manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Smoke Alarm
  8. •
  9. System Sensor 1112/24B User manual

System Sensor 1112/24B User manual

D200-63-00 1 I56-931-02
1112/24B and 1112/24BA Ionization
Smoke Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read System Sensor Manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing,
placement, zoning, wiring, and special applications.
Copies of this manual are available at no charge from
System Sensor. (For installation in Canada, refer to
CAN/ULC-S524-M91, Standard for the Installation of
Fire Alarm Systems, and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
Specifications
Diameter: 5.5 inches (140 mm)
Height (including adapter bracket): 1.7 inches (43 mm)
Weight: 5.3 oz. (150 g)
Operating Temperature Range: 32°to 120°F (0°to 50°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Relay Contact Ratings–
Resistive or inductive (60% power factor) load
Form A: 0.5A @ 30VAC/DC
Electrical Ratings
System Voltage nominal: 12 or 24 VDC
Minimum: 8.5 VDC
Maximum: 35 VDC
Maximum Ripple Voltage: 30% of nominal voltage (peak to peak)
Reset Voltage: 0.8 VDC minimum
Standby Current: 50 µA maximum
Alarm Current: 17 mA typical, 23 mA maximum @ 12V
19 mA typical, 25 mA maximum @ 24V
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 60 second reset)
General Description
The 1112/24B and 1112/24BA are 4-wire ionization
smoke detectors that use a state-of-the-art sensing
chamber. These detectors are designed to provide open
area protection.
Installation of these detectors are simplified by the use
of an adapter bracket and a plug-in screw terminal block
that can be prewired to the system, allowing the detec-
tors to be easily installed or removed for cleaning. The
detector sensitivity can be tested in place using the
MOD400R Test Module.
An LED on the detector provides local visual indication of
the detector status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every five seconds. The LED also latches on in alarm.
The 1112/24B also features visual indication that mainte-
nance is required; if the sensing chamber drifts out of its
sensitivity limits, the LED ceases to blink.
D200-63-00 2 I56-931-02
Mounting
Each 1112/24B and 1112/24BA detector is supplied with a
mounting bracket that permits the detector to be mounted:
1. To a single gang box, or
2. Directly to a 3 1/2-inch or 4-inch octagonal box, or
3. To a 4 inch square electrical box by using a plaster ring.
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na-
tional Electrical Code, applicable local codes, and any spe-
cial requirements of the local authority having jurisdiction.
Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
The screw terminal block accepts 14 – 22 gauge wire. For
best system performance, all wiring should be installed in
separate grounded conduit. Do not mix fire system wiring
in the same conduit as any other electrical wiring. Twisted
pair may be used to provide additional protection against
electrical interference.
A78-2336-01
P
W
R
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
–
+
–
P
W
R
+
+
–
–
N.O. C
+
+
–
–
N.O. C
Figure 2. 1112/24B and 1112/24BA detector
mounting bracket:
ALIGNMENT ARROWS
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
Figure 1. Surface mounting 1112/24B and 1112/24BA
detectors on 3 1/2-inch and 4-inch octagonal box:
A78-2563-00
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
A78-2333-02
Figure 3. Wiring diagram for the 1112/24B(A) detector:
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel specifications for the total loop resistance al-
lowed for the control panel being used before wiring the
detector loops.
Wire connections are made by stripping about 1/4inch of
insulation from the end of the feed wire, inserting the wire
into the appropriate terminal, and tightening the screw to
secure the wire in place.
Tamper-Resist Feature
This detector includes a tamper-resist feature that prevents
its removal from the bracket without the use of a tool. To
make the detector tamper-resistant, remove the smaller tab
by breaking it at the scribed line on the tamper resistant tab
on the detector mounting bracket (see Figure 2), then in-
stall the detector. To remove the detector from the bracket
once it has been made tamper resistant, use a small screw-
driver to depress the tamper-resistant tab, located in the
slot on the mounting bracket (see Figure 4), and rotate the
detector counterclockwise.
D200-63-00 3 I56-931-02
Installation
WARNING
Remove power from the control unit or initiating device cir-
cuits before installing detectors.
1. Wire the plug-in screw terminal block per Figure 3 and
plug the terminal block into the detector.
2. Align the arrows on the detector with the arrows on the
mounting bracket.
3. Rotate the detector clockwise in the mounting bracket
