depends on the length of the programming tables contained in the
memory, and the complexity of the collected data.
The Alarm light “!”, is located to the left of the display. The alarm light is an
LED that lights when at least half of the memory is used; its blinks when the
memory is almost full.

-4-
2.0 Unpacking and Installation
Note: Do not throw away the box or packing materials.
Check the box and the contents for any signs of damage that may have happened during shipment. Carefully unpack
and check the contents.
The TA-785 package contains:
1 TA-785 terminal
Mounting panel/back plate
10 meter serial cable.
1 RJ-45 -> DB9F connector.
Optional w/Modem: LAN Distribution Box w/6” white cable (Part#620178)
Four Phillips flat head 3.5x30mm and anchors, for terminal mounting purpose.
1 Product CD with the manuals and other tools.
2.1 Location/Site Requirements
The terminal can be installed in any normal office or factory environment. Controlled environments are not required
for proper operation of the terminal. However, installing and operating the terminal under adverse conditions may
affect the functionality of the unit.
2.1.1 Selecting a Location
Consider the following environmental factors that may affect the operation of the terminal, when considering a
location:
•The cable should not be installed near EMI (Electromagnetic Interference) sources, such as:
oMotors, generators, alternators and transformers.
oAir conditioners, elevators, etc.
oRadio/Television transmitters, signal generators and internal communication networks.
•Cables should not be within:
o30 cm. (1 ft.) from 5 KVA power lines or less.
o60 cm. (2 ft.) from 5-10 KVA power lines.
o1.5 meters (5 ft.) of power lines exceeding 10 KVA.
•Cables should not run parallel to power lines for more than 15 m. (49 ft.)

-5-
2.2 Mounting the Terminal
Make sure the unit is unplugged and that it is not connected to the network/PC.
Caution: The terminal should not be mounted where it will be exposed to
extreme heat or cold, water, steam, violent vibrations, high electromagnetic
radiation including high voltage power lines and electrical equipment.
Place the terminal near an easily accessible power source. Select an appropriate location for the terminal. The
recommended height from the floor is 140 cm (4’ 7”).
1. Remove the back/mounting panel.
2. Using the Mounting Panel place the panel onto the wall at the correct height, making sure that the panel is
level.
a. Mark the three holes for the screws for your drilling locations.
i. Drill holes using drill bit size: 0.23” (6 mm) and insert the plastic screw anchors.
b. Options for power cable and communication wiring.
i. If you are running the wiring within the wall that the clock is mounted to, you have the
option of running the cabling through the center hole of the mounting plate.
ii. If you are bringing the cable from outside the wall, there are knockouts located on both
sides of the cable shield of the mounting plate.
Warning: Live wires in the vicinity may contain 115v or 230v. Make sure not to
drill into any electric wires. Failure to heed this warning may result in serious
injury or death.
3. Mount the back plate making sure that the plate is level.
a. Use the screws that came in the kit to complete the mounting of the back plate.
4. Mount terminal by sliding the unit unto the tabs on the back of the terminal.

-6-
a. Note: Before mounting the terminal to the back plate, you will need to plug in the electrical
connection and the communications wires to the bottom of the terminal before sliding the terminal
into place.
3.0 Terminal Configuration
The TA-785 Terminal can be connected to the host computer using either RS-232(Direct), RS-485(LAN), Ethernet
including Wi-Fi or Modem connections.
3.1 Entering Technician Mode
The TA-785 Terminal contains a built in configuration program called Technician mode. Technician mode enables
the set-up of the following options:
Real Time clock I (RTC) calibration
Baud Rate
Fingerprint unit Baud rate
Printer Baud rate
Station ID settings
Modem Rings
Network connection settings
User Field – A field in which the user can fill-in 4 digits that will characterize that terminal
To enter technician mode:
•If the Terminal screen is displaying “NO PROG”.
oPress the
[0]
key 6 times, then press
[Enter]
.
If the clock has a Barcode reader or a Magnetic reader, using a badge with six zeros (000000) will
work as well.
oUse the
[ENTER]
key to move from one screen to the next. To return to the previous screen, use the
[Back Space]
key.
•If the Terminal screen is displaying the date and time.
oSimultaneously press the
and keys 6 times.
If the clock has a Barcode reader or a Magnetic reader, using a badge with six zeros (000000) will
work as well.
oUse the
[ENTER]
key to move from one screen to the next. To return to the previous screen, use the
[Back Space]
key.

