Vers. 2013-0 wall mounted fan coil unit
4
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
INTRODUCTION
RECOMMENDATIONS
Please read this manual carefully before operating the unit.
Pay particular attention to the instructions for use accompanied by the writing
“DANGER” or “CAUTION”, as failure to comply with these instructions could
cause damage to the appliance or property and injury to persons.
For any malfunctioning not contemplated in this guide, immediately contact an
authorised after-sales service centre.
1. Do not store or unpack the unit in a wet area or expose to rain or water, it may
cause the unit short circuit and may result electric shocks or fire.
2. Do not install in a place where flammable gas may leak, it may cause fire.
3. This unit is designed for domestic and commercial use only, if used in cer-
tain enviroments, such as manufacturing workplace, the air conditioner may not
function efficiently
The manufacturer cannot be held liable for any damage or injury caused
by misuse of the appliance or by partial or superficial knowledge of the
information contained in this guide.
- Installations must be performed by a qualified technician.
- Before carrying out installation, put proper individual protection device.
- This air conditioner must be properly installed in accordance with the Instal-
lation Manual.
- Check all local codes and ordinances that could affect installation of this unit.
- Refer to rating plate on each unit for the correct voltage, frequency and cur-
rent.
- Be sure that the power supply corresponds to the specified rating in the na-
meplate.
- Do not use the extension cables. In the case extended cables are needed use
terminal block.
- Refer to dimensional drawings for location of refrigerant tubing, condensate
drain, and electrical connections before setting in place.
- The appliance shall be installed in accordance with national wiring regula-
tions.
THIS PRODUCT MUST BE PROPERLY GROUNDED
Moving machinery and electrical power is hazards it may cause severe injury or
death. Turn off and disconnect the power during installation and repair or any
services attempt to the unit.
Sharp edges and coil surfaces are a potential injury hazard avoid contact with
them.
MAIN COMPONENTS
4. REMOTE CONTROL UNIT
Using this unit make possible to set all operating parameters of the unit, these para-
meter are shown in the LCD display to make the programming operations easier.
5. AIR FILTERS
To trap all dirt and dust coming with the air.
6. EMERGENCY/AUXILIARY SWITCH
Make it possible to turn the unit “ON” or “OFF” in the absence of remote control.
To access it, raise the frontal panel.
7. DISPLAY
Shown the current operating status of the unit, receive signal from remote con-
trol.
8. BASE PAN
The base of the whole unit.
9. FRAME GRILLE
1. FRONTAL PANEL
The air intake is through the slots of the frontal panel. Lifting the frontal panel
you will have the access to the air filter and to the other internal parts.
2. EVAPORATOR COIL
This is made of a copper tube with turbelented type.
3. HORIZONTAL LOUVER
Use to deflect the air from the unit, operated with the step motor.
1. Frontal panel
2. Evaporator coil
3. Horizontal louver
4. Remote control unit
5. Air filters
6. Emergency/auxiliary switch
7. Display
8. Base Pan
9. Frame grille
LOCATION FOR FAN COIL UNIT
WORK LIMITS
Select the location of fan coil unit with following consideration:
1. The front of air inlet and outlet shall be free from any obstruction.
The outlet air should flow out freely.
2. The wall where unit is to be mounted should be strong enough to bear the
weight and not to produce noise.
3. Ensure the clearance on every side of fan coil unit (see drawing below).
Avoid installing the unit in direct sunlight.
Dimensions are in millimeter
HIGHER THAN EYE LEVEL HIGHER THAN EYE LEVEL
FLOOR
LEVEL
1
2
359
8
6
7
4
On
Auto
Auto F
C
am
pm
zz
MODE
SLEEP
SET
LOUVER
LIGHT
SEND
OFF
ON
SWING
150.0
150.0 150.0
150.0
SUMMER (COOLING)
Minimum inlet water temperature +4°C
Maximum operating pressure 15 bar
Maximum room air temperature +35°C
Maximum room air humidity 80%
WINTER (HEATING)
Maximum inlet water temperature +70°C
Maximum operating pressure 15 bar
Minimum room air temperature +4°C
Maximum room air humidity 80%
Maximum room air temperature +35°C