System air CD Control Panel User manual

CDControlpanel
ServiceMenu
D2074870-EN_GB
25-04-2012V .A003

Contents
1Operation..................................................................................................................................1
1.1Interfacedescription.........................................................................................................1
1.1.1Controlpanel..........................................................................................................1
2Displaysymbols.........................................................................................................................2
3ServicemenuOverview..............................................................................................................3
3.1SettingTemperature.........................................................................................................7
3.2ManualSettingofFanspeed.............................................................................................7
3.3ManualSummermode......................................................................................................8
3.4Coolrecovery...................................................................................................................8
3.5Softwarecongurationforelectricalheater.........................................................................8

1Operation
1.1Interfacedescription
1.1.1Controlpanel
Belowillustrationshowsthecontrolpanelwithashortdescription(gure1).
Fig.1Controlpanel
PositionDescriptionExplanation
1DisplayShowssymbols,menusandsettings.
2SelectionknobMovethroughthemenulistsorchange
settingsandvaluesbyturningtheknob
leftorright.
3ConrmbuttonConrmmenuchoicesorsettingsby
pressingthebutton.
4BackbuttonStepbackinthemenulevelsby
pressingthebutton.
CDControlpanelServiceMenu
D20748701SystemairAB

2Displaysymbols
SymbolDescriptionExplanation
Temp
Illustratesthecurrentsettemperature.The
temperaturesettingisdonein5steps(fromcompletely
emptytolledsymbol)andcanbechangedmanually
byturningthe“selectionknob”.
Conrmthesettingwiththe“conrmbutton”(chapter
3.1andchapter3.3).
Fanspeed
Illustratesthecurrentsetfanspeed.
Thefanspeedcanbesetmanuallyin3steps(Low,
NomandHigh)byturningtheselectionknoband
conrmingwiththeconrmbuttonaftercompleted
setting.
A
BC
•Lowventilation(A):Canbeusedwhenleavingthe
buildingforalongerperiod.1
•Nominalventilation(B):Willgiverequiredair
changeundernormalconditions.
•Highventilation(C):Toincreasetheairowif
necessary.
ServiceAccesstheservicemenubypressingtheconrm
button.
AlarmAccessthealarmlistbypressingtheconrmbutton.
1.CanbesettoOFFbyactivating“Manualfanstop”.See“Servicemenuoverview”under
“Functions”.
CDControlpanelServiceMenu
D20748702SystemairAB

3ServicemenuOverview
Entertheservicemenubyselectingtheservicesymbolinthedisplay.
Belowoverviewdisplaystheservicemenustructurein3levels.
Menulevel1Menulevel2Menulevel3Explanation
Service
→Password
Password
PasswordXXXX
LockedYES/NO
Entertheservicelevelbytyping1111.Use
theselectionknobforeachdigitandconrm
withtheconrmbuttonaftereachsetdigit.
Service
→Changepassword
Filterperiod
Time/Date
Changepassword
ActualXXXX
NewXXXX
ConfirmXXXX
Setnewpasswordifnecessary.
Incasethenewpasswordwouldbeforgotten
ormisplacedit’sstillpossibletoenterthe
servicelevelbywriting8642.Thisoverrides
theearliersetpassword.
Service
Changepassword
→Filterperiod
Time/Date
Filterperiod
Reset:NO
Timetoreplace9
month
Showsselectedtimeintervalbetweenlter
change.
SetResetofthelterperiodtoYESafter
completedlterchange.
Settimebetweenlterchanges.
Service
Changepassword
Filterperiod
→Time/Date
Time/DateYY/MM/DD
Date:10/05/08
Time:10:00
Weekday:SAT
Showscurrentsetdateandtime.
SetCorrectdateandtime.
Service
→Ext/ForcRun
Weekprogram
Fanspeedlog
Ext/ForcRun
Minutes:0
Fanspeed:
Nominal
Usethisdialogueframetoprogramextended
timeyouwanttheunittoworkunder
operationconditionsotherthandetermined
bytheweekschedule.
Showssettimeforextended/forcedrunning.
ShowsSetfanspeed.
Setthetimeinminutestheunitistorunin
extended/forcedrunningmode.
Setthefanspeedforthismode.Choose
betweenLow,NomorHigh.DefaultisNom.
Service
Ext/ForcRun
→Weekprogram
Fanspeedlog
Weekprogram
Weekprogram
Fanspeed
Weekprogram
DayMON
Per1:07:0016:00
Per2:00:0000:00
Programhowyouwanttheunittooperate
accordingtotheweekschedule.It’spossible
toset2periodsperday.
Setweekdayandtimeintervalforthetime
youwanttheunittobeinONmode.
Fanspeed
ONlevel:
Low/Nom/High
OFFlevel:
OFF/Low/Nom/High
Usethisdialogueframetodeterminethe
ONandOFFspeedforthefansintheweek
schedule.
SetONlevel.
ChoosebetweenLow,NomorHigh.Default
isNom
SetOFFlevel.
ChoosebetweenOFF,Low,NomorHigh.
DefaultisLow.
CDControlpanelServiceMenu
D20748703SystemairAB

