manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Switch
  8. •
  9. System Sensor EPS10 Series User manual

System Sensor EPS10 Series User manual

EPS10 Series Alarm Pressure Switches
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
IMPORTANT
Please Read Carefully and Save
This instruction manual contains important information about the installation and op-
eration of alarm pressure switches. Purchasers who install switches for use by others
must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following only those instructions
that apply to the model you are installing.
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems
NFPA 13: Installation of Sprinkler Systems
NFPA 13A: Inspection, Testing, and Maintenance of Sprinkler Systems
Other applicable NFPA standards, local codes, and the requirements of the authority
having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm
condition. System Sensor is not responsible for devices that have been improperly
installed, tested, or maintained.
CAUTION
Do not use in potentially explosive atmospheres. Do not leave unused wires exposed.
SPECIFICATIONS
Contact Ratings: 10 A, 1/2HP @ 125/250 VAC
8 A, 125/250 VAC (LPCB only)
2.5A @ 6/12/24 VDC
Overall Dimensions: See Figure 1
Operating Temperature Range: –40° to +160°F
Maximum Service Pressure: 300 PSI
Maximum Adjustment Range: 4 – 20 PSI
Enclosure Rating: UL 4x — Indoor or Outdoor Use
NEMA 4 — Indoor or Outdoor Use
IP54
Approximate Differential: 3 PSI throughout range
OPERATION
As pressure changes, a diaphragm actuates 1 or 2 snap action switches. The pressure
switch actuation is determined by adjustment settings.
INSTALLATION
1. Remove Cover
Cover is held on by two tamper resistant screws. (Removal key is enclosed with
pressure switch.)
2. Mounting the Switch
The device is designed to be mounted in the upright or horizontal position; side
mounting is also acceptable. Locate it where vibration, shock, and mechanical
loading are minimal. Refer to piping diagram (Figure 2 on page 2).
a. Mount the device directly to the line via the
1⁄2″
NPT pressure connec-
tion. The use of teflon pipe sealant tape is recommended. Be sure the
fitting is tight enough to prevent leaks.
b. Apply tightening torque to the black plastic hex portion of device.
WARNING
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a de-
vice to which AC power is applied. Doing so may result in severe injury or death.
When utilizing switches at voltages greater than 74 VDC or 49 VAC
, means to provide all-pole disconnection must be incorporated in the field wiring,
such as a circuit breaker.
3. Wire the device in accordance with the National Electrical Code. Two
7⁄8″
diameter conduit connection holes have been provided in the mounting
plate to accept standard
1⁄2″
conduit fittings (one is removable knock-out
type). If a NEMA 4/UL 4x (waterproof unit) is required, waterproof flex-
ible metallic conduit and appropriate conduit fittings must be used. Recom-
mended connectors are Thomas and Betts PN 5332 (180° coupling), PN
5352 (90° coupling), and PN 5262 seal ring.
4. Connect wiring to terminals (see Figure 3 and Table 1).
FIGURE 1. PRESSURE SWITCH BASIC DIMENSIONS:
W0170-00
HEX
ADJUSTMENT
SCREW
MAIN ADJUSTMENT
WHEEL
4-1/4"
5-1/8"
LOCKING SCREW
1/2" NPT
COM
AB
GROUND
SCREW
(GREEN)
SWITCH #2
I56-0551-011R
TABLE 1. ELECTRICAL CONNECTIONS
(REFERENCED AT FACTORY SETTINGS):
MODEL EPS10-1 MODEL EPS10-2
A
COM
B
SWITCHES AT 0 P.S.I.
SWITCH AT 0 P.S.I.
SWITCH AT 4-8 P.S.I. (HIGH TRIP PT.)
B
COM
A
B
COM
A
B
COM
A
A
COM
B
A
COM
B
SWITCH 1 BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
SW1 SW2
SW1 SW2
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
1 I56-0551-011R
04-29
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER
MOTOR
GONG
EPS10EXP
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER
MOTOR
GONG
EPS10EXP
DRY
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
WATER
MOTOR
GONG
CHECK
VALVE
EPS10
WET SYSTEM WET SYSTEM DRY SYSTEM
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
TO
SPRINKLER
SYSTEM
TO
SPRINKLER
SYSTEM
TO
SPRINKLER
SYSTEM
FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS10-1, EPS10-2
W0171-01
FIGURE 3. SWITCH TERMINALS:
W0173-00
GROUND
SCREW
COM
B
A
COMMON
TERMINALS
BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.
SWITCH #1
SWITCH #2
SWITCH #2
LOCKING
SCREW
TERMINAL “A”
TERMINAL “B”
EPS10 EPS10
point setting by approximately 2.5 PSI. A reset differential of approximately 3
PSI is typical throughout the entire adjustment range of switch.
4. Retest the set point several times to ensure accuracy of setting.
5. Re-seat locking screw.
TABLE 2.
MODEL
FACTORY SETTINGS (PSI)
Fall
(Low Switch)
Approx.
Reset
Rise
(High Switch)
Approx.
Reset
EPS10-1 — — 4 – 8 3 PSI diff.
EPS10-2 — — 4 – 8 3 PSI diff.
NOTE: The sensor assembly is not field replaceable. Do not attempt to disassemble
these parts. If you have any questions, consult System Sensor. System Sen-
sor recommends careful consideration of the following factors when specify-
ing and installing Alarm Pressure Switches. Always refer to the Installation
and Maintenance Instruction for specific recommendations on individual
devices before installing the unit.
• Electrical ratings stated in literature and on nameplates should not be exceeded.
• Overload on switch can cause failure on the first cycle. Always wire devices
according to national and local electrical codes.
• Install units away from shock and vibration. Proper electrical fittings should be
used to prevent moisture from entering the enclosure via the conduit.
• Test all devices for proper operation after initial installation. Perform preven-
tive maintenance and periodic testing as required by the applicable NFPA
standards but not less than bimonthly.
• Install a back-up control for all critical applications where control failure could
endanger life or property. A backup control to serve as a high or low limit
control is especially recommended for applications where a runaway condition
could result.
• Do not mount unit where ambient temperatures will exceed published limits.
• Avoid impact or mechanical loading.
System Sensor warrants its enclosed pressure switch to be free from defects in materials
and workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this pressure switch.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the pressure
switch which is found to be defective in materials or workmanship under normal use
and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: Honeywell, 12220 Rojas
Please refer to insert for the Limitations of Fire Alarm Systems
THREE-YEAR LIMITED WARRANTY
Drive, Suite 700, El Paso TX 79936, USA. Please include a note describing the malfunc-
tion and suspected cause of failure. The Company shall not be obligated to repair or
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
ADJUSTMENTS TO FACTORY SETTINGS
Both EPS10-1 and EPS10-2 devices are pre-adjusted at the factory to alarm at 4–8
PSI on rising pressure (see Table 2). Pressure switch settings may be adjusted in the
field to obtain a different pressure alarm response from 4 PSI to 20 PSI. The switch
has an override feature on the adjustment mechanism to prevent exceeding the 20
PSI max. setting of the switch. This override feature carries with it a tolerance band
that may limit the upper adjustment to 16–20 PSI. Care must be used when setting
the switch to ensure that the lower limit of 4 PSI is not exceeded. This will allow the
switch to reset within the 3 PSI differential stated.
1. Install pressure switch as stated in “INSTALLATION” portion of instruction
manual. Attach pressure test source to system.
2. Back off locking screw (see Figure 1) to allow main adjustment wheel to rotate
freely.
3. Test trip point by slowly introducing pressure from the pressure test source.
When trip point is found, reduce pressure to zero. Rotate main adjustment
wheel (counterclockwise to increase pressure) and retest until switch trip point
is at the desired pressure setting (4–20 PSI range). Each number represents an
approximate trip point change of 0.2 PSI. One full rotation changes the trip
2 I56-0551-011R
©2016 System Sensor. 04-29

