
6
The display
shows
x 1
x 1
x 1
x 1
x 3
1.
2.
10.
11.
12.
3.
4.
5.
Value to be changed flashes.
Change of set point for normal flow (1/1) and
for reduced flow (1/2). If the system is confi-
gured to control the flow through the fans, the
unit is m3/h or if the system is configured to
control the pressure in the ducts, the unit is Pa.
6.
7.
The display is lit up
Air control
Selection of supply air fan (SAF)
or exhaust air fan (EAF).
Supply air fan selected as example.
Confirm change of the set point value with
OK.Value to change is flashing.
Confirm selected value with OK.
Confirm change of the set point value with
OK.Value to change is flashing.
Outdoor compensation of the airflow is able
to reduce the air flow when the outdoor tem-
perature is low.Two node points - outdoor
temperature/airflow defines the reduction of
airflow by declining outdoor temperature.The
temperature compensation between the 2
node points is linear.
Select and confirm new value for normal air
flow (1/1) and for reduced air flow (1/2).
To return to the start menu at once
– press and several times.
➞
8.
9.
Follow the steps
below
Setting of flows
SAF (SAF = Supply Air Fan)
EAF (EAF = Exhaust Air Flow
Actual: zzz
Setp: xxx
Setp 1/1: x.xxx m3/h eller Pa
Setp 1/2: y.yyy m3/h eller Pa
Setp 1/1: xxx
Setp 1/2: yyy
Outdoor comp. Setp
aa ˚C = bb m3/h or Pa depending
on conguration
cc ˚C = bb m3/h or Pa depending
on conguration
Danvent DV TIME
2009-03-23 8:03
Syst: Stopped