until it clicks into place.
4. After all detectors have been installed, apply power to
the control unit or initiating device circuits.
5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity. Be sure to remove dust covers from
any sensors that were left in place during construction as
part of returning the system to service.
A78-2564-01a
Figure 4. Top and side views showing location of test switch:
PUSH RECESSED
SWITCH WITH A
0.1″MAX. DIAMETER TOOL
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,,,,,,,,
A78-2564-00a
I
N
T
A
P
T
O
N
O
D
LED
TEST MODULE
SOCKET RECESSED TEST
SWITCH
Testing
NOTE: Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte-
nance and, therefore, will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following pe-
riodic maintenance. Test the 1112/24B and 1112/24BA as
follows:
A. Test Switch
1. A recessed test switch is located on the detector hous-
ing (See Figure 4).
2. Press and hold the recessed test switch with a 0.1 inch
maximum diameter tool such as an allen wrench or
small screwdriver.
3. The detector’s LED should light within 5 seconds.
B. Test Module (System Sensor Model No. MOD400R).
The MOD400R test module can be used with a DMM or
analog voltmeter to check the detector sensitivity as de-
scribed in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side
of the detector and gently blow smoke through the de-
tector until the unit alarms.
A detector that fails to activate with any of the above tests
should first be cleaned as outlined in MAINTENANCE. If
the detector still fails to activate, return it for repair.
Notify the proper authorities the system is back in operation.
D200-63-00 4 I56-931-02
© System Sensor 1997
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
This smoke detector is designed to activate and initiate emergency ac-
tion, but will do so only when it is used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not
reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large de-
lays in detecting a smoldering fire with either an ionization type detector
or a photoelectric type detector. Either one of them may alarm only after
flaming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a fire developing on another level of a building quickly or at
all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
smoldering type. This is to ensure that both can detect a wide range of
types of fires. Ionization detectors offer a broad range of fire sensing capa-
bility but they are somewhat better at detecting fast flaming fires than
slow smoldering fires. Photoelectric detectors sense smoldering fires better
than flaming fires which have little, if any, visible smoke. Because fires de-
velop in different ways and are often unpredictable in their growth, nei-
ther type of detector is always best, and a given detector may not always
provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires re-
sulting from inadequate fire protection practices, violent explosions, es-
caping gases which ignite, improper storage of flammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smok-
ing in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to dilu-
tion of smoke densities created by frequent and rapid air exchanges. Addi-
tionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic
parts. Even though smoke detectors are made to last over 10 years, any
part can fail at any time. Therefore, smoke detectors shall be replaced after
being in service for 10 years. The smoke detector system that this detector
is used in must be tested regularly per NFPA 72. This smoke detector
should be cleaned regularly per NFPA 72 or at least once a year.
WARNING
The Limitations of Property Protection Smoke Detectors
Maintenance
NOTE: Before removing the detector, notify the proper au-
thorities that the smoke detector system is under-
going maintenance and will be temporarily out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
1. Remove the detector housing by gently prying the four
housing tabs on the bottom of the base with a small-
bladed screwdriver and pull the housing from the base.
2. Vacuum the screen carefully without removing it.
3. Remove the screen by pulling it straight away from the
sensing chamber (see Figure 5).
4. Clean the sensing chamber by vacuuming or blowing
out dust and particles.
5. Replace the screen by sliding it, tab side up, over the
sensing chamber. Make sure that the screen contact
slides into the circuit board contact.
6. Replace the housing by aligning the three triangular slots
on the base with their counterparts on the housing. Gen-
tly press the housing until it locks in place.
REMOVABLE
HOUSING
REMOVABLE
SCREEN
BASE
SENSING
CHAMBER
Figure 5. Removal of cover and screen for cleaning:
A78-2565-01
7. Reinstall the detector.
8. Notify the proper authorities that the system is back in
operation.