This manual suits for next models

2

Other System Sensor Switch manuals

System Sensor PSP1 User manual

System Sensor

System Sensor PSP1 User manual

System Sensor OSY2 User manual

System Sensor

System Sensor OSY2 User manual

System Sensor PSP1 User manual

System Sensor

System Sensor PSP1 User manual

System Sensor EPS40 Series User manual

System Sensor

System Sensor EPS40 Series User manual

System Sensor EPS40 Series User manual

System Sensor

System Sensor EPS40 Series User manual

System Sensor OSY2 User manual

System Sensor

System Sensor OSY2 User manual

System Sensor EPS40EXP User manual

System Sensor

System Sensor EPS40EXP User manual

System Sensor Zonecheck Keyswitch ZCK-1 User manual

System Sensor

System Sensor Zonecheck Keyswitch ZCK-1 User manual

System Sensor EPS10 Series User manual

System Sensor

System Sensor EPS10 Series User manual

System Sensor PIBVEXP User manual

System Sensor

System Sensor PIBVEXP User manual

System Sensor EPS10 Series User manual

System Sensor

System Sensor EPS10 Series User manual

Popular Switch manuals by other brands

Sapcon COAT-ENDURE instruction manual

Sapcon

Sapcon COAT-ENDURE instruction manual

Turning Point Propellers MasterGuard 501 installation instructions

Turning Point Propellers

Turning Point Propellers MasterGuard 501 installation instructions

Yeastar Technology UF51 5G CPE installation guide

Yeastar Technology

Yeastar Technology UF51 5G CPE installation guide

LIFX Switch manual

LIFX

LIFX Switch manual

Cisco Catalyst 2900 Series XL Hardware installation guide

Cisco

Cisco Catalyst 2900 Series XL Hardware installation guide

Extreme Networks ReachNXT 100-8t user guide

Extreme Networks

Extreme Networks ReachNXT 100-8t user guide

ABB 3299-11500 Instructions for installation and use

ABB

ABB 3299-11500 Instructions for installation and use

H3C SE-S5130 Series installation guide

H3C

H3C SE-S5130 Series installation guide

Siemens 3VW9011-0AH01 operating instructions

Siemens

Siemens 3VW9011-0AH01 operating instructions

Xtralis ADPRO VM22E Technical manual

Xtralis

Xtralis ADPRO VM22E Technical manual

West Mountain Radio RIGrunner 4010S+ manual

West Mountain Radio

West Mountain Radio RIGrunner 4010S+ manual

FS S3150-8T2FP Configuration guide

FS

FS S3150-8T2FP Configuration guide

Aluratek AKSUP02 quick start guide

Aluratek

Aluratek AKSUP02 quick start guide

Planex SWE-0224G2 user manual

Planex

Planex SWE-0224G2 user manual

Market Central Data Deadbolt D1000 Series user manual

Market Central

Market Central Data Deadbolt D1000 Series user manual

TESmart HKS0202A2U user manual

TESmart

TESmart HKS0202A2U user manual

Madas CE-51CM4100 manual

Madas

Madas CE-51CM4100 manual

ALFAtron ALF-SCU91T-N user manual

ALFAtron

ALFAtron ALF-SCU91T-N user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.