-7-
3.2 Communication and Configuration
3.2.1 Communication parameters
Communication between the host and terminals is performed under an asynchronous mode. The baud rate is
programmable, enabling rates from 1200 to 19200 bps.
3.2.2 Multiple terminal configurations
RS-485 communication enables you to connect up to 32 terminals to a single COM port and/or to extend the cabling
distance to up to 1,000 meters (3,280 feet) using 9600 baud via an RS-485 multi-drop line. RS-485 communication uses
three wires as opposed to RS-422 communication, which uses four wires.
3.2.3 Point to point configuration
A single TA-785 terminal, equipped with RS-232 communications, can be connected directly to an asynchronous RS-
232 port. If RS-232 communication is used, only one terminal may be connected to each COM port and cabling
distances should not exceed 50 ft.
3.2.5 Network connections
The terminal can be connected to one of the following communication networks:
Ethernet (optional card)
- For this type of communication, an IP address is defined for every TA-785 terminal, enabling
communication with each terminal in any 10/100 Ethernet network.
Wi-Fi (optional card)
- For this type of communication an SSID is specified to authorize the connection and an IP
address is defined for every TA-785 terminal, enabling communication with each terminal in TCP/IP protocol.
WI-FI Technical Specification Table
Card access current
~5V
Module current
~3.3V
Idle power consumption
200mA
Working power consumption
390~420mA
Ripple on card
6m V P-P
Ripple on module
5m V P-P
Pressure on power source at complete terminal capacity
when using WI-
FI/ internal magnetic reader/ external CCD
reader and FPU.
~7.04V
Complete power consumption at complete terminal capacity
when using WI-
FI/ internal magnetic reader/ external CCD
reader and FPU.
~350mA I(JP11)<1A(~250mA)
I(V1)<<1A(small) I(BAT)~100mA
3.3 Terminal Setup
The following describes the different selections within Technician mode in the TA-785 for RS-232 communications.
In bold on the left is the setting on the clock screen, and in bold on the right is the default setting. Unless otherwise
specified, the settings should always be left at the default values.

-8-
3.3.1 RS-232
•
Adjust the RTC (N/Y): N
oOption is for internal clock calibration purposes.
•
Adjust host baud rate: 19200
o
Note:
If using XactTime, the default baud rate should be 9600.
•
Adjust fingerprint unit baud rate: 57600
•
Adjust printer baud rate: 19200
•
Adjust station ID: 0
oThe Station ID is the TA-785’s unique identifier for multi-terminal communication. Any number from 0 to
31 may be used as the ID, but it must match the ID in the software.
•
Adjust the amount of modem rings: N
oChoose
N
for no rings.
•
Network connection: N
oThe main screen enables three modes:
N
for Serial connection,
A
(not used)
B
(10/100Base) Ethernet, or
E
for using WI-FI.
RS-232 uses the default
N
setting.
•
User Field: ####
oSpecify 4 digits which characterize the terminal.
•
FPU - Setting the fingerprint unit mode N
3.3.1.1 RS-232 Connection
The TA-785 terminal can be connected to the host computer via RS-232 with the DB9 Serial Adapter and a serial
cable. The maximum supported cable length for the serial cable is currently 50’.
When plugging the serial cable into the clock, make sure that it is plugged into the HOST port.

-9-
3.3.3 Ethernet Settings
For this type of communication an IP address is defined for every TA-785 terminal enabling communication with each
terminal in any 10/100 Ethernet network.Unless otherwise noted, the default settings in bold on the right should
always be used.
•
Adjust the RTC (N/Y): N
•
Adjust host baud rate: 19200
•
Adjust fingerprint unit baud rate: 57600
•
Adjust printer baud rate: 19200
•
Adjust station ID: 0
•
Adjust the amount of modem rings: N
•
Network connection: B
oThe main screen enables three modes:
N
for serial connection,
A
(not used)
B
(10/100Base)
Ethernet, or
E
for using WI-FI.
•
Polling (Y/N): N
•
MAC Send (Y/N): N
•
My MAC Address(If Y selected above):############
•
My IP Address:###.###.###.###
oUse the numeric keys to enter the IP Address.
•
Gateway Address:###.###.###.###
oUse the numeric keys to enter the Gateway Address.
•
Remote Address:000.000.000.000
oOption not used, always left at all zeros.
•
Subnet Mask:###.###.###.###
oUse the numeric keys to enter the terminal’s subnet mask.
•
My Port:03734
•
Host Port:03734
•
Disconct Sec:30
oDisconnect seconds defines the number of waiting seconds before reverting to offline mode,
can be set up to a maximum value of 99.
•
DHCP (Y/N): N
o
Note:
TA applications uses static IP addresses for communication, as this feature is not
supported. Should always be set to
N
.
3.3.3.1 Ethernet Connection
When plugging the Ethernet cable into the terminal, use the NET port.