Menulevel1Menulevel2Menulevel3Explanation
Fanspeedlog Service
Ext/ForcRun
Weekprogram
→Fanspeedlog
Level:
1–5
SF:140
EF:140
Reset:
No/Yes
/140
/140
Usethisdialogueframetoseehowthefans
haveoperatedduringthetime(h)theyhave
beenactive.
Thespeedsareshownin5differentlevels:
•Level1:0%
•Level2:1–29%
•Level3:30–44%
•Level4:45–59%
•Level5:60–100%
Choosebetweenthelevelstoseethetime
inhoursthefanshavebeenactiveinthe
differentlevels.
ResetYesresetstheSFandEFtimeinthe
leftcolumnforalllevels.Therightcolumn
continuestocountaheadandcannotbe
reset.
Note:
Factoryreset(seeFunc-
tions/Factoryreset)willnot
affectthisfunction.
Service
Weekprogram
Fanspeedlog
→Functions
Functions
→Heater/Cooler
Frostprotection
Airflow
Heater/Cooler
Heater:
None/Electrical/
Water
Cooler:
None/Water
Usethisdialogueframetosetuptheunitfor
heatingand/orcooling.
SetHeatertoNone,Electricalor
Water.
SetCoolertoNoneorWater.
Functions
Heater/Cooler
→Frostprotection
Airflow
Frostprotection
Alarmlimit11°C
Showscurrentsetfrostprotectionalarmlimit
in°Cfortheinstalledwatercoil.
Setalarmlimitin°C.Defaultis7°C.
Service
Ext/ForcRun
Weekprogram
→Functions
Functions
→Airflow
Airflowunit
Manualfanstop
AirflowEFSF
Nom5050
Max107107
Low3030
Usethisdialogueframetosetthefanspeed.
Thespeedcanbesetindividuallyforeach
fan(EF:Exhaustfan,SF:Supplyfan).Max.
diff20%,canbeEFandSF.
SetthefanspeedforEFandSFforeach
step(Low,Nom,andHigh).
Note:
ThevaluesforNom,MaxandLowsuggested
inthisoverviewareexamplesettings.
Functions
Airflow
→Airflowunit
Manualfanstop
Airflowunit
%l/sm3/h
VRunitsl/sdefault
VCunits%only
Functions
Airflow
Airflowunit
→Manualfanstop
Manualfanstop
Allowmanualfan
stopY/N
Setifitshouldbepossibletoturnoffthefans
intheunitmanuallyfromthecontrolpanel.
ChosebetweenYandN.
IfYisselectedthefanscanbeturnedoff
byturningtheselectionknobtoemptyfan
symbol
CDControlpanelServiceMenu
D20748704SystemairAB

Menulevel1Menulevel2Menulevel3Explanation
Functions
→Analoginput
Analogoutput
Digitalinput
Analoginput
1:SS20.0
2:ETS20.0
3:Notused
3:EHS20.0
4:OT/FPS20.0
5:OS10.5
Showsanalogueinputsfromactive
temperaturesensors.
SS:Supplyairtempsensor.
ETS:Extractairtempsensor.
Notused(VCunits)
EHS:Exhaustairtempsensor(VR
units)
OT/FPS:Overheatprotection
sensor/Frostprotectionsensor.
OS:Outdoorairtempsensor.
Functions
Analoginput
→Analogoutput
Digitalinput
Analogoutput
AO1auto/man/off
0.0V
AO2auto/man/off
7.3V
AO3auto/man10V
Showscurrentanalogueoutputsin0–10Vto
hot/coldwateractuatorandbypassdamper.
SetAO1(Analogueoutputtohotwater
actuator)toauto,manoroff.Defaultis
off.
AO2(Analogueoutputtocoldwateractuator)
toauto,manoroff.Defaultisoff.
AO3(Analogueoutputtobypassdamper)to
autoorman.Defaultisauto.(VCunits)
Selectingmanenablestheusertomanually
controltheactuator/damperwitha0–10V
signal.0Vmeanscompletelyclosedand
10Vcompletelyopenedactuator/bypass
damper.Whenusedonthebypassdamper
theunitcanbeforcedtogotosummer
operationorforceddefrosting(10V).
Functions
→Digitalinput
ConfigDI1–3
ConfigDI4–7
Digitalinput
DI1ON/OFF
DI2ON/OFF
DI3ON/OFF
DI4ON/OFF
DI5ON/OFF
DI6ON/OFF
DI7ON/OFF
Showscurrentsettingofthedigitalinputs
ONorOFF
DI1:Fanconguration
DI2:Fanconguration
DI3:Fanconguration
DI4:Heaterstopped
DI5:Extended/forcedrunning
DI6:Dampertest
DI7:Home/leave
Functions
Digitalinput
→ConfigDI1–3
ConfigDI4–7
ConfigDI1–3
1SFhighEFnom
2SFoffEFlow
3SFhighEFhigh
Usethisdialogueframetosethowyouwant
thefanstoreactto3differentdigitalinputs
whentheyareswitchedonoroff(thesettings
inthecolumntotheleftareexamples).
On/offswitchesneedtobeconnected
physicallytoterminalsonthemainprintcard
toobtainthedifferentfunctions.Seethe
wiringdiagramformoreinformation.
Setthesupplyairfan(SF)andextractair
fan(EF)tooff,low,nomorHighfordigital
inputs1–3
CDControlpanelServiceMenu
D20748705SystemairAB

