THR4-SSERIES POWER SYSTEM
This product accepts a nominal AC Voltage
between 100 and 240 VAC, 47 to 63 Hz,
and produces a regulated output of 10.5-14
VDC capable of delivering a max of 400
Amperes (300 amps continuous) DC for 12V
rectifiers, 21-28 VDC capable of delivering a
max of 200 Amperes DC for 24V rectifiers,
28-42V
capable of delivering a max of 160 amperes
DC for 36V rectifiers, 42-56 VDC capable of
delivering a max of 200 Amperes DC for
48V rectifiers, in an ambient operating tem-
perature range of -40°C to +70°C (depend-
ing upon deployed rectifiers and shelf).
HAZARDOUS
VOLTAGE
AND
ENERGY
LEVELS
ARE
PRESENT
WHICH
CAN
PRODUCE
SERIOUS
SHOCKS
AND
BURNS.
Only authorized, qualified, and trained per-
sonnel should attempt to work on this equip-
ment. Refer to datasheets for full product
specifications.
Observe all local and national electrical,
environmental, and workplace codes.
Each power shelf should be fed from a dedi-
cated AC branch circuit of a Terra Neutral
(TN) power system.
If a line cord(s) is (are) used as the AC
connection means, the plug end of the cord
is considered to be the primary disconnect
means, and reasonable access must be
given to the plug and receptacle area. The
receptacle must be fed with a breaker or
fuse according to Table 4.
For hard-wired AC connections, a readily
accessible disconnect device shall be incor-
porated in the building installation wiring.
Select a wall breaker and wire sizes accord-
ing to Table 4.
CAUTION:
ALL
RECTIFIERS
EMPLOY
INTERNAL
DOUBLE
POLE/NEUTRAL
FUSING
Use double hole, UL listed lugs for all DC
connections to prevent lug rotation and inad-
vertent contact with other circuits.
Class 1 wire is recommended for all DC con-
nections. Minimum wire sizes are shown in
Table 5. In practice, loop voltage drop con-
siderations will usually dictate larger than
minimum safe wire size.
Connection and mounting torque require-
ments are listed in Table 7.
Lambda does not recommend shipping the
rack with the power modules installed. Power
modules should be shipped in separate boxes.
Revision A4 : August, 2009
Page. 3
1
Safety
and
Recommended
Practices
1.1
General
practices
For use in restricted access locations only.
Suitable for mounting on concrete or other non-combustible surfaces