-10-
3.3.4 Wi-Fi Card Settings
Setting the Wi–Fi network connection is done by entering the parameters into the terminal via the keypad.
Some of the parameters are entered in HEX form. To enter the parameters in their HEX form, enter the corresponding
HEX value into the terminal.
In the terminal, HEX alphabetic values are entered using the F-keys. Use the following table for the characters and
there alphabetic values along with the corresponding F-keys.
Char HEX Char HEX Char HEX Char HEX Char HEX Char HEX
0 30 @ 40 P 50 ` 60 p 70
! 21 1 31 A 41 Q 51 a 61 q 71
“ 22 2 32 B 42 R 52 b 62 r 72
# 23 3 33 C 43 S 53 c 63 s 73
$ 24 4 34 D 44 T 54 d 64 t 74
% 25 5 35 E 45 U 55 e 65 u 75
& 26 6 36 F 46 V 56 f 66 v 76
‘ 27 7 37 G 47 W 57 g 67 w 77
( 28 8 38 H 48 X 58 h 68 x 78
) 29 9 39 I 49 Y 59 i 69 y 79
* 2 F1 : 3 F1 J 4 F1 Z 5 F1 j 6 F1 z 7 F1
+ 2 F2 ; 3 F2 K 4 F2 [ 5 F2 k 6 F2 { 7 F2
, 2 F4 < 3 F4 L 4 F4 \ 5 F4 l 6 F4 | 7 F4
- 2 F5 = 3 F5 M 4 F5 ] 5 F5 m 6 F5 } 7 F5
. 2 IN > 3 IN N 4 IN ^ 5 IN n 6 IN ~ 7 IN
/ 2OUT ? 3OUT O 4OUT
_
5OUT o 6OUT 7OUT
•
Adjust the RTC (N/Y): N
oOption is for internal clock calibration purposes.
•
Adjust host baud rate: 19200
oBaud rates: 1200, 2400, 4800, 9600 and 19200.
o
Note:
If using XactTime, the default baud rate should be 9600.
•
Adjust fingerprint unit baud rate: 57600
oBaud rates: 57600, 9600, 19200 and 38400.
•
Adjust printer baud rate: 19200
oBaud rates are: 1200, 2400 and 4800, 9600 and 19200
•
Adjust station ID: 0
oThe Station ID is the TA-780/785’s unique identifier for multi-terminal communication. Any number from 0 to 31 may
be used as the ID, but it must match the ID in the software.
•
Adjust the amount of modem rings: N
oChoose
N
for no rings.
•
Network connection: E
oThe main screen enables three modes:
N
for no connection,
A
(not used)
B
(10/100Base) Ethernet, or
E
for using WI-
FI.

-11-
•
Set/Reset/Exit: E
o
Set
Select S to continue and setup the Wi-Fi settings.
o
Reset
Use this menu to reset the Wi-Fi card and to change the password.
o
Exit
Use this menu option to exit out of the Network Connection settings.
•
Polling (Y/N): N
oOption not used, should always be
N
.
•
MAC Send (Y/N): N
oIf you want to confirm sending your terminal’s network MAC address to the host. Then after exiting technician mode
the terminal will send the host a “Hardware configuration network” message informing it of its MAC address, IP etc.
•
My IP Address (If Y selected above): ###.###.###.###
oUse the numeric keys to enter the IP Address.
•
Gateway Address: ###.###.###.###
oUse the numeric keys to enter the IP Address.
•
Remote Address: 000.000.000.000
oAlways left at all zeros.
•
Subnet Mask: ###.###.###.###
oThe subnet mask is the network address plus the bits reserved for identifying the sub-network. Use the numeric
keys to determine the terminal’s subnet mask affiliation within your local net.
•
My Port: 03734
oTCP/IP enables connecting multiple applications via the same address. The port number selected here is the
application identification number used by the computer when communicating with the terminal. TA applications use
the default port number 3734. However, you may change this according to your specific needs.
•
Host Port: 03734
oTA applications use the default port number 3734. However, you may change this according to your specific needs.
Use the numeric keys to change the port number.
•
Disconct Sec: 30
oDisconnect seconds defines the number of waiting seconds before reverting to offline mode.
•
DHCP (Y/N): N
o
Note:
TA applications uses static IP addresses for communication, as this feature is not supported.
•
SSID (service Set Identifier):
oEntered in HEX form. The sequence of characters identifying the wireless local area network, allowing the stations
to connect to a specific network when multiple independent networks operate in the same physical area.
•
Authentication Method:
oSpecifies the method of authentication. Set by drilling down and selecting the parameters:
Open
•WEP – Enter 4 keys
•WEP Key Number – Specify the number of the key in the sequence of 4 keys.
•WEP Key – Enter the key.
•Wi-Fi WEP – choose:
•None
•64 bit
•128 bit
•
Shared Key:
oSet by drilling down and selecting the parameters.
Open
WEP Key Number – Specify the number of the key on the sequence of 4 keys.
WEP Key – Enter the key.
Wi-Fi WEP – choose:
None
64 bit
128 bit
WEP – Enter 4 keys.
WEP Key Number – Specify the number of the key on the sequence of 4 keys.
WEP Key – Enter the key.
Wi-Fi WEP – choose:
None
64 bit
128 bit
•
WEP (802.1x authorization):
oSet by drilling down and selecting the parameters.