Menulevel1Menulevel2Menulevel3Explanation
Functions
Digitalinput
ConfigDI1–3
→ConfigDI4–7
DI4–7
DI4:Stopheat
DI5:Extrun
DI6:Dampertest
DI7:Home/leave
DI4–7aredefaultsetfromfactoryandcan’t
bechangedbytheuser.Belowfollowsa
shortdescriptionofeachfunction.
DI4:Makesitpossibletoturntheelectrical
re-heaterbatteryonoroff.
DI5:TurntheExtended/forcedrunning
functiononoroffbythehelpofaswitch.The
functionoverridescurrentsetfanspeed.
DI6:Automatictestofthebypassdamper
function.Thisdigitalinputisnotavailablefor
theuser.(VCunits).
DI7:Switchingonthisinputdecreases
thesupplyairtempsetpointwith10K.
Thisfunctionisusedwhenthebuildingis
uninhabitedforalongerperiod.
Note:
The“Home/leave”functionisnotworkingif
Waterheaterisactivated.
Functions
→Digitaloutput
Defrosting
Modbus
Digitaloutput
1:SF67%
2:EF67%
3:Rotormotor
4:AlarmY/N
5:DmpOFF
6:ReheaterY/N
ShowsThecurrentsettingsofdigitaloutputs
1–5(thesettingsinthecolumntotheleftare
examples).
1:SF67%:Currentsetspeedofthe
supplyairfan(shownaspercentageofthe
maximumspeed).
2:EF67%Currentsetspeedofthe
extractairfan(shownaspercentageofthe
maximumspeed).
3:RotorON/OFF:Indicatediftherotor
isactiveornot(VRunits).
3:Notused(VCunits)
4:AlarmY/N:Indicatesifthesum.
alarmisactiveornot
5:DmpOFF:Outdoor/exhaustairdamper
isonoroff(230Vsignalrelay).
6:ReheaterY/N:Indicatesifthe
electricalre-heaterisactiveornot.
Defrosting
Mode0–5
Usethisdialogueframetosethow
aggressiveyouwantthedefrostingfunction
tooperate.
SetVRunits,defrostingmodebetween0–5,
VCunitsbetween1–5.ForVRdefaultis0,
defaultforVCis3.
Functions
Digitaloutput
→Defrosting
Modbus
Allowunbalance
Yes/No
Reducedflow
Active
Bypassdefrosting
Active
Stopdefrosting
Active
OnlyforVCunits.
SetIfyouduringthedefrostingcyclecan
acceptatemporaryunbalanceoftheair
owfromtheunit,i.e.supplyairdecreases.
SelectYESorNO.
Showsifanydefrostingcycleisactive.
Functions
Defrosting
→Modbus
Factoryreset
Modbus
Address:1–247
Baud:9600/19200
Parity:
None/Even/Odd
InformationaboutModbuscommunication
andvariablescanbefoundintheModbus
usermanualforresidentialunitsintheonline
catalogueatwww.systemair.com.
CDControlpanelServiceMenu
D20748706SystemairAB