This manual suits for next models

1

Other System Sensor Smoke Alarm manuals

System Sensor 22051E-RF User manual

System Sensor

System Sensor 22051E-RF User manual

System Sensor DH400ACDCP User manual

System Sensor

System Sensor DH400ACDCP User manual

System Sensor FAAST LT-200 User manual

System Sensor

System Sensor FAAST LT-200 User manual

System Sensor B402B User manual

System Sensor

System Sensor B402B User manual

System Sensor ECO1003ABLINK User manual

System Sensor

System Sensor ECO1003ABLINK User manual

System Sensor D4P120 User manual

System Sensor

System Sensor D4P120 User manual

System Sensor Innovair Flex DNRE User manual

System Sensor

System Sensor Innovair Flex DNRE User manual

System Sensor DH100 Series User manual

System Sensor

System Sensor DH100 Series User manual

System Sensor 6500S User manual

System Sensor

System Sensor 6500S User manual

System Sensor Innovair DH100LP User manual

System Sensor

System Sensor Innovair DH100LP User manual

System Sensor 5451 User manual

System Sensor

System Sensor 5451 User manual

System Sensor Innovair DH200PL User manual

System Sensor

System Sensor Innovair DH200PL User manual

System Sensor ECO2000 Series User manual

System Sensor

System Sensor ECO2000 Series User manual

System Sensor FAAST LT Use and maintenance manual

System Sensor

System Sensor FAAST LT Use and maintenance manual

System Sensor i4 Series COSMO-2W User manual

System Sensor

System Sensor i4 Series COSMO-2W User manual

System Sensor BEAM1224 User manual

System Sensor

System Sensor BEAM1224 User manual

System Sensor D4P120 User manual

System Sensor

System Sensor D4P120 User manual

System Sensor 2451, 2451TH User manual

System Sensor

System Sensor 2451, 2451TH User manual

System Sensor 2312/24TB User manual

System Sensor

System Sensor 2312/24TB User manual

System Sensor 2112/24S User manual

System Sensor

System Sensor 2112/24S User manual

System Sensor FAAST User manual

System Sensor

System Sensor FAAST User manual

System Sensor BEAM1224SA User manual

System Sensor

System Sensor BEAM1224SA User manual

System Sensor Sounder Base B501BH User manual

System Sensor

System Sensor Sounder Base B501BH User manual

System Sensor Innovair flex D4120A User manual

System Sensor

System Sensor Innovair flex D4120A User manual

Popular Smoke Alarm manuals by other brands

teko Astra-421 RF user guide

teko

teko Astra-421 RF user guide

Polon-Alfa DUR‐4046 Installation and maintenance manual

Polon-Alfa

Polon-Alfa DUR‐4046 Installation and maintenance manual

First Alert 7010B user manual

First Alert

First Alert 7010B user manual

BRK electronic P H O T O & I O N 3120B Technical specifications

BRK electronic

BRK electronic P H O T O & I O N 3120B Technical specifications

pyrexx PX-1C operating manual

pyrexx

pyrexx PX-1C operating manual

Heiman HM-622PS user manual

Heiman

Heiman HM-622PS user manual

SETRONIC VERONA BOOMERANG 5P70 quick start guide

SETRONIC VERONA

SETRONIC VERONA BOOMERANG 5P70 quick start guide

Fire-Lite Alarms BG-12LPS manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LPS manual

Xtralis VESDA-E VES-A10-P installation instructions

Xtralis

Xtralis VESDA-E VES-A10-P installation instructions

Honeywell FMST FXV(E) Series installation manual

Honeywell

Honeywell FMST FXV(E) Series installation manual

NEAT Electronics SMOKE user manual

NEAT Electronics

NEAT Electronics SMOKE user manual

Fire-Lite MS-9600 Supplement

Fire-Lite

Fire-Lite MS-9600 Supplement

EDS OD12R installation manual

EDS

EDS OD12R installation manual

Lexing LX928-N Instruction

Lexing

Lexing LX928-N Instruction

ELRO FS1805M manual

ELRO

ELRO FS1805M manual

Schako RMS manual

Schako

Schako RMS manual

Cooper Wheelock SM87 PBL specification

Cooper Wheelock

Cooper Wheelock SM87 PBL specification

U-Line H-9470 installation instructions

U-Line

U-Line H-9470 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.