-12-
oWEP
User Name
User Password
•
WPA PSK:
oSet by drilling down and selecting the parameters.
WEP
WEP PSK Password – enter password.
TKIP
WEP PSK Password – enter password.
CCMP
WEP PSK Password – enter password.
•
WPA (802.1x authorization):
oSet by dialing and selecting the parameters.
WEP
User Name
User password
TKIP
User Name
User password
CCMP
User Name
User password
•
LEAP (Cisco LEAP):
oSet by dialing and selecting the parameters.
WEP
User Name
User password
•
Reset: N
oPassword – Used to change the password.
Password – Enter the current password.
•The default password is 0.
Change Password – Enter the new password.
Reset – Returns settings to the factory default.
3.3.4 Resetting the Wi-Fi Card
oTo reset the card:
Step 1
•Disconnect the battery backup cable
Step 2
•Press and hold the reset button for 5 seconds
•Disconnect the main power source, and continue to hold the reset button for an
additional 30 seconds.
Reconnect the main power source; then reconnect the battery backup power.
oThis restart process may need to be repeated more than once.
Step 1
Step 2
Step 3

-13 -
4.0 Terminal Maintenance
4.1 Recovery from Memory Error
If there is a memory error, a
MEM CRASH
message will appear on the terminal screen. You will need to clear the
terminal’s memory and return the terminal to the
NO PROG
(No Programming) state according to the procedure
below.
1.
Press the
[0]
key 6 times.
a. If the clock has a Barcode reader or a Magnetic reader, using a badge with six zeros (000000) will work
as well.
2.
Press the
[ENTER]
key 1 time.
3.
Press the up arrow 3 times.
4.
Press the down arrow 2 times.
5.
Press the up arrow 3 times.
a.
The message “
CLEAR MEMORY
” will appear on the display.
6.
Press the down arrow 2 times.
a.
The message “
MEMORY CLEARER
” will appear on the display.
7. Press the
[CLEAR]
button, and the message “
NO PROG
” will appear on the screen.
4.2 How to Reset the Memory
Warning: This function should be performed by qualified personnel only. It
requires working with an open unit. Make sure to unplug the unit wherever
the instructions call for it. Failure to heed this warning may result in serious
injury or death.
4.2.1 Location of Jumpers
Use the following steps reset the memory, causing a Memory Crash.
1.
Unplug the Terminal and make sure that it is powered off.
a.
The terminal will shut down after 15 seconds of being unplugged from the power.
2.
Unscrew and remove the front panel.
3.
Remove the JP4 jumper from the 1-2 position and place it in the 2-3 position.
4.
Reposition the JP4 jumper back to its original 1-2 position.
5.
Replace the front panel, replacing the screws.
6.
Plug the Terminal back into a power source and make sure that “MEM CRASH” appears in the terminal
display.
7. Follow the steps from section 4.1 on recovering from the “MEM CRASH” state.

-14-
5.0 Field Upgrades and Servicing
One of the many features of the TA-785 terminal is the ability to do field upgrades and servicing. This section
provides an explanation on how to perform the following upgrades:
•Internal Ethernet Card installation
•Internal Wi-Fi Card installation
•POE Card Installation
•Finger Reader Installation
•Proximity Reader Installation
Warning: This function should only be performed by qualified/trained
personnel only. It requires working with an open unit. Make sure to unplug
the unit wherever the instructions call for it. Failure to heed this warning may
result in serious injury or death.
5.1 Procedure – Internal Ethernet Card Installation
NOTE: Refer to the section 3.3.3 for additional information on configuration settings for this option.
1.
Unplug the power cord from the bottom of the Terminal and allow the unit to shut down after the battery
backup takes over. This will last about 20 seconds.
2.
Unscrew and remove the front panel; there are 5 screws on the back side of the terminal.
3.
Locate the connectors that the Ethernet card will be plugging into using the follow image as a reference.

-15-
4. Line up the pins to the connectors on the board. Slide the pins into the connectors until the board rests on
the two screw mounts. Use the image below as a reference for proper card placement.
5. Insert the two screws for the Ethernet card.
6. Replace the front panel, inserting the 5 screws and being careful not to over tighten them.
7. Plug the Terminal back into a power source and make sure that the date/time appears in the terminal
display.
8. Plug the Ethernet cable into the NET port at the bottom of the terminal.
Type B
Type F

-16-
5.3 Procedure – Internal Wi-Fi Card Installation
NOTE: Refer to the section 3.3.4 for additional information on configuration settings for this option.
1.
Unplug the power cord from the bottom of the Terminal and allow the unit to shut down after the battery
backup takes over. This will last about 20 seconds.
2.
Unscrew and remove the front panel; there are 5 screws on the back side of the terminal.
3.
Locate the connectors that the Wi-Fi card will be plugging into using the follow image as a reference.
4.
Line up the pins to the connectors on the board.
Slide the pins into the connectors until the board rests on
the two screw mounts. Insert the two screws that came with the card into the two screw mounts. Use the
image below as a reference for proper card placement.
5.
Using the mounting piece and the zip tie that came with the Wi-Fi card, secure the Antenna to the interior of
the front panel.
6.
Replace the front panel, insert the screws inserting the 5 screws and being careful not to over tighten them.
7.
Plug the Terminal back into a power source and make sure that the date/time appears in the terminal
display.

-17 -
5.4 Procedure – POE Card Installation
Warning: These functions should only be performed by qualified personnel
only. It requires working with an open unit. Make sure to unplug the unit
wherever the instructions call for it. Failure to take the proper precautions
may result serious injury or death.
NOTE: Refer to the section 3.3.3 for additional information on configuration settings for this option.
1.
Unplug the power cord from the bottom of the Terminal and allow the unit to shut down after the battery
backup takes over. This will last about 20 seconds.
2.
Unscrew and remove the front panel; there are 5 screws on the back side of the terminal.
3.
Unplug the connector for the display, and if equipped, the connectors for the fingerprint. See image below
for locations of connectors. You can now move the cover away from the unit.
4.
Disconnect the connectors for the main power and battery backup
a.
If necessary, remove the cover for the battery compartment if it’s in the way.
5.
Remove the 4 screws that hold in the main board. See image below for locations of screws.
Finger unit
connector.
Display connector.
Battery backup
Connector.
Main power connector.

-18 -
6.
Remove the main board from the unit.
7.
Remove the screws from the plastic protection cover on the power board.
Warning: Be very careful when handling the power board, failure to take proper
precautions may result in serious injury or death.
8.
Remove the power cable by loosening the 3 screws for the black, white
and green wires and pulling them from the connectors. Remove the
power cable from the unit.
9.
Remove the two screws from the power board, and then remove the
board from the unit.
10.
Place the power and the new main board into place, using image below as a reference. Insert the two
screws for the power board and the four screws for the main board.
11.
Reconnect the power wire for the backup battery.
12.
Reconnect the cables for the display and if equipped the cables for the Fingerprint.
13.
Replace the front panel and the four screws.

-19 -
5.5 Procedure – Finger Reader Installation
1.
Unplug the power cord from the bottom of the Terminal and allow the unit to shut down after the battery
backup takes over. This will last about 20 seconds.
2.
Unscrew and remove the front panel; there are 5 screws on the back side of the terminal.
3.
Pop out and replace the plug with the holder for the finger reader.
Place the reader into the holder as
shown in the image below.
4.
Place the back of the holder onto the unit, and insert the three screws to hold it place. See image below.
5.
Using two screws, mount the board for the unit onto the two pegs as seen in the image below, and plug the
light from the reader into the clear slot on the holder.
6.
Replace the front panel, insert the screws inserting the 5 screws and being careful not to over tighten them.
7.
Plug the Terminal back into a power source and make sure that the date/time appears in the terminal
display.
Table of contents
Other Synel Touch Terminal manuals