Menulevel1Menulevel2Menulevel3Explanation
Functions
Defrosting
Modbus
→Factoryreset
Factoryreset
Reallyreset?
Yes/No
Usethisdialogueframetoreturntofactory
settings.
SetYESorNO
Note:
Thiswilleraseallyourpersonalsettingsthat
havebeendonefortheunit.
Service
→Language
Versions
Alarms
Languages
LanguageENGLISH
Usethisdialogueframetoselectyourlocal
language.
SetLanguagebyturningtheselectionknob.
Service
Languages
→Versions
Alarms
VersionVC300
CDEC
Appl.1.08.00
1.22.00
Boot1.00.01
1.01.00
Showscurrentsoftwareversionandunit.
Service
Languages
Versions
→Alarms
Alarms
FanY
EmT/FrostN
Damp/RotN
PbFailN
TempN
FilterY
Showsthealarmlistandwhichalarmshave
beentriggered(indicatedbyY).Seealarm
list.
3.1SettingTemperature
Thesupplyairtemperatureissetmanuallyin5stepsinthemainmenudisplaybychoosingthe
temperaturesymbol(gure2).
Ifanelectricalorwaterre-heaterisinstalledthetemperaturestepsare12.0,14.5,17.0,19.5and22.0
°C.Defaultis12.0°C.
Iftheunitisusedwithoutanyre-heaterinstalledorifthere-heaterisdeactivated,thetemperaturesteps
are15.0,16.0,17.0,18.0or19.0°C.Defaultis15.0°C.
Eachtemperaturestepisillustratedbyincreasingthellingofthetemperaturesymbol.
Fig.2Temperaturesymbol
3.2ManualSettingofFanspeed
It’spossibleatanytimetomanuallysetthefanspeedinthemainmenudisplay.Bychoosingthefan
symbolandconrming(gure3)it’spossibletoincreaseordecreasethefanspeedinthe3steps,Low,
NomandHigh.Bydoingsoyouoverridetheprogrammedweekschedulefortheunituntiltheendof
CDControlpanelServiceMenu
D20748707SystemairAB

thepresenttimeperiodintheweekprogram.CanbesettoOFFbyactivating“Manualfanstop”.See
“Servicemenuoverview”under“Functions”.
Fig.3Fanspeedsymbol
3.3ManualSummermode
Manualsummermodeoccursifonesteplowerthan12°Cisselected.Thetemperaturesymbolonthe
mainmenuisthencompletelyempty(gure4).ForVCunitsthismeansthatthebypassdamperopens
(10VcontrolsignaltooutputDAMPER),forVRunitstherotorstops.Ifthere-heaterisactive,itwill
switchoffduringmanualsummermode.Manualsummermodeabortsautomaticallyaftertwominutesif
thesupplyairtemperatureis≤5°C.
Ifwaterheaterbatteryisinstalledandactivatedthemanualsummermodeisabortediftheoutdoor
airorsupplyairtemperatureis≤5°C.
Fig.4Symbolformanualsummermode
3.4Coolrecovery
Coolrecoveryoccurswhenthereisacoolingneedandtheoutdoorairtemperatureishigherthanthe
extractairtemperature.
3.5Softwarecongurationforelectricalheater
1
Gototheservicemenubyusingtheselection
knob.
2
Entertheservicelevelbytypingthepassword.
Usetheselectionknobforeachdigitandconrm
withtheconrmbuttonaftereachsetdigit.
Password
1111
3
GotoFunctions.
Ext/ForcedRun
Weekprogram
→Functions
CDControlpanelServiceMenu
D20748708SystemairAB

4
ChooseHeater/Cooler.
→Heater/Cooler
Frostprotection
Airflow
5
SelectHeater:Electrical.
Heater:Electrical
Theunitisnowreadytobeusedwiththeinstalledelectricalheater.
CDControlpanelServiceMenu
D20748709SystemairAB

lastpage
SystemairABreservestherighttomakechangesandimprovementstothecontents
ofthismanualwithoutpriornotice.
SystemairAB
Industrivägen3
SE-73930Skinnskatteberg,Sweden
Phone+4622244000
Fax+4622244099
www.systemair.com
D2074870
Table of contents
Other System air Control Panel manuals
Popular Control Panel manuals by other brands

Balboa
Balboa TP200 PANEL user guide

INIM
INIM GameOver SmartLiving 505 Installation and programming manual

Ecolab
Ecolab MU421-P Software manual

Leviton
Leviton EZ-MAX PLUS series installation guide

Parker
Parker PowerStation XT Series user manual

drexel und weiss
drexel und weiss aerosilent topo Operating, Maintenance, Commissioning

Summit Systems
Summit Systems SFC-500 SERIES installation instructions

HotSpring
HotSpring IQ 2020 Quick reference guide

Trane
Trane ComfortLink II XL950 Control user guide

resideo
resideo PROHP-EU installation guide

Alde
Alde Compact 3030 quick guide

Haes
Haes MZAOV-1001 Installation, commissioning & operating manual