20 | Alarms GB
Alarm name Explanation Do the following
Secondary air damper Secondary air defrosting failed.
Outdoor air temperature sensor
measures < 10°C in 2 sec after
defrosting
OR
Outdoor air temperature sensor
measures < 5°C in 5 min after
defrosting
Check if secondary air damper is in
correct position.
Check that damper is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Outdoor air temperature
sensor
Indicates outdoor air temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Overheat temperature sensor Indicates overheat temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Supply air temperature
sensor
Indicates supply air temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Room air temperature sensor Indicates room air temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Extract air temperature
sensor
Indicates extract air temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Extra controller temperature
sensor
Indicates extra controller
temperature sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Efficiency temperature
sensor
Indicates efficiency temperature
sensor malfunction.
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
PDM RH Indicates internal relative humidity
sensor malfunction.
Active: measured humidity = 0%
Returned: measured humidity > 5%
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
PDM RH Extract air
temperature
Indicates internal extract air
temperature sensor malfunction.
Active: measured temperature = 0°C
Returned: measured temperature >
5°C
Check that sensor is connected
properly and cable is not damaged.
Contact your installation company or
place of purchase.
Filter Time for filter change. Change the filter.
Change filter according to the
instructions in the User Manual.
Details about filter retailers can be
found in Help menu.
Extra controller alarm Error from external device. Check if external device is connected
properly and cable is not damaged.
Reset overheat protection on
electrical pre-heater. Contact your
installation company or place of
purchase.
212